HomeMy WebLinkAboutOrdinance 2627
ORDINANCE NO. 2627
2
4
AN ORDINANCE AMENDING CHAPTER 5 OF THE NORTH
RICHLAND HILLS CODE OF ORDINANCES AND ADOPTING THE
2000 EDITION OF THE INTERNATIONAL ENERGY CONSERVATION
CODE WITH AMENDMENTS RECOMMENDED BY THE NORTH
CENTRAL TEXAS COUNCIL OF GOVERNMENTS AND THE 2001
SUPPLEMENT TO THE 2000 EDITION OF THE INTERNATIONAL
ENERGY CONSERVATION CODE; ESTABLISHING A PENALTY;
AND AUTHORIZING PUBLICATION.
6
8
10
12
WHEREAS, the State of Texas has mandated adoption of the International Energy
Conservation Code, and its adoption, with amendments recommended by the
North Central Texas Council of Governments for this region, will make North
Richland Hills regulations consistent with other area cities; NOW,
THEREFORE,
14
16
18
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF NORTH RICHLAND
HILLS, TEXAS:
20
Section 1:
THAT Chapter 5 ofthe North Rich1and Hills Code of Ordinances be amended
by amending Section 5-5 thereofto read as follows:
22
24
"Section 5-5. International Energy Conservation Code Adopted.
26
THAT the International Energy Conservation Code, 2000 Edition, and the 2001
Supplement to the 2000 Edition of the International Energy Code, published by the
International Code Council in cooperation with Building Officials and Code
Administrators International, Inc.; the International Conference of Building Officials;
and Southern Building Code Congress International Inc., copies of which are on file
with the City Secretary, as amended by the recommended amendments of the North
Central Texas Council of Governments, as further amended by the North Rich1and Hills
amendments thereto, a copy of which amended recommendation is also on file in the
office of the City Secretary is hereby adopted."
28
30
32
34
36
Section 2:
Each violation ofthis ordinance including a failure to correct or comply with an
order the violation shall be punishable by a fine of up to $500.00. Each day any
violation shall continue shall constitute a separate offense punishable hereunder.
Additionally, civil penalties of $1 ,000.00 per day may be sought.
38
40
Section 3:
It is hereby declared to be the intention of the City Council that the sections,
paragraphs, sentences, clauses and phrases ofthis ordinance are severable and,
if any phrase, clause, sentence, paragraph or section of this ordinance shall be
declared unconstitutional or otherwise invalid by the final judgment or decree
42
44
W:\NorthRIcNMdHh\Gener8\Ordln.x:MlJnUEnergyCodeV..Ion2.2000.wpd
1
2
of any court of competent jurisdiction, such invalidity shall not affect any ofthe
remaining phrases, clauses, sentences, paragraphs and sections of this ordinance,
since the same would have been enacted by the city council without the
incorporation in this ordinance of any such invalid phrase, clause, sentence,
paragraph or section.
4
6
Section 4:
Ordinances conflicting herewith are hereby repealed, but only to the extent of
such conflict; remaining portions of such ordinances are hereby saved from
repeal to the extent they do not conflict herewith.
8
10
Section 5:
The City Secretary is hereby authorized and directed to cause the publication of
the descriptive caption and penalty clauses ofthis ordinance as provided by law.
12
14
Section 6:
This ordinance and the rules, regulations, provisions, requirements, orders and
matters established and adopted hereby shall take effect and be in full force and
effect immediately upon passage.
16
18
AND IT IS SO ORDAINED.
20
PASSED AND ADOPTED on this 10th day of June, 2002.
24
CHLAND HILLS
22
26
By:
28
_", Q\~nL.AAI""'11
~'~~ '::.....-.;.:.'<1 /'i
~' .... .... /~
'" .-n e. ~
~~¡ ". --
~ ðf'. TTE,: .\"..)
~~. . i. h.' /.:~.jE
~C;~~
Patricia Hutson, City Secretary
Oscar Trevino, Mayor
30
32
34
36
APPROVED AS TO FORM AND LEGALITY:
G~~/
38
W:\NarthRlchlIrlClHll\G«wll\Otdin....\lnttEnergyCodeV.aIon2.2000.wpd
2
North Central Texas Council of Governments'
Recommended Amendments to the
2000 International Energy Conservation Code
As Amended by the City of North Richland Hills
Section 101.3; amend as follows:
101.3 Compliance. Compliance with this code shall be determined in accordance
with Sections 101.3.1~-and-101.3.2. or 101.3.3.
Add the following item:
101.3.3. Alternative compliance. A building certified through a voluntary
energy performance testing program approved as meeting or exceeding the
provisions ofthis code may be deemed to comply with the requirements ofthis
code.
(Reason: This amendment would encourage participation in above-code programs
and provide an attractive alternative path for unconventional builders who are
committed to quality and efficiency, but concerned about mechanics of code
compliance. NCTCQG will arrange advisory review of such programs.)
Section 302.1; Replace blank Table 302.1 Exterior Design Conditions with the
following:
CONDITION
Winter a, design dry-bulb (OF)
Summera, design dry-bulb COF)
Summer a, design wet-bulb (OF)
Degree days heating b
Degree days cooling b
Climate zone C
(99.6%)
(0.4%)
(0.4%)
VALUE
17
100
78
2407
2603
5B
1
Delete note "a" and replace with thefollowing:
a. These values are from ASHRAE Handbook of Fundamentals for Dallas/Ft.
Worth International Airport 99.6% Winter DB, 0.4% Summer DB, and 0.4%
Summer WB: and from Local Climatological Data for Dallas-Ft. Worth published
by the National Climatic Data Center, National Oceanic and Atmospheric
Administration. These values are for the purpose of providing a uniform basis of
requirements for North Central Texas. This will not preclude licensed
professionals from submitting design analyses based on site measurements or
published data more specific to the building site. Adjustments shall be permitted
to reflect local climates which differ from the tabulated values, or local weather
experience determined by the code official.
(Reason: One of the references in note "a" is in error. The 1997 ASHRAE
Handbook of Fundamentals no longer publishes the design temperature tables in
the format assumed by this reference. The main purpose of this change, however,
is to provide typical design data for the NCTCOG region for ease of reference
within this code.)
Delete Figures 302.1 (1-43, 45-51).
(Reason: There is no need to reference the maps of other states.)
Section 502.1.1; delete exception #2 and substitute thefollowing:
2. Buildings located in Climate Zones 1 through 9 as indicated in Table 302.1. If
a vapor retarder is installed, it is recommended that it be installed on the warm-in-
summer side ofthe thermal insulation.
(Reason: This would eliminate the requirement of a vapor retarder throughout the
NCTCOG region. Eliminating vapor retarders in hot and humid climate zones is
consistent with the recommendation of most building scientists. Although the
omission of a vapor barrier is recommended, it is not the intent ofthe amendment
to prohibit the installation.)
Section 502.1.3; delete item #2:
(Reason: The use of fabricated assemblies to provide air seals creates an
enforcement difficulty in preventing fire hazards due to clearance requirements of
the light fixtures.)
2
------.-----.·--·-_·_____~____.._.__c_~______.__.._____
Section 502.1.5; modify and add exceptions:
502.1.5 Fenestration solar heat gain coefficient. In locations with heating
degree days (HDD) less than 3,500, he combined solar heat gain coefficient (the
area-weighed average) of all glazing fenestration products (illduding thG dfc.cts of
any peÙllall'llt extGl~Or solar shading deviGes) in the building shall not exceed 0.4.
Exceptions:
1. Any glazing facing within 45 degrees of true north:
2. Any glazing facing within 45 degrees of true south which is shaded along its full
width by a permanent overhang with a projection factor of 0.3 or greater.
(Reason: This will allow north facing windows, which do not receive direct solar
radiation, to be exempt from the minimum SHGC requirement; provides a simple
way for south facing windows to effectively achieve summer shade and still
receive some solar heat benefit in. Solar shades are not intended to be utilized to
obtain SHGC requirements due to being non-permanent assemblies.)
Section 502.2; Replace blank Table 502.2 Heating & Cooling Criteria with the
following:
Table 502.2a,g
HEATING AND COOLING CRITERIA
Element Mode Type A-I Type A-2
Residential Residential
Buildings Buildings
Uo Uo
Walls Heating or cooling 0.15 0.22
Roof/ceiling Heating or cooling 0.03 0.03
Floors over unheated Heating or cooling 0.05 0.05
spaces
Heated slab on grade Heating R-value = 6 R-value = 6
Vnheated slab on Heating R-va1ue = 0 R-value = 0
grade
Basement wall Heating or cooling V-factor = 0.15 V-factor = 0.15
Crawl space wall Heating or cooling V-factor = 0.15 V-factor = 0.15
3
Delete Note "a" and replace with thefollowing:
a. The above values have been determined for all counties in the North Central
Texas Council of Governments region.
Add Note "g":
g. These requirements apply only to the boundaries of conditioned space. Air
conditioning equipment is recommended, but not required. to be located within
the conditioned space in North Central Texas zones.
Delete Figures 502.2(1-6)
(Reason: This change unifies the requirements for all counties within the North
Central Texas COG. Reference to the graphs is no longer needed when the values
have been specified.)
Section 502.2; Add note to Fig 502.2(7):
All counties within the North Central Texas Council of Governments region are
designated as within the area of very heavy termite infestation probability for
purpose of uniform interpretation of this requirement.
(Reason: This allows for uniform interpretation of the map throughout the area of
the COG.)
Section 502.2.4; Delete prescriptive Tables 502.2.4(1-9) and substitute the
following:
Replace Tables 502.2.4 (1-6) with:
Table 502.2.4(1)
Prescriptive Building Envelope Requirements, Type A-I Residential Buildings, Based on
Window Area as a Percent of Gross Exterior Wall Area (for zones 5b and 6b)
% Maximum Minimum
Glaiing
Glazing Ceiling Exterior Floor Basement Slab Crawl
U-factor R-value wall R- wall perimeter space
R-value value R-value R-value wall
and R-value
depth
~8% 0.70 R-26 R-ll R-ll R-5 R-O R-6
~12% 0.65 R-26 R-13 R-ll R-5 R-O R-5
4
:::;15% 0.65 R-30 R-13 R-ll R-6 R-O R-7
:::;18% 0.52 R-30 R-13 R-19 R-6 R-O R-7
:::;20% 0.50 R-38 R-13 R-19 R-6 R-O R-7
:::;25% 0.46 R-38 R-16 R-19 R-6 R-O R-7
Replace Tables 502.2.4 (7-9) with:
Table 502.2.4(2)
Prescriptive Building Envelope Requirements, Type A-2 Residential Buildings, Based on
Window Area as a Percent of Gross Exterior Wall Area
% Maximum Minimum
Glazing
Glazing Ceiling Exterior Floor Basement Slab Crawl
U-factor R- wall R- wall perimeter space
value R-value value R-value R-value wall
and R-
depth value
:::;20% 0.55 R-30 R-13 R-ll R-5 R-O R-6
:::;25% 0.55 R-30 R-13 R-ll R-5 R-O R-5
:::;30% 0.47 R-38 R-13 R-19 R-7 R-O R-8
(Reason: This change a) reduces the number oftables to be referenced; b) unifies
envelope prescriptive requirements across all areas within the COG, requiring the
more restrictive values of zones 5b or 6b; and c) eliminates slab edge insulation
requirement. )
Section 503.3.3.3; amend as follows:
All supply and return-air ducts and plenums installed as part of an HV AC air-
distribution system shall be thermally insulated in accordance with Table 503.3.3.3 or
where such ducts or plenums operate at static pressures greater than 2 in. w.g. (500
Pa) in accordance with Section 503.3.3.4.1. Duct insulation products that are
required to meet increased insulation values found in Table 503.3.3.3 ofthe 2001
Supplement to the International Energy Conservation Code are not yet readily
available in the NTCOG region. Until such time as the materials become reasonably
available, the Building Official may authorize alternate materials that substantially
meet these requirements.
(Reason: This change clarifies that requirements for higher pressure ducts are given
elsewhere. These duct systems are typically associated with commercially sized
equipment. This change will be included in the IECC 2001 Supplement.)
5
Section 503.3.3.4; amend subsections as follows:
503.3.3.4.1 High- and medium-pressure duct systems. All ducts and plenums
operating at static pressures greater than 2 in. W.g. (500 Pa) shall be insulated and
sealed in accordance with Section 803.2.8. Iligh µressurG and mediwll pressure
dDucts operating at static pressures in excess of3 in. w.g. (750 Pa) shall be leak
tested in accordance with SMACNA IlV AC Air Duct LcakagG Test Manual with a
rate of air leakage 110t to GXGGGd the maximum rate spcÚfied in that standard. Section
803.3.6. Pressure classifications specific to the duct system shall be clearly indicated
on the construction documents in accordance with the International Mechanical
Code.
503.3.3.4.2 Low pressure duct systems. All longitudinal and transverse joints,
seams and connections of low-pressure supply and return ducts operating at static
pressures less than or equal to 2 in. W.g. (500 Pa) shall be securely fastened and sealed
with welds gaskets, mastics (adhesives), mastic-pIus-embedded fabric systems or
tapes installed in accordance with the manufacturer's installation instructions.
Pressure classifications specific to the duct system shall be clearly indicated on the
construction documents in accordance with the International Mechanical Code.
(Exception is unchanged)
(Reason: These changes, which will be included in the 2001 Supplement to the IECC,
are necessary because the term "low" and "high" have been discontinued by
SMACNA. The modification more clearly delineates the static pressure classification
of duct systems in question.)
Section 802.2; Replace blank tables 802.2 (1-4) with the completed tables provided
as follows. Delete tables 802.2 (5-37).
(Reason: This change provides a unified set of prescriptive requirements for all areas
within the NCTCOG area based upon the most restrictive zone's requirements (5b or
6b). The deleted tables are not necessary after tables 1-4 are completed, and
eliminates data irrelevant to the NCTCOG region.)
TABLE 802.2(1)
BUILDING ENVELOPE REQUIREMENTS
ELEMENT
Skylights (V-factor)
WINDOW AND GLAZED DOOR AREA 10 PERCENT OR LESS OF ABOVE-
GRADE WALL AREA
CONDITIONN ALUE (Zones 5B,6B)
1
6
Slab or below-grade wall (R-
value)
Windows and glass doors
PF < 0.25
0.25 :S PF < 0.50
PF 2: 0.50
Roof assemblies (R-value)
All-wood joist/truss
Metal joist/truss
Concrete slab or deck
Metal purlin with thermal block
Metal pur1in without thermal block
Floors over outdoor air or
unconditioned space (R-value)
All-wood joist/truss
Metal joist/truss
Concrete slab or deck
Above-grade walls (R-value)
Framed
R-value cavity
R-value continuous
CMU, 2: 8 in., with integral
insulation
R-value cavity
R-va1ue continuous
Other masonry walls
R-va1ue cavity
R-value continuous
SHGC
Any
Any
Any
Insulation between
framing
R-19
R-25
NA
R-25
X
Insulation between
framing
R-ll
R-ll
NA
No framing
R-O
U-factor
Any
Any
Any
Continuous insulation
R-16
R-17
R-16
R-17
R-17
Continuous insulation
R-6
R-6
R-6
Wood framing
Metal framing
NA
NA
R-ll
R-O
R-ll
R-O
NA R-O R-O
R-O R-O R-O
NA R-O R-O
R-O R-O R-O
7
TABLE 802.2(2)
BUILDING ENVELOPE REQUIREMENTS
WINDOW AND GLAZED DOOR AREA OVER 10 PERCENT BUT NOT
GREATER THAN 25 PERCENT OF ABOVE-GRADE WALL AREA
ELEMENT
Skylights (U-factor)
Slab or below-grade wall (R-
value)
Windows and glass doors
PF < 0.25
0.25 :S PF < 0.50
PF 2 0.50
Roof assemblies (R-value)
All-wood joist/truss
Metal joist/truss
Concrete slab or deck
Metal purlin with thermal block
Metal purlin without thermal block
Floors over outdoor air or
unconditioned space (R-value)
All-wood joist/truss
Metal joist/truss
Concrete slab or deck
Above-grade walls (R-value)
Framed
R-va1ue cavity
CONDITIONN ALUE
1
R-O
SHGC
0.6
0.7
Any
Insulation between
framing
R-25
R-25
NA
R-30
X
Insulation between
framing
R-ll
R-ll
NA
No framing
U-factor
Any
Any
Any
Continuous insulation
R-19
R-20
R-19
R-20
R-20
Continuous insulation
R-6
R-6
R-6
Metal framing Wood framing
NA
8
R-ll R-ll
R-va1ue continuous
CMU, 2: 8 in., with integral
insulation
R-value cavity
R-value continuous
Other masonry walls
R-va1ue cavity
R-value continuous
NA
R-O
R-O
NA R-ll R-ll
R-5 R-O R-O
NA R-ll R-ll
R-5 R-O R-O
TABLE 802.2(3)
BUILDING ENVELOPE REQUIREMENTS
WINDOW AND GLAZED DOOR AREA OVER 25 PERCENT BUT NOT
GREATER THAN 40 PERCENT OF ABOVE-GRADE WALL AREA
ELEMENT
Skylights (U-factor)
Slab or below-grade wall (R-
value)
Windows and glass doors
PF < 0.25
0.25 ::: PF < 0.50
PF 2: 0.50
Roof assemblies (R-value)
All-wood joist/truss
Metal joist/truss
Concrete slab or deck
Metal purlin with thermal block
Metal purlin without thermal block
CONDITIONN ALUE
1
R-O
SHGC
U-factor
0.4
0.5
0.6
Insulation between
framing
0.7
0.7
0.7
Continuous insulation
R-25
R-25
NA
R-30
X
R-19
R-20
R-19
R-20
R-20
9
Floors over outdoor air or
unconditioned space (R-value)
All-wood joist/truss
Metal joist/truss
Concrete slab or deck
Above-grade walls (R-value)
Framed
R-value cavity
R-value continuous
CMU, 2: 8 in., with integral
insulation
R-value cavity
R-value continuous
Other masonry walls
R-value cavity
R-value continuous
Insulation between
framing
Continuous insulation
R-ll
R-ll
NA
No framing
Metal framing
R-6
R-6
R-6
Wood framing
NA
NA
R-ll
R-O
R-ll
R-O
NA R-ll R-ll
R-5 R-O R-O
NA R-ll R-ll
R-5 R-O R-O
10
TABLE 802.2(4)
BUILDING ENVELOPE REQUIREMENTS
WINDOW AND GLAZED DOOR AREA OVER 40 PERCENT BUT NOT
GREATER THAN 50 PERCENT OF ABOVE-GRADE WALL AREA
ELEMENT
Skylights (U-factor)
Slab or below-grade wall (R-
value)
Windows and glass doors
PF < 0.25
0.25 :5 PF < 0.50
PF 2: 0.50
Roof assemblies (R-value)
All-wood joist/truss
~etaljoist/truss
Concrete slab or deck
Metal purlin with thermal block
Metal purlin without thermal block
Floors over outdoor air or
unconditioned space (R-value)
All-wood joist/truss
~etaljoist/truss
Concrete slab or deck
Above-grade walls (R-value)
Framed
R-value cavity
CONDITIONN ALUE
1
R-O
SHGC
0.4
0.5
0.6
Insulation between
framing
R-25
R-25
NA
R-30
R-38
Insulation between
framing
R-11
R-11
NA
No framing
U-factor
0.7
0.7
0.7
Continuous insulation
R-19
R-20
R-19
R-20
R-20
Continuous insulation
R-6
R-6
R-6
Metal framing Wood framing
NA
11
R-13 R-ll
R-value continuous
CMU, ~ 8 in., with integral
insulation
R-value cavity
R-va1ue continuous
Other masonry walls
R-value cavity
R-va1ue continuous
NA
R-3
R-O
NA,NA R-ll R-ll
R-5 R-O R-O
NA R-ll R-ll
R-5 R-O R-O
Section 805.2.1 Interior Lighting Controls; add a third sentence to read:
Large spaces shall have a separate switch or control for each 2500 square feet of floor
~
(Reason: This change is consistent with energy conservation measures in the 4th
public review ASHRAE 90.1 - 1999, Space Control. This "zoning" is especially
relevant for after-hours employees in office spaces.)
Chapter 9; Replace referenced standard as follows:
ASIIRAD/IDS -- 9J :Energy Code fur Commercial and IIigh-Rise RGsidcntial
Dui1diügs - DasGd on ASIIRAD/ffiS 90.1-1989 - with Revisioüs thru OctobGr 7,1997
including :Ellata and Addendulll 90.1 c-199J
ASHRAE/IES -- 99 Energy Efficient Design of New Buildings Except Low-Rise
Residential Buildings -- 1999 Edition
(Reason: This adopts the most recent edition of the ASHRAE Standard 90.1 as the
reference standard for commercial construction.)
12
INVOICE
Bill To:
CITY OF N RICHLAND HILLS/SECRET
PO BOX 820609
NORTH RICHLAND HILLS, TX 76182-
rï\~ WI Q'J tb "'~(..Q NO
~(Pa...'
Customer ID:
Invoice Number:
Invoice Date:
Terms:
Due Date:
PO Number:
Order Number: 21553159
Sales Rep: 073
Description: CITY OF NORTH RI
Publication Dates: 6/18/02 - 6/19/02
CIT13
215531591
6/19/02
Net due in 21 days
6/30102
Star- Telegram
400 w. 7th Street
FORT WORTH, TX 76102
(817)390-7761
Federal Tax ID 22-3148254
CITY OF NORTl- '~;bks... F~~FftHNI.LS S
= OR[»N~'7~ o.
M ·Ordlnance . ømer1d-
Sales Discount . .~~_~. 5of..:li1:
. Code ~~~
~t~~nft~2ÕÕÕ
InternatiOnal Energy
Conservation Coae
with amendments
recommended bY the
North Central Texas
Council of Govern-
. ments and the 2001
. S IP'8lement to the
2801 Edition of the
Internatlc;mal Ese::RY
:: ~,g~r,f¡~~~gl'1a p~°n.a':
ty' and authorlzmg
- J'ùblication. .
~'Each violation of this
~r ordinance including a
.failure to. correct· or
comply with an order
the . n shall .be
. pu b~,a fme,
_, of I . :.EaCh
13580
55
55 LINE
$6.08
$668.80
($629.20)
Net Amount:
$39.60
~~~n~~fTia~~n~'"
ichlan Hills. Texas'
.. the 10th day of June.
Before me, a Nota . 2002. APPROVED: Çounty and State, this day personally appeared KAREN WILLIAMS, Bid and Legal Coordinator
for the Star-Telegr; Oscar Ti"èvino-MI:\yorr-Telegram, Inc. at Fort Wor. ,in Tarrant County, Texas; and who, after being duly sworn, did depose and say
that the attached c (~:1Jr~~T:. Hut$On.c. ity:!nt was published In the a ve named paper on the Ii~ted tes: BIDS & LEGALS DEPT. STAR TELEGRAM
(817) 390-7182. A~W~~t-~..D... AS ATLO!, OJ" fj
FORM AND LEG -\
'ITY'
~~~~~~ _~. . Staples-At-¡ Signed
SUBSCRIBED AND SWORN TO BEFORE ME, THIS Thursday, June 20, 2002.' I ~ .¡J
Notary Public ''-{)~(.,c - ^. LfbvoOV'--
·"~~,,~'i"';~_''I.,~< :__,,:.!_!..,__~~' - r ,
i¡CKI L. WASON ¡
Thank You F or Your Payment MY COM,\;¡SSION EXPiRES I:
? AUGdST 28, 2004 I'
- - - - - - - - - - - - - - - - - - - - - - - - ~~~~..--.~~ - ~ ~ ~-~_J;-- - - - - - - --