HomeMy WebLinkAboutOrdinance 2610 ORDINANCE NO. 2610 AN ORDINANCE AMENDING CHAPTER 19 OF THE NORTH RICHLAND HILLS CODE OF ORDINANCES, ADOPTING THE 2000 INTERNATIONAL PLUMBING CODE AS AMENDED BY THE RECOMMENDED AMENDMENTS OF THE NORTH CENTRAL TEXAS COUNCIL OF GOVERNMENTS AS THE PLUMBING CODE OF THE CITY OF NORTH RICHLAND HILLS; PROVIDING FOR SEVERABILITY; REPEALING OBSOLETE AND CONFLICTING ORDINANCES; ESTABLISHING A PENALTY; AUTHORIZING PUBLICATION; AND ESTABLISHING AN EFFECTIVE DATE. WHEREAS, the North Richland Hills City Council desires to adopt the 2000 International Plumbing Code with amendments recommended by the North Central Texas Council ofGovemments in order to better provide for the safety of its residents and their property; NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF NORTH RICHLAND HILLS, TEXAS: Section 1: THAT Section 19-3 of the North Richland Hills Code of Ordinances be amended to read as follows: "Sec. 19-3. International Plumbing Code Adopted. The International Plumbing Code, 2000 Edition, as adopted by the International Code Council, Inc., in cooperation with the International Conference of Building Officials, a copy of which is on file in the office ofthe City Secretary, as amended by the recommended amendments ofthe North Central Texas Council ofGovemments, as further modified by the North Richland Hills Technical Code Committee, is hereby adopted by reference and designated as the Plumbing Code of the City of North Richland Hills, the same as though such Code were copied at length herein. " Section 2: Sections 19-4, 19-5, 19-6 and 19-13 of the North Richland Hills Code of Ordinances are hereby repealed. All other Ordinances, or parts of Ordinances in conflict herewith, are hereby repealed to the extent that they are in conflict. Such other Ordinances are hereby saved from repeal to the extent they do not conflict herewith. Section 3: It is hereby declared to be the intention of the City Council that the sections, paragraphs, sentences, clauses and phrases ofthis ordinance are severable and, if any phrase, clause, sentence, paragraph or section of this ordinance shall be declared unconstitutional or otherwise invalid by the W :\NorthRichlandHiIls\General\Ordinances\IntlPlumbingCode2000. wpd Page 1 final judgment or decree of any court of competent jurisdiction, such invalidity shall not affect any ofthe remaining phrases, clauses, sentences, paragraphs and sections ofthis ordinance, since the same would have been enacted by the city council without the incorporation in this ordinance of any such invalid phrase, clause, sentence, paragraph or section. Section 4: Violation of any provision ofthis ordinance or the International Plumbing Code herein adopted, which governs fire safety and public health, shall be punished by a fine of not more than Two Thousand Dollars ($2,000.00). Each day any violation shall continue shall constitute a separate offense. Section 5: The City Secretary is hereby authorized and directed to cause the publication ofthe descriptive caption and penalty clauses ofthis ordinance two times. Section 6: This Ordinance shall become effective immediately upon passage. AND IT IS SO ORDAINED. PASSED on the 25th day of March, 2002. CITY OF NORTH RICHLAND HILLS æL By: Charles Scoma, ~J?-ònn ~dlrt: George A. StaPl~ .W:\NorthRichlandHiIls\General\OrdinancesllntlPlumbingCode2000 wpd Page 2 Recommended Amendments to the 2000 International Plumbing Code North Central Texas Council of Governments region (As modified by the North Richland Hills Technical Code Committee) **Table of Contents, Chapter 7, Section 714; change to read as follows: Section 714 Engineered Computerized Drainage Design. . . .. . . . . . . . . . . . . . . 60 **Section 102.8; change to read as follows: 102.8 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 13 and such codes. when specifically adopted. and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where the requirements of reference standards or manufacturer's installation instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards. each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. **Section 305.6.1; change to read as follows: 305.6.1 Sewer depth. Building sewers th3t connoct to private WW3g0 dispOS31 systom Sh311 bo a minimum of [number] inches (mm) bolow finishod gr3de 3t the point of wptic t3nk connection. Building sewers shall be a minimum of.12 inches (304 mm) below grade. **Section 305.9; change to read as follows: 305.9 Protection of components of plumbing system. Components of a plumbing system installed within 3 feet along alleyways, driveways, parking garages or other locations in a manner in which they would be exposed to damage shall be recessed into the wall or otherwise protected in an approved manner. **Sectíons 312.9.1 and 312.9.2; change to read as follows: 312.9.1 Inspections. Annual inspections shall be made of all backflow prevention assemblies and air gaps to determine whether they are operable. In the absence of local provisions. the owner is responsible to ensure that testing is performed. 312.9.2 Testing. Reduced pressure principle backflow preventer assemblies, double check-valve assemblies, double-detector check valve assemblies and pressure vacuum breaker assemblies shall be tested at the time of installation, immediately after repairs or relocation and at least annually. The testing North Central Texas 2000 IPC amendments February 2001 procedure shall be performed in accordance with applicable local provisions. In the absence of local provisions. the owner is responsible to ensure that testing is done in accordance with one of the following standards: {list of standards unchanged} **Section 314.2.1; modify second sentence to read as follows: 314.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Condensate shall not discharge in a publicly exposed area such as into a street, alley. sidewalk or other areas so as to cause a nuisance. **Section 314.2.2; add a second paragraph to read as follows: Condensate waste pipes from air-cooling coils may be sized in accordance with equipment capacity as follows: Equipment Capacity in tons of refrigeration Up to 20 tons Over 20 to 40 tons Over 40 to 90 tons Over 90 to 125 tons Over 125 to 250 tons Minimum Condensate Pipe Inside Diameter 3/4 inch 1 inch 1 1/4 inch 1 Y2 inch 2 inch The size of condensate waste pipes may be for one unit or a combination of units. or as recommended by the manufacturer. The capacity of waste pipes assumes a 1/8-inch-per-foot slope. with the pipe running three-quarters full. **Section 314.2.3; add item #4 to read as follows: 4. Discharge. as noted. shall be to a conspicuous point of disposal to alert occupants in the event of a stoppage of the drain. However. the conspicuous point shall not create a hazard such as dripping over a walking surface or other areas so as to create a nuisance. **Section 401.1; add a sentence to read as follows: The provisions of this Chapter are meant to work in coordination with the provisions of the Building Code. Should any conflicts arise between the two chapters. the Code Official shall determine which provision applies. North Central Texas 2000 IPC amendments 2 February 2001 **Add Section 403.1.2 to read as follows: 403.1.2 Finish material. Finish materials shall comply with Section 1209 of the International Building ~ **Section 404.2; change to read as follows: 404.2 Unisex toilet and bathing rooms. In assembly and mercantile occupancies, an accessible unisex toilet room shall be provided where an aggregate of six or more male or female water closets are requirod provided. In buildings of mixed occupancy, only those water closets. . . {remainder of section unchanged} **Section 405.6; delete. **Section 409.2; change to read as follows: 409.2 Water connection. The water supply to a commercial dishwashing machine shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608. **Section 410.1; change to read as follows: 410.1 Approval. Drinking fountains shall conform to ASME A112.19.1, ASME A112.19.2 or ASME A 112.19.9, and water coolers shall conform to ARI1 01 O. Whore w3ter is eerved in rostaurants or whoro bottlod w3tor coolers 3ro providod in other occupancies, drinking fountains Sh311 not bo roquirod. Exception: A drinking fountain need not be provided in a drinking or dining establishment. **Section 412.4; change to read as follows: 412.4 Required location Public laundries and contral washing facilitios. Floor drains shall be installed in the following areas. .1. In public coin-operated laundries and in the central washing facilities of multiple family dwellings, the rooms containing the automatic clothes washers shall be provided with floor drains located to readily drain the entire floor area. Such drains Sh311 havo 3 minimum outlot cross 8Oction of not loss than 3 inches (76 mm) in diametor. 2. Commercial kitchens. (In lieu of floor drains in commercial kitchens. the code official may accept floor sinks.) 3. Public toilet rooms containing two or more water closets or a combination of one (1) water closet and one (1) urinal. Floors of such rooms shall slope toward the floor drain. North Central Texas 2000 IPC amendments 3 February 2001 **Section 413.4; change to read as follows: 413.4 Water supply required. All food waste grinders shall be provided with a supply of cold water. The water supply shall be protected against backflow by an air gap or with the installation of a backflow preventer in accordance with Section 608. **Section 417.5; change to read as follows: 417.5 Shower floors or receptors. Floor surfaces shall be constructed of impervious, noncorrosive, nonabsorbent and waterproof materials. Thresholds shall be a minimum of 2 inches (51 mm) and a maximum of 9 inches (229 mm). measured from top of the drain to top of threshold or dam. Thresholds shall be of sufficient width to accommodate a minimum twenty-two (22) inch (559 mm) door. Exception: Showers designed to comply with ICC/ANSI A117.1. **Section 417.5.2; change to read as follows: 417.5.2 Shower lining. Floors under shower compartments, except where prefabricated receptors have been provided, shall be lined and made water tight utilizing material complying with Sections 417.5.2.1 through 417.5.2.4. Such liners shall turn up on all sides at least~~ inches (51 mm) above the finished threshold level and shall extend Qutward over the threshold and fastened to the outside of the threshold iamb. Liners shall be recessed and fastened to an approved backing. . . {remainder of section unchanged} . . . . **Add Section 417.7 to read as follows: 417.7 Test for shower receptors. Shower receptors shall be tested for water tightness by filling with water to the level of the rough threshold. The drain shall be plugged in a manner so that both sides of pans shall be subjected to the test at the point where it is clamped to the drain. **Section 419.3; change to read as follows: 419.3 Surrounding material. Wall and floor space to a point 2 feet (610 mm) in front of a urinal lip and 4 feet (1219 mm) above the floor and at least 2 feet (610 mm) to each side of the urinal shall be waterproofed with a smooth, readily cleanable, hard. nonabsorbent material. **Section 502.5; change to read as follows: 502.5 Water heaters installed in attics. Attics containing a water heater shall be provided. . . {bulk of paragraph unchanged} . . . side of the water heater. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), or larger where such dimensions are not large North Central Texas 4 February 2001 2000 IPC amendments enough to allow removal of the water heater. **Add Section 502.5.1 to read as follows: 502.5.1 Electrical requirements. A lighting fixture controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the equipment location in accordance with the electrical code. **Add Section 502.7 to read as follows: 502.7 Water heaters above ground or floor. When the attic. roof. mezzanine or platform in which a water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor level. it shall be made accessible by a stairway or permanent ladder fastened to the building. 502.7.1 Whenever the mezzanine or platform is not adequately lighted or access to a receptacle outlet is not obtainable from the main level. lighting and a receptacle outlet shall be provided in accordance with Section 502.5.1. **Section 504.6.1; change to read as follows: 504.6.1 Discharge. The relief valve shall discharge through full size pjQjng to a safe place of disposal such as ª tHe floor drain, outside the building, or an indirect waste receptor. The discharge pipe shall not have any trapped sections. When the drain pipe run is exposed. in an area outside of the room where the water heater is located. in a manner that would make it subject to damage. the drain aAfi shall have a visible air gap or air gap fitting located in the same room as the water heater. The discharge shall be installed in a manner that does not cause personal injury to occupants in the immediate area or structural damage to the building. The end of the discharge pipe shall not be threaded. The discharge pipe shall not discharge into the pan required in Section 504.7. When discharging outside the building. the point of discharge shall be with the end of the pipe not more than two (2) feet (610 mm) nor less than six (6) inches (152 mm) above the ground or the floor level of the area receiving the discharge and pointing downward. **Section 505.1; change to read as follows: 505.1 Unfired vessel insulation. Unfired hot water storage tanks shall be insulated so that heat loss is limited as specified in Section 504. International Energy ConseNation Code. {delete remainder of section} North Central Texas 2000 IPC amendments 5 February 2001 **Add Section 506, 506.1 to read as follows: SECTION 506 COMBUSTION AIR AND VENTILATION 506.1. Combustion air and ventilation. Combustion air and ventilation for fuel burning water heaters. other than gas-fired. shall be in accordance with the International Mechanical Code. Combustion air and ventilation for gas-fired water heaters shall be in accordance with the International Fuel Gas Code. **Add Section 604.4.1 to read as follows: 604.4.1 State maximum flow rate. Where the State mandated maximum flow rate is more restrictive than those of this section. the State flow rate shall take precedence. **Amend Section 604.9 to read as follows: Section 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick- closing valves are utilized, unless otherwise approved. Wator hammer 3rrostors Sh311 be inet3110d in accordance with tho m3nuf3cturor's spocifications. W3torh3mmor 3rrostors shall conform to ASSE -iQ..W... **Tables 605.4 and 605.5; delete "Polybutylene (PB) plastic pipe and tubing". **Amend Section 605.5 to read as follows: Section 605.5-Water distribution pipe. Water distribution pipe shall conform to NSF 61 and shall conform to one of the standards listed in Table 605.5. All hot water distribution pipe 3nd tubing shall have a minimum pressure rating of 100 psi (690 kPa at 180°F (82°C). Plastic pipe. tubing or similar type materials shall be prohibited from use for water distribution inside any building or residence. with the following exceptiuons: Exception #1: Plastic pipe or tubing not exceeding three-eighths ( ) inch in diameter and not exceeding fifteen (15) feet in length shall be allowed for use on a refrigerator ice maker. Exception # 2: Plastic pipe or tubing not exceeding twenty-four (24) inches in length shall be allowed between a shutoff valve and an appliance or device. **Section 606.1; delete items #4, 5 and 6. North Central Texas 2000 IPC amendments 6 February 2001 DATE, TIME FAX NO./NAME DURATION PAGE(S) RESULT MODE TRANSMISSION VERIFICATION REPORT 03/05 10:35 5707 00:03:19 11 OK STANDARD ECM TIME 03/05/2004 10:39 NAME ÉÈÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ FAX 00000000000 TEL 000000000000 **Section 606.2; items #1 and 2 change to read as follows: 1. On the fixture supply to each plumbing fixture.. in othor than one and two family 3nd multiplo f3mily residonti31 occupancies, and othor than in individu31 guo&trooms that 3re providod with unit shutoff valvos in hotels, motels, boarding houws :md similar occup3ncios. Exception: Tub and shower valves. 2. On the water supply pipe to each sillcock when subject to freezing. **Section 607.2.1; change to read as follows: 607.2.1 Piping insulation. Piping in required return circulation systems shall be insulated as required in Section 504. International Energy Conservation Code. {delete remainder of section} **Section 608.1; change to read as follows: 608.1 General. A potable water supply system shall be designed, installed and maintained in such a manner so as to prevent contamination from non potable liquids, solids or gases being introduced into the potable water supply through cross-connections or any other piping connections to the system. Back flow preventer applications shall conform to applicable local regulations. Table 608.1, ~ and as specifically stated in Sections 608.2 through 608.16.9. **Section 608.17; change to read as follows: 608.17 Protection of individual water supplies. An individual water supply shall be located and constructed so as to be safeguarded against contamination in accordance with applicable local regulations. In the absence of other local regulations. installation shall be in accordance with Sections 608.17.1 through 608.17.8. **Section 708.3.4; change to read as follows: 708.3.4 Upper terminal Ba60 of stack. Each horizontal drain shall be provided with a cleanout at its upper terminal ^ cloanout shall bo providod 3t the baw of ooch W3Sto or soil stack. Exception: Clean outs may be omitted on a horizontal drain less that five (5) feet (1524 mm) in length unless such line is serving sinks or urinals. Amend Section 710.1 to read as follows: Section 710.1 - The maximum number of drainage fixture units connected to a given size building sewer, building drain or horizontal branch of the building drain shall be determined by using Table 710.1 (1), however. no exterior waste. sewer or drainage piping that is connected to a city sewer main shall be less North Central Texas 7 February 2001 2000 IPC amendments thanfour (4) inch inside diameter pipe. nor less than schedule 40 pipe. This minimum four inch piping shall be continuous from the building or structure to the city main. The maximum number of drainage fixture units connected to a given size of horizontal branch or vertical soil or waste stack shall be determined using Table 710.1 (2). **Add Section 712.5 to read as follows: 712.5 Dual Pump System. All sumps shall be automatically discharged and. when in any "public use" occupancy where the sump serves more than 10 fixture units. shall be provided with dual pumps or ejectors arranged to function independently in case of overload or mechanical failure. For storm drainage sumps and pumping systems. see Section 1113. **Section 714, 714.1; change to read as follows: SECTION 714 ENGINEERED COMPUTERIZED DRAINAGE DESIGN 714.1 Design of drainage system. The sizing requirements for plumbing drainage systems shall be determined by approved computor progr3m design methods. **Section 802.1.1; delete the exception. **Section 802.4; add a sentence to read as follows: No standpipe shall be installed below the ground. **Section 904.1; changed to read as follows: 904.1 Roof extension. All open vent pipes that extend through a roof shall be terminated at least six (6) inches (152 mm) above the roof, except that where a roof is to be used for any purpose other than weather protection. the vent extensions shall be run at least 7 feet (2134 mm) above the roof. **Section 912.1; change to read as follows: 912.1 Type of fixture. A combination drain and vent system shall not serve fixtures other than floor drains, standpipes, siAAs-and 13v~tories indirect waste receptors. Combination drain and vent systems shall not receive the discharge of a food waste grinder. **Section 912.2; change to read as follows: North Central Texas 8 2000 IPC amendments February 2001 912.2 Installation. The only vertical pipe of a combination drain and vent system shall be the connection between the fixture drain of a sink, 13v3tory or standpipe, and the horizontal combination drain and vent pipe. The maximum vertical distance shall be 8 feet (2438 mm). **Section 1106.1; change to read as follows: 1106.1 General. The size of the vertical conductors and leader, building storm drains, building storm sewers, and any horizontal branches of such drains or sewers shall be based on six (6) inches per hour the 100 yom hourly rainfall rate indicated in Figura 1106.1 or on othor rainf311 r3tes detorminod from 3pprovod local w03thor dat3. **Section 1107.3; change to read as follows: 1107.3 Sizing of secondary drains. Secondary (emergency) roof drain system shall be sized in accordance with Section 1106 b3wd on the rainf311 r3to for which tho primary systom is sizod in Tables 1106.2, 1106.3 3nd 1106.6 by two. Scuppers shall be sized to prevent the depth of ponding water. . . {remainder of section unchanged} . . . . **Chapter 12; delete. END North Central Texas 2000 IPC amendments 9 February 2001 INVOICE Star- Telegram 400 W. 7th Street FORT WORTH, TX 76102 (817) 390-776] Federal Tax ID 22-3148254 Customer ID: Invoice Number: CIT13 212497441 4/1/02 Net due in 21 days 3/31/02 Bill To: CITY OF N RICHLAND HILLS/SECRET PO BOX 820609 NORTH RICHLAND HILLS, TX 76182-' P&\e ~I ~v'tt V\ I.N'\'~ -¡ Cop \ 0 Invoice Date: Terms: Due Date: PO Number: Order Number: 21249744 Sales Rep: 073 Description: ORDINANCE NO.2 Publication Dates: 3/29/02 - 4/1/02 ORDINANCE NO. 2610 An ordinanc 13580 59 59 LINE $6.08 $717.44 Sales Discount ($675.68) SUBSCRIBED AI', C I'n~~~p) bln~ CøI;II' a. amend, ed 111. recommended ..mepdm.nts of'thI' North Central 'T.xa. Có ,l!1cll of Govern- ment. as tha Plumb- In.a Coda of the 'CIW or North 'Rlchlal1C1 Hilla; providing. fOr sg~r:~IItY~:r.~~~ ~Ictlng ordinance.; e1Stabllshlng .. panal- W; authoriZing pubU- óatlon; and 'estab- lishing an effective date. V~?~~tlgrt~~ ~~IÆ~~~ or thlil Internstronal Pi,mbllngC,øI;IS h,e,re,ln a ted, .whlChgQV- ern fire ,1Iaftít1~~.CJ pule t¡ealth.,., It pun .he<l bY"" more m~wo "nd ,.' r. .M8a.OO1. eac WI( violatIOn shall Inue shall conatl- a separate of- ed nd p.',..,., .d County and State, this day personally appeared Christy Holland, Bid and Legal Coordinator 'b~y.1ty ',,<!F, ,,',..,.,.,...,'tar-Telearam, Inc. at FLtrt , In Tarrant County, Texas; and WhO". after beln,K dUlY, sworn, d Iddepose and say ~dd~~I~~ .. 'ment was published In th aiJie med paper on the IIstZ)dates: iZlDS LEGAL DEPT. STAR TLEGRAM APPRæ.g j :~~~~.~ Signed ~')' a-ê I ¿¿A/LV "'-- HUt80!l. .'-.; HUte~ AnD t~, lE ME, THIS Friday, April 12, 200'. / -/. of I 6:~~~. Notary Public Y.! £t!-~ ~ /VI) /\ the CIW '. V(/'-'t./ r '-- Net Amount: $41.76 THE STATE OF County of Taml' Before me, a No- for the Star- Tele that the attached' (817) 390-71 f - - - ~ - - -..--.--- ~~ VICKI L WASON -jt MY COMMISSION EXPIRES i' Thank You F or Your Payment AUGUST 28, 2004 Ii __________________________..:.:.::;:\c-~~i,=-= __._~J _______ Remit To: Star-Telegram P.O. Box 901051 FORT WORTH, TX 76101-2051 Customer ID: Customer Name: Invoice Number: Invoice Amount: PO Number: Amount Enclosed: CIT13 CITY OF N RICHLAND HIL 212497441 $41.76 r$~'''''·-''''-'''''''''-''~''- ,~.. ¡ -'''''-'''''''1 Star-Telegram 400 W. 7th Street FORT WORTH, TX 76102 (817) 390-7761 Federal Tax ID 22-3148254 INVOICE Customer ID: Invoice Number: Invoice Date: Terms: Due Date: PO Number: Order Number: Sales Rep: Description: Publication Date: CIT13 212601231 3/31/02 Net due in 21 days 3/31/02 Bill To: CITY OF N RICHLAND HILLS/SECRET PO BOX 820609 NORTH RICHLAND HILLS, TX 76182- FT' \e ~I bV £t..... ~.&Q ~...' tI Attn 21260123 073 ORDINANCE NO.2 3/31/02 ORDINANCE NO. 2610 An ordinanc ORDINANcE' NO. '" ,:ønb. ~g~pt«-1~ Nðrth Alchlañd "'i-ÌÌri; Code of Ordinance. adopting the 2000 Internatfonal PllJmb- Ing Code as amended by the recommended Il.mendments of the! NOrth Central Texas Council of Govern. ¡nents as the PllJmb- , ~~.rh of ~~~hl~~~ HII,,; providing for .Eaö/llty; repealing lete and con- "'~shln~dk'~~';¡.1.: ty; a,uthoriZln9i! ~; snd . ~g an eff THE STATE OF TEXAS County of Tarrant 13580 59 LINE $0.00 59 ~, 'itJi,~., to .:=rect~'Wf1!Ch .~- ewflre ..fetv publ health, sliall punl~.Ø bV a fine' . " not more \han T.... Thousand Dot ($.2.000,',001. ead1. any violation s èontlnue shatl co tute a separate '. fense. PaS$ed ~rd ð'pp~~, , fJe 1heClt ty ofU~ AIChlan~ Hills, T..- .~th daY of M&'íIff~ "_"" h~~:sA~=, ';\:\,. . .. scoma~~, "';,' ~T' '-.{ ·'.'..,."C,IS HI', tSO,n ... ',,' Hutson'vltý' ~~D AS TO AND LEGAL- t ,;, _9 Staples Staples- " . ' for the City Net Amount: $0.00 Before me, a Notary Public In and for said County and State, this day personally appeared CHRISTY L. HOLLAND, Bid and Legal Coordinator for the Star-Telegram, published by the Star-Telegram, Inc. at For rth, In Tarrant County, Texas; and who, after being duly sworn, did depose and say that the attached clipping of an advertisement was published In e a v amed paper on the IiVte dates: BIDS LEGALS DEPT. STAR T EGRAM (817) 390-7182. . Signed SUBSCRIBED AND SWORN TO BEFORE ME, THIS Wednesday, AP~llcr2f2.~ ï ~ v1 Notary Public uJ-(!AJ. Ot ~ ~~'~<:f~~~~/: ,', 'VI ~-KI- (;, ~;o~ :'=--4,1 ¡ ~'~o~~_;:~;_ ~ ~~YouForYou~pa~em______________,I~~:Y::;;~~___ Customer ID: Customer Name: Invoice Number: Invoice Amount: PO Number: Amount Enclosed: CITB CITY OF N RICHLAND HIL 212601231 $0.00 Remit To: Star-Telegram P.O. Box 901051 FORT WORTH, TX 76101-2051