Loading...
HomeMy WebLinkAboutOrdinance 2590 ORDINANCE NO. 2590 AN ORDINANCE OF THE CITY OF NORTH RICHlAND HillS, TEXAS, ADOPTING THE 2000 EDITION OF THE INTERNATIONAL RESIDENTIAL CODE, REGULATING THE ERECTION, CONSTRUCTION, ENLARGEMENT, ALTERATION, REPAIR, MOVING, REMOVAL, DEMOLITION, CONVERSION, OCCUPANCY, EQUIPMENT, USE, HEIGHT, AREA AND MAINTENANCE OF ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES IN THE CITY OF NORTH RICHLAND HilLS; PROVIDING FOR THE ISSUANCE OF PERMITS AND COLLECTION OF FEES THEREFOR; PROVIDING FOR PENALlTIES FOR THE VIOLATION THEREOF; PROVIDING A SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY OF FINE NOT TO EXCEED THE SUM OF $200.00 FOR EACH OFFENSE; AND PROVIDING AN EFFECTIVE DATE. BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF NORTH RICHLAND HILLS, TEXAS: SECTION 1. That the 2000 International Residential Code, a copy of which is on file in the office of the City Secretary, be, and is hereby adopted as the residential building code of the city, which governs the construction of One- and Two-Family Dwelling Units in the City of North Richland Hills, Texas. SECTION 2. The following sections of 2000 International Residential Code, are amended and adopted to read as follows: **Section R102.4; change to read as follows: R102.4 Referenced codes and standards. The codes, when specifically adopted, and standards referenced in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference. Whenever amendments have been adopted to the referenced codes and standards. each reference to said code and standard shall be considered to reference the amendments as well. Any reference made to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. Where differences occur between provisions of this code and referenced codes and standards, the provisions of this code shall apply. **Section R105.2, item #1; change as follows: 1. One-story detached accessory structures, provided the floor area does not exceed 120 square feet (18.5811.15 m2). **Section R109.1.3; change to read as follows: R109.1.3 Floodplain inspections. For construction permitted in areas prone to flooding as established by Table R301.2 (1), upon. . .. construction, the building official may require submission. . . {remainder of section unchanged}. Ordinance No. 2590 Page 1 of 14 **Section R110 (R110.1 through R110.4); delete. **Section R112.2.2; delete. **Section R202; change definition of nTownhouse" to read as follows: TOWNHOUSE. A single-family dwelling unit constructed in a group of attached units separated by property lines in which each unit extends from foundation to roof and with open space on at least two sides. **Table R301.2(1); fill in as follows: Wind Roof Snow e Load Speed (mph) 5 LB/ft2 90 (3-sec-gust)/75 fastest mile Seismic Design f,g Category A Subject To damage from a Frost line c d Winter design Flood Weathering b Termite Decay f h Depth Temp Hazard moderate 6" Very Slight to 22°F Local heavy Moderate Code **Section R303.3, exception; change to read as follows: Exception: The glazed areas shall not be required where artificial light and a mechanical ventilation system, complying with one of the following, are provided. 1- The minimum ventilation rates shall be 50 cfm (23.6 LIs) for intermittent ventilation or 20 cfm (9.4 LIs) for continuous ventilation. Ventilation air from the space shall be exhausted directly to the outside. 2. Bathrooms that contain only a water closet. lavatory or combination thereof may be ventilated with an approved mechanical recirculating fan or similar device designed to remove odors from the air. **Section R303.6; change to read as follows: R303.6 Required heating. Every dwelling unit shall be provided with heating facilities capable of maintaining a minimum room temperature of 680F (200C) at a point 3 feet (914 mm) above the floor and 2 feet (610 mm) from exterior walls in all habitable rooms at the design temperature. **Section R314.8; change to read as follows: R314.8 Under stair protection. Enclosed accessible space under stairs shall have walls, under stair surface and any soffits protected on the enclosed side with 5/8-inch (15.8 mm) fire-rated gypsum board or one-hour fire-resistive construction. Ordinance No. 2590 Page 2 of 14 Section N1102.2 amend as follows: N1102.2 Maximum solar heat gain coefficient for fenestration products. The area-weighted-average solar heat gain coefficient (SHGC) for glazed fenestration installed in climate zones with less than 3,500 HDD) shall not exceed 0.40. **Add Section M1304.2 to read as follows: M1304.2 Minimum burial depth. Underground fuel piping systems shall be installed a minimum depth of 18 inches (458 mm) below grade. **Section M1305.1.3,· change to read as follows: M1305.1.3 Appliances in attics. Attics containing appliances requi ri ng access shall be provided . . . {bulk of paragraph unchanged} . . . sides of the appliance where access is required. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), or larger where such dimensions are not large enough to allow removal of the largest appliance. As a minimum. access to the attic space shall be provided by one of the following: 1. A permanent stair. 2. A pull down stair. 3. An access door from an upper floor level. Exception: The passageway and level service space are not required where the appliance is capable of being serviced and removed through the required opening. **Add Section M1305.1.5, M1305.1.5.1 to read as follows: M1305.1.5 Water heaters above around or floor. When the mezzanine or platform in which a water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor level. it shall be made accessible by a stairway or permanent ladder fastened to the building. M1305.1.5.1 Whenever the mezzanine or platform is not adeauately lighted or access to a receptacle outlet is not obtainable from the main level. lightino and a receptacle outlet shall be provided in accordance with Section M1305.1.3.1. **Section M1305.1.3.1; add a sentence to read as follows: Low voltage wiring of 50 Volts or less shall be installed in a manner to prevent physical damage. **Section M1305. 1.4.1; change to read as follows: M1305.1.4.1 Ground clearance. Appliances supported from the ground shall be level and firmly supported on a concrete slab or other approved material extending above the adjoining grade a minimum of 3 inches (76 mm). Appliances suspended from the floor shall have a clearance of not less than 6 inches (152 mm) above the ground. Ordinance No. 2590 Page 5 of 14 **Section M1305.1.4.3; add a sentence to read as follows: Low voltage wiring of 50 Volts or less shall be installed in a manner to prevent physical damaQe. **Section M1307.3. 1; delete. **Section M1501.2; change to read as follows: M1501.2 Exhaust duct size. The minimum diameter of the exhaust duct shall be as recommended by the manufacturer, shall be at least the diameter of the appliance outlet and shall be a minimum nominal size of 4 inches (102 mm) in diameter. The size of duct shall not be reduced along its developed length nor at the point of termination. **Section M1501.3; change to read as follows: M1501.3 Length limitation. The maximum length of a clothes dryer exhaust duct shall not exceed 25 feet (7620 mm) from the dryer location to the wall or roof termination with not more than two bends. When extra bends are installed, the maximum length of the duct shall be reduced 2.5 feet (762 mm) for each 45-degree (0.79 rad) bend and 5 feet (1524 mm) for each 90-degree (1.6 rad) bend that occur after the first two bends, measuring in the direction of airflow. The maximum length of the exhaust duct does not include the transition duct. {Exception is unchanged} **Section M1601.3.4, item #1; change to read as follows: 1. Duct insulation shall conform to the reQuirements of Table M1601.3.4 and Section N1101.2. Should there be any conflicts between this section and the energy efficiency provisions. the energy efficiency provisions shall take precedence. A vapor retarder in accordance with Table M1601.3.4 or aluminum foil having a minimum thickness of2 mils (0.051 mm), shall be installed on the exterior of insulation on cooling supply ducts that pass through nonconditioned spaces conducive to condensation. Insulations havinQ a permeance of 0.05 perms f2.87 ng/(Pa . s . m2)1 or less shall not be reQuired to be covered. **Add Table M1601.3.4 to read as follows: Table M1601.3.4 -Insulation of Ducts Insulation Duct Location Types Heating Mechanically Zone1 Cooled Insulation Types Heating Only On roof on exterior of building 2 C, V and W Attics, garages and crawl spaces 2 A and V I II III I II A and W BandW CandW A A Ordinance No. 2590 Page 6 of 14 3 3 In Walls, within floor-ceiling spaces 2 A and V III I II III B A A B Within the conditioned space or in basements, return ducts in air plenums None Required None Required Cement slab or within ground None Required None Required Note: Where ducts are used for both heating and cooling, the minimum insulation shall be as required for the most restrictive condition. 1 Heating Degree Days: Zone I below 4,500 D.D. Zone 114,501 to 8,000 D.O. Zone III over 8,000 D.D. 2 Vapor retarders shall be installed on supply ducts in spaces vented to the outside in geographic areas where the summer dew point temperature based on the 2 % percent column of dry-bulb and mean coincident wet-bulb temperature exceeds 600 F. (15.40 C). 3 Insulation may be omitted on that portion of a duct which is located within a wall- or a floor-ceiling space where: 3.1 Both sides of the space are exposed to conditioned air. 3.2 The space is not ventilated. 3.3 The space is not used as a return plenum. 3.4 The space is not exposed to unconditioned air. Ceilings which form plenums need not be insulated. INSULATION TYPES4 : A -- A material with an installed conductance of 0.48 [2.72 W/(m*K») or the equivalent thermal resistance of 2.1 [0.367 (m*K)/W). Example of materials capable of meeting the above requirements: 1-inch (25 mm), 0.60 Ib.lcu.ft. (9.6 kg/m3) mineral fiber, rock, slag or glass blankets. %-inch (13 mm), 1.5 to 3 Ib.lcu.ft. (24 to 48 kg/m3) mineral fiber blanket duct liner. %-inch (13 mm), 3 to 10 Ib.lcu.ft. (48 to 160 kg/m3) mineral fiber board. 8 -- A material with an installed conductance of 0.24 [1.36 W/(m*K») or the equivalent thermal resistance of 4.2 [0.735 (m*K)/W). Example of materials capable of meeting the above requirements: 2-inch (51 mm), 0.60 Ib.lcu.ft. (9.6 kg/m3) mineral fiber blankets. 1-inch (25 mm), 1.5 to 3 Ib.lcu.ft. (24 to 48 kg/m3) mineral fiber blanket duct liner. Ordinance No. 2590 Page 7 of 14 1-inch (25 mm), 3 to 10 Ib.lcu.ft. (48 to 160 kg/m3) mineral fiber board. C -- A material with an installed conductance of 0.16 [0.9 W/(m*K)] or the equivalent thermal resistance of 6.3 [1.1 (m*K)/W). Example of materials capable of meeting the above requirements: 3-inch (76 mm), 0.60 Ib.lcu.ft. (9.6 kg/m3) mineral fiber blankets. 1 %-inch (38 mm), 1.5 to 3 Ib.lcu.ft. (24 to 48 kg/m3) mineral fiber blanket duct liner. 1 %-inch (38 mm), 3 to 10 Ib.lcu.ft. (48 to 160 kg/m3) mineral fiber board. V --Vapor Retarders: Material with a perm rating not exceeding 0.05 perm [29 ng/Pa*s*m2). All joints to be sealed. W - Approved weatherproof barrier. 4 The example of materials listed under each type is not meant to limit other available thickness and density combinations with the equivalent installed conductance or resistance based on the insulation only. **Section M2005.2; change to read as follows: M2005.2 Prohibited locations. Fuel-fired water heaters shall not be installed in a room used as a storage closet. Water heaters located in a bedroom or bathroom shall be installed in a sealed enclosure so that combustion air will not be taken from the living space. Access to such enclosure may be from the bedroom or bathroom when through a solid door. weather-stripped in accordance with the exterior door air leakage requirements of the International EnerQv Conservation Code and eQuipped with an approved self-closino device. Direct- vent water heaters are not required to be installed within an enclosure. ** Sect/on G2403; amend definition of nUnvented Room Heater" to add a sentence to read as follows: For the purpose of installation. this definition shall also include "Unvented Decorative Appliances." **Section G2407.15, item #1; change the exception to read as follows: Exception: Unobstructed stud and joist spaces within dwellinlJ units shall not be prohibited from conveying combustion air, provided that not more than one required fireblock is removed. **Section G2408.3; delete. **Section G2411.5; add a second paragraph to read as follows: Both ends of each section of medium pressure corrugated stainless steel tubino (CSST) shall identify its operating oas pressure with an approved tao. The taos are to be composed of aluminum or stainless steel and the following wording shall be stamped into the tao: 'WARNING 1/2 to 5 psi oas pressure Ordinance No. 2590 Page 8 of 14 Do Not Remove" **Section G2412.3; add an exception to read as follows: Exception: Corrugated stainless steel tubin~ (CSST) shall be a minimum of 1/2". **Section G2414.6; change to read as follows: G2424.6 (404.6) Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner what will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels, the piping shall be installed in accordance with Section G2414.11 (404.11) **Section G2414.9; change to read as follows: G2414.9 (404.9) Minimum burial depth. Underground piping systems shall be installed a minimum depth of 18 inches (458 mm) below grade. **Section G2414.9.1; delete. **Section G2416.4; add a sentence to read as follows: The equipment used shall be of an appropriate scale such that pressure loss can be easily determined. **Section G2416.4.1; change to read as follows: G2416.4.1 (406.4.1) Test pressure. The test pressure to be used shall be not less than 10 psig (68.9 kPa gauge), or at the discretion of the Code Official. the piping and valves may be tested at a pressure of at least six (6) inches (152 mm) , of mercury. measured with a manometer or slope gauge. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa). the test pressure shall not be less than sixty (60) pounds per square inch (413.4 kPa). **Section G2416.4.2; change to read as follows: G2416.4.2 (406.4.2) Test duration. Test duration shall be held for a length of time satisfactory to the Code Official, but in no case for less than fifteen (15) minutes. For welded piping. and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa). the test duration shall be held for a length of time satisfactory to the Code Official. but in no case for less than thirty (30) minutes. **Add Section G2419.1.4 to read as follows: G2419.1.4 Valves in CSST installations. Shutoff valves installed with corrugated stainless steel (CSST) piping systems shall be supported with an approved termination fitting. or equivalent support. suitable for the size of the valves, of adequate strength and Quality. and located at intervals so as to Ordinance No. 2590 Page 9 of 14 prevent or damp out excessive vibration but in no case greater than 12-inches from the center of the valve. Supports shall be installed so as notto interfere with the free expansion and contraction of the system's piping. fittings. and valves between anchors. All valves and supports shall be designed and installed so they will not be disengaged by movement of the supporting pipinQ. **Section G2420.1; add a second paragraph and exception to read as follows: Access to regulators shall comply with the reQuirements for access to appliances as specified in Section M1305. Exception: A passageway or level service space is not reQuired when the regulator is capable of beinQ serviced and removed through the reQuired attic opening. **Section G2437.5; add a sentence to read as follows: The size of duct shall not be reduced alonQ its developed length nor at the point of termination. **Section G2437.5.1; change to read as follows: G2437.5.1 (613.6.1) Maximum length. The maximum length of a clothes dryer exhaust duct shall not exceed 25 feet (7620 mm) from the dryer location to the outlet terminal with not more than two bends. When extra bends are installed, the maximum length of the duct shall be reduced 2 1/2 feet (762 mm) for each 45- degree (0.79 rad) bend and 5 feet (1524 mm) for each 90-degree (1.6 rad) bend that occur after the first two bends. measuring in the direction of airflow. {Exception is unchanged} **Section G2443.2; change to read as follows: G2443.2 (620.2) Prohibited use. One or more unvented room heaters shall not be used as the sole source of comfort heating in a dwelling unit. Exception: Existinq approved unvented heaters may continue to be used in dwellinQ units. in accordance with the code provisions in effect when , installed. when approved bv the Code Official unless an unsafe condition is determined to exist as described in International Fuel Gas Code Section 108.7. **Section G2446.1.1; change to read as follows: G2446.1.1 (623.1.1) Installation requirements. The requirements for water heaters relative to access. sizing, relief valves, drain pans and scald protection shall be in accordance with this code. **Section P2503.5.1, item 1; add a second paragraph to read as follows: Shower receptors shall be tested for water tiQhtness by filling with water to the level of the rouQh threshold. The drain shall be plugqed in a manner so that Ordinance No. 2590 Page 10 of 14 both sides of pans shall be subjected to the test at the point where it is clamped to the drain. **Section P2503.7.2; change to read as follows: P2503.7.2 Testing. Reduced pressure principle. . . {bulk of section unchanged}. . . at the time of installation, immediately after repairs or relocation and at regular intervals as reQuired by applicable state or local provisions, **Add Section P2603.6.1 to read as follows: P2603.6.1 Sewer depth. Building sewers shall be a minimum of 12 inches (304 mm) below Qrade. **Section P270B.1; change to read as follows: P2708.1 General. Shower compartments shall. . . {bulk of section unchanged} . . . shall be constructed as per Section R307.2 . Such walls shall. . . {remainder of section and exception unchanged}. **Section P270B.1; add a sentence to read as follows: Thresholds shall be of sufficient width to accommodate a minimum twenty-two (22) inch (559 mm) door. **Section P2709. 1; add an exception to read as follows: Exception: Showers designed to comply with ICC/ANSI A 117.1. **Section P2710.1; change to read as follows: P2710.1 Finished. Shower walls shall be finished in accordance with Section R307.2. **Section P2B03.6.1; change to read as follows: P2803.6.1 Requirements for discharge. The outlet of a pressure relief valve, temperature relief valve or combination thereof, shall not be directly connected to the drainage system. The discharge from the relief valve shall be piped full size separately to the outside of the building or to an indirect waste receptor located inside the building. The pipe shall be made of minimum Type M Copper. In areas subject to freezing, the relief valve shall discharge through an air gap into an indirect waste receptor located within a heated space, or by other approved means. The discharge pipe shall not discharge into the pan reQuired in Section P2801.5. The discharge shall be installed in a manner that does not cause personal injury or property damage and that is readily observable by the building occupants. The discharge from a relief valve shall be trapped. The diameter of the discharge piping shall not be less than the diameter of the relief valve outlet. Ordinance No. 2590 Page 11 of 14 The discharge pipe shall be installed so as to drain by gravity flow and shall terminate atmospherically. When discharginq outside the buildinq. the point of discharge shall be with the end of the pipe not more than two (2) feet (610 mm) nor less than six (6) inches (152 mm) above the ground or the floor level of the area receiving the discharQe and pointinQ downward. The end of the discharge pipe shall not be threaded. **Table P2904.4.1; delete npolybutylene (PS) plastic pipe and tubing". **Sections P2904.5, 2904.5.1 and 2904.12,' delete reference to "PSn plastic pipe. **Section P3005.2.6; changed to read as follows: P3005.2.6 Upper terminal Each horizontal drain shall be provided with a cleanout at its upper terminal. Exception: Cleanouts may be omitted on a horizontal drain less that five (5) feet (1524 mm) in length unless such line is servinq sinks or urinals. **Section P3103.1; changed to read as follows: P3103.1 Roof extension. All open vent pipes which extend through a roof shall be terminated at least six (6) inches (152 mm) above the roof except that. . . {remainder of section unchanged}. **Sections P3105.2 and P3105.3 and Figure P3105.3; delete **Section P3111.1; change to read as follows: P3111.1 Type of fixture. A combination waste and vent system shall not serve fixtures other than floor drains, standpipes, indirect waste receptors. Combination drain and vent systems shall not receive the discharge of a food waste grinder. **Section P3111.2; change to read as follows: P3111.2Installation. The only vertical pipe of a combination drain and vent system shall be the connection between the fixture drain of a standpipe, and the horizontal combination waste and vent pipe. The maximum vertical distance shall be 8 feet (2438 mm). **Section E3301.1; add a sentence to read as follows: All references to NFPA 70 shall mean the Electrical Code as adopted. **Section E3306.3; change to read as follows: E3306.3. Minimum size of conductors. The minimum size of conductors for branch circuits shall . . . {remainder of section unchanged} . . .' Ordinance No. 2590 Page 12 of 14 **Section E3306.6; change to read as follows: E3306.6 Conductors in parallel. Circuit conductors that are electrically joined at each end to form a single conductor shall be limited to sizes NO.1/0 and larger. {remainder of section unchanged.} **Section E3802.8; change to read as follows: E3802.8 Exempt receptacles. Receptacles installed under exceptions to Sections E3802.2 and E3802.5 shall not be considered as meeting the requirements of Section E3801.9. SECTION 3. Part VIII Electrical Section of the 2000 International Residential Code is not adopted by this ordinance. The most recently adopted National Electrical Code shall be in full force and effect to establish the rules and regulations governing electrical aspects of construction. SECTION 4. That if any section, subsection, sentence, clause, or phrase of this Ordinance is, for any reason, as amended hereby, be adjudged or held to be invalid, such decision shall not affect the validity of the remaining portions of this Ordinance. SECTION 5. That any person, firm or corporation violating any of the provisions of this ordinance shall be deemed guilty of a misdemeanor and, upon conviction in the municipal court of the City of North Richland Hills, Texas, shall be subject to a fine not to exceed the sum of $200.00 for each offense, and each and every day said violation is continued shall constitute a separate offense. SECTION 6. This ordinance shall take effect on January 1, 2002. DULY PASSED by the City Council of North Richland Hills, Texas, on the 17th day of December, 2001. ~rOVed: L ~_JL ~ Charles scom~~ Ordinance No. 2590 Page 13 of 14 ,,' I"",('\'-~¡ iii" "" 1iÅ'~ ~vø"'" fj}:-- .:\y~.~. ". '" '/ ., ATTESTl,t " n .~_, ~:; , r :~ ø~~~ ~ Patricia HU~J;!, eIÿ S~cretary ""1" /1' tH'~' \' APPROVED AS TO FORM AND LEGALITY: ~ 7Il~>:rk~ tt~y APPROVED AS TO CONTENT: ~ John Pitstick, Department Head Ordinance No. 2590 Page 14 of 14 INVOICE Star- Telegram 400 W 7th Street FORTWORTI!, TX 76102 (817)390-7761 Federal TaxID 22-3148254 Customer ID: Inv~')iee Number: Invdce Date: Tel-m§: Bill To: CITY OF N RICHLAND HILLS/SECRET PO BOX 820609 NORTH RICHLAND HILLS, TX 76182- Pi \e. Lùt {:)v l.:4 ,,~~ ~ ð. ct"5 ~ ò Due Date: PO I~umber: Order Number: Sales Rep: Des~ription: Publication Dates: Attn FINANCE . DEPT CIT13 209434581 1/7/02 Net due in 21 days 1/31/02 20943458 073 ORDINANCE NO, 2 1/4/02 - 1/7/02 ORDINi\NCE NO, 2590 An Ordinanc 13580 57 5'1 LINE 1 Sales Discount ~ NO, Aa~¿f~~~~,. Hllrs, Texasec1rtl':j m: 200~nternacmnal Resldéntlal Codé; r~ulatlng the erec- tlon, construotlo!"l, enlargement, , alter- atIon, repair, m9Ä1nR' '6~~~~!on?=upgn~ ~¥t\~uIP:r.-:~t, u..~ ma~ntenanoe of one- and two-family. ctwell- Ings and townhouseSh In the CItv of Nort Rlchland 'Hills: pro- vIding for the Issuance, of permits and co· leotlons of fees thetefore' ,Provldl[f. for penalties for th violatIon thereo , I providing. a sevet- ability crause=;_~rovld~ Ing for ape..... 0. fine not to ex 00 tfohe sum of $200. r each offense' ,and p'rovldlng an eff~l~: -- ~.J of the THE STATE OF 1 r.;;;-:nattonl" Rasl- C,"",y of T&,," i1'='~ ¡~ in th,e o~,:, Of '~Ity Seoret~;J,' ad Before me, a Not II!', d ~$ECnc~ of for the Star-Telel< .'., CItv,' of North nd Hills, Texas depose and say tl ~Deoembèr 17, 1, Approved Charles scoma, Mayor SUBSCRIBED ANI~~"; F~ x McEntire, City Attorney Net Amount: $6.08 $693.12 ($652,08) $41.04 I and State, thi ~a p rsonally appear, ed Christy Holland, Bid an Legal Coordinator gram, Inc. at F. rt o~ ,in Tarrant County, Te~s; and who, a er being duly swo~n,' did Idvertisemen w p . hed i¡l the above name pa r on t IS,ted Jat¡j>: a,M' ~~ ~ ¡ Th"",.y, Jao'C.l'lOO~. ~ A- '- !Þ, /' I ,.,.., __... Notary Public -U ~ (7\ .V().L JJ r~ - ~ - - -- 1\ ..<......,..,......... VICKI L. WASON (~ ) MY COMMISSION EXPIRES l....:~ ..' AUGUST 28, 2004 ~ _ .. ''a<; Thank You For Your Payment .~... ~ .......~ '....... ~.. ___~,~............. .,...,,,.'" ,....... ........ .~ ~.... _ ....-. ......-.. '~A ~ ,...___ .__. ____ __..~""--,, .......... .........., __ ___ ...~ ___n h... ..__~ "...... ........... ........... ~..~ .~ ..........,.......,.,.. ..no.._ ......... '.."". ....~ ~_...................... Remit To: Star-Telegram P.O. Box 901051 FORT WORTH, TX 76101-2051 CIT13 CITY OF N RICHLA,TD HIL 209434581 $41. 04 Customer ill: Customer Name: Invoice Number: Invoice Amount: PO Number: Amount Enclosed: . . . ....·.....·.·u.·u.·.·.·.·.·NN~. ....... ·.·.~·.·.·.·~.·.·.·.·N.·.·.....·.·.~·. .::...::'..:::::~ it.uuuu___. ..u..uuuu.uu.u