HomeMy WebLinkAboutOrdinance 2625
ORDINANCE NO. 2625
2
8
AN ORDINANCE OF THE CITY OF NORTH RICHLAND HILLS
AMENDING CHAPTER 10 OF THE NORTH RICHLAND HILLS CODE
OF ORDINANCES AND ADOPTING THE 2000 EDITION OF THE
INTERNATIONAL FIRE CODE, AND THE 2002 SUPPLEMENT TO THE
2000 INTERNATIONAL FIRE CODE; PROVIDING AMENDMENTS TO
THE INTERNATIONAL FIRE CODE; REGULATING AND GOVERNING
THE SAFEGUARDING OF LIFE AND PROPERTY FROM FIRE AND
EXPLOSION HAZARDS ARISING FROM THE STORAGE, HANDLING
AND USE OF HAZARDOUS SUBSTANCES, MATERIALS AND
DEVICES, AND FROM CONDITIONS HAZARDOUS TO LIFE OR
PROPERTY IN THE OCCUPANCY OF BUILDINGS AND PREMISES IN
NORTH RICHLAND HILLS; PROVIDING FOR THE ISSUANCE OF
PERMITS FOR HAZARDOUS USES OR OPERATIONS; REPEALING
SECTIONS 10-2, 10-43,10-44,10-52,10-53,10-54,10-56,10-57,10-58,10-59,
10-60, 10-61, 10-62, 10-63, 10-65 & 10-67, AND ALL OTHER ORDINANCES
AND PARTS OF ORDINANCES IN CONFLICT HEREWITH;
ESTABLISHING A PENALTY; AUTHORIZING PUBLICATION; AND
PROVIDING AN EFFECTIVE DATE.
4
6
10
12
14
16
18
20
22
WHEREAS, the North Richland Hills City Council desires to adopt the 2000
International Fire Code and the 2002 Supplement to the 2000
International Fire Code with amendments in order to better provide for the
safety of its residents and their property; NOW, THEREFORE,
24
26
28
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF NORTH
RICHLAND HILLS, TEXAS:
30
Section 1:
THAT Section 10-42 ofthe North Richland Hills Code of Ordinances be
amended to read as follows:
32
"Sec. 10-42. International Fire Code Adopted.
34
46
The documents, copies of which are on file in the office of the City Secretary of North
Richland Hills, marked and designated as the International Fire Code, including Appendix
Chapters Band D (see International Fire Code, Section 101.2.1,2000 edition), and 2002
Supplement to the 2000 International Fire Code, as published by the International Code
Council, as amended by the recommended amendments of the North Central Texas
Council of Governments as further amended by the City of North Richland Hills, which
amendments are also on file in the office of the CitySecretary, are hereby adopted as the
Fire Code of the City of North Richland Hills for regulating and governing the
safeguarding oflife and property from fire and explosion hazards arising from the storage,
handling and use of hazardous substances, materials and devices, and from conditions
hazardous to life or property in the occupancy of buildings and premises in the City of
North Richland Hills, and providing for the issuance of permits for hazardous uses or
36
38
40
42
44
C:\WINDOWS\TEMP\lntlFirl.wpd
1
operations; and each and all of the regulations, provisions, conditions and terms of such
International Fire Code, 2000 edition, and 2002 Supplement to the 2000 International
Fire Code published by the International Code Council, as amended by the recommended
amendments of the North Central Texas Council of Governments as further amended by
the City of North Richland Hills, on file in the office of the City Secretary are hereby
referred to, adopted and made a part hereof, as if fully set forth in this ordinance."
2
4
6
8
Section 2:
10
THAT Section 10-55 of the North Richland Hills Code of Ordinances be
amended to read as follows:
12
"Sec. 10-55. Fire Alarms.
(a)(8) Change to read:
14
Premises: Any building or structure, or combination of buildings or structures, including
residential dwellings, tenant or lease spaces located wholly or partially inside such building
or structures classified by the International Fire Code as a Group A, B, E, F, H, I, M, R, and
S occupancies, where a fire alarm system is installed.
16
18
20
(c )(2) Change to read:
No fee shall be assessed for the first three (3) false fire alarms or fire alarms or fire alarm
malfunctions at the same premises during each calendar year. Thereafter, a fee of two
hundred fifty dollars ($250.00) shall be paid by the owner/occupant for each false fire
alarm or false fire alarm malfunction located in a Group A, B, E, F, H, I M, R-1 and S
occupanCIes.
22
24
26
28
(d)(2) Change to read:
The installation, maintenance and continuous operation of smoke detectors in every
occupancy classification listed in the International Fire Code . . . {remainder of section
unchanged} ."
30
32
34
Section 3:
36
38
40
Section 4:
42
44
46
Sections 10-2, 10-43, 10-44, 10-52, 10-53, 10-54, 10-56, 10-57, 10-58, 10-
59, 10-60, 10-61, 10-62, 10-63, 10-65, and 10-67 of the North Richland
Hills Code of Ordinances are hereby repealed. All other ordinances
conflicting with this ordinance are hereby repealed to the extent only of
such conflict. Such ordinances with conflicting provisions are hereby saved
to the extent they do not conflict herewith.
If any section, subsection, sentence, clause or phrase of this ordinance is,
for any reason, held to be unconstitutional, such decision shall not affect the
validity of the remaining portions of this ordinance. The City Council
hereby declares that it would have passed this ordinance, and each section,
subsection, clause or phrase thereof, irrespective ofthe fact that anyone or
more sections, subsections, sentences, clauses and phrases be declared
C:\WINDOWS\TEMP\IntlFirl.wpd
2
2
Section 5:
4
6
Section 6:
8
10
12
14
16
Section 7:
18
20
Section 8:
22
unconstitutional.
Ordinances conflicting herewith are hereby repealed, but only to the extent
of such conflict; remaining portions of such ordinances are hereby saved
from repeal to the extent they do not conflict herewith.
Any person, firm, or corporation violating any provision of the Fire Code
herein adopted shall be deemed guilty of a misdemeanor and upon
conviction fined in an amount not to exceed Two Thousand Dollars
($2,000) for each such violation. Each day, a violation shall continue to
exist shall constitute a separate offense punishable hereunder. Violations
may also be punished by civil penalties imposed after suit. The amount of
such civil penalties shall be any amount up to the maximum allowed by
law.
The City Secretary is hereby ordered and directed to cause the descriptive
caption and penalty provisions of this ordinance to be published as an
alternative method of publication provided by law.
This ordinance and the rules, regulations, provisions, requirements, orders
and matters established and adopted hereby shall take effect and be in full
force and effect immediately upon passage.
24
AND IT IS SO ORDAINED.
26
PASSED AND ADOPTED this 10th day of June, 2002.
.,~, ";'/111
" III
.'.:.cv-. .......... ~/""
f'~~:-.ÍI .....\~\
III r r~~
~ST: h /f
~.. ..,
~/ ....:¡:.,..~ .,'
'II ....
'III/ ~.
~/II'''''_'''''.''''
dathC/a
Patricia Hutson, City Secretary
28
30
32
34
36
38
40
CITY OF NORTH RICHLAND HILLS
By:
Oscar Trevino, Mayor
APPROVED AS TO FORM AND LEGALITY:
George A. Sraples, ArÊJ .¡
42
44
C:\WINDOWS\TEMP\lntlFirl.wpd
3
North Richland Hills
Amendments to
North Central Texas Council of Governments
Amendments to
2000 International Fire Code
Section 101.1 Insert: City of North Richland Hills.
Section 102.4; change to read as follows:
102.4 Application of building other codes. The design and construction of new structures
shall comply with this code, and other codes as applicable the bltematio1lal Building Code; and
any alterations, additions, changes in use or changes in structures required by this code which are
within the scope of this and other codes the I1ltematio1lal Buildi1lg Code shall be made in
accordance therewith.
(Reason: Clarification of requirements and that the IFC also applies to new residential
construction. )
Section 102.6; change to read as follows:
Section 102.6 Referenced codes and standards. The codes and standards referenced in this
code shall be those that are listed in Chapter 45 and such codes, when specifically adopted, and
standards shall be considered part of the requirements of this code to the prescribed extent of
each such reference. Where differences occur between the provisions of this code and the
referenced standards, the provisions of this code shall apply. Whenever amendments have been
adopted to the referenced codes and standards, each reference to said code and standard shall be
considered to reference the amendments as well. Any reference to NFP A 70 or the ICC Electrical
Code shall mean the Electrical Code as adopted.
Section 109.3 Substitute: Any person who shall continue any work after being ordered to stop
shall be deemed guilty of a misdemeanor punishable by a fine not exceeding $2,000.00.
Section 111.4 Substitute: Any person who shall continue any work after being ordered to stop
shall be deemed guilty of a misdemeanor punishable by a fine not exceeding $2,000.00.
Section 202; add definitions to read as follows:
HIGH-RISE BUILDING is a building having floors used for human occupancy located more
than 55 feet (16,764 mm) above the lowest level of fire department vehicle access.
Page 1 of 18
SELF-SERVICE STORAGE FACILITY. Real property designed and used for the purpose of
renting or leasing individual storage spaces to customers for the purpose of storing and removing
personal property on a self-service basis.
ST ANDBY PERSONNEL. Qualified fire service personnel. approved by the Fire Chief. When
utilized, the number required shall be as directed by the Fire Chief. Charges for utilization shall
be as normally calculated by the jurisdiction.
(Reason: To provide definitions that do not exist in the code.)
Section 307.2; change to read as follows:
307.2 Permit required. A permit shall be obtained from the code official in accordance with
Section 105.6 prior to kindling a fire for recognized trench burns or open burning a bonfire.
Application for such approval shall only be presented by and permits issued to the owner of the
land upon which the fire is to be kindled.
Examples of state or local law, or regulations referenced elsewhere in this section may include
but not be limited to the following:
1. Texas Natural Resource Conservation Commission guidelines and/or restrictions.
2. State, Country or Local temporary or permanent bans on open burning.
3. Local written policies as established by the Code Official.
Section 307.3; change to read as follows:
307.3 Location. The location for open burning other than recreationalfìres shall not be less
than 5&-300 feet (1524091 440 mm) from any structure, and provisions shall be made to prevent
the fire from spreading to within 5B 300 feet (1524091440) of any structure.
(exceptions unchanged)
Add Section 307.3.3 to read as follows:
307.3.3 Trench Burns. Trench burns shall be conducted in air curtain trenches and in
accordance with Section 307.2.
Section 307.4; change to read as follows:
307.4 Attendance. Open burning, trench burns, bonfires or recreational fires shall be
constantly attended by a person eighteen (18) years of age or older until the 1... {remainder of
section unchanged}.
Page 2 of 18
(Reason: Amendments to 307.2, 307.3, 307.3.3 and 307.4 better explain current requirements
and recognize that jurisdictions have local established policies that best fit their environments.)
Section 307.5; change to read asfollows:
307.5 Open-flame cooking devices. Charcoal burners and other open-flame cooking devices
shall not be operated or located on combustible balconies or within 10 feet (3048 mm) of
combustible construction.
Exceptions:
1. One and two-family dwellings.
2. Where buildings, balconies and decks are protected by an approved automatic sprinkler
system.
(Reason: To better explain protection options.)
Section 307.5.1; change to read asfollows:
307.5.1 Liquified-petroleum-gas-fueled cooking devices. When permitted as listed in the
exceptions of Section 307.5, LP-gas burners having a LP-gas container with a water capacity
greater than 2.5 pounds (1.14 kg) (nominal 1 pound (0.454 kg) LP-gas capacity] shall not be
located on combustible balconies or within 10 feet (3048 mm) of combustible construction.
Exception: One and two-family dwellings, and other residential occupancies when those
residential occupancies are in compliance with Section 307.5, exception #2, may have containers
with water capacity not greater than 20 pounds (9.08 kg) [nominal 1 pound (0.454 kg) LP-gas
capacity] .
(Reason: Clarification and defines container size residences are allowed.)
Section 503.1.1; add thefollowing sentence to thefirst paragraph:
Except for single or two-family residences, the path of measurement shall be along a minimum
of a ten feet (10') wide unobstructed pathway around the external walls of the structure.
(Reason: Recognizes that the hose lay provision can only be measured along a pathway that is
wide enough for firefighter access.)
Section 503.2.1; change to read asfollows:
503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less
than 20 feet (6096 mm), except for approved security gates in accordance with Section 503.6,
Page 3 of 18
and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 111111) 14 feet (4267 mm).
Exception: Vertical clearance may be reduced, provided such reduction does not impair access
by fire apparatus and approved signs are installed and maintained indicating the established
vertical clearance when approved.
Section 503.2.2; change to read as follows:
503.2.2 Authority. The code official shall have the authority to require an increase in the
minimum access widths and vertical clearances where they are inadequate for fire or rescue
operations.
(Reason: Amendments to 503.2.1 and 503.2.2 recognize that the equipment now used in fire
fighting is increasing in size. The code already recognizes that larger dimensions may be
required under Section 503.2.2. The amendments are to standardize the dimensions for this
area. )
Section 503.3; change to read as follows:
503.3 Marking. Where requircd by the code official, approved Approved striping or, when
allowed by the code official. signs, or both, or other approved 116tiees shall be provided for fire
apparatus access roads to identify such roads or prohibit the obstruction thereof. Signs or notices
and striping shall be maintained in a clean and legible condition at all times and be replaced or
repaired when necessary to provide adequate visibility.
(1) Striping - Fire apparatus access roads shall be marked by painted lines of red traffic
paint six inches (6") in width to show the boundaries of the lane. The words "NO PARKING
FIRE LANE" or 'FIRE LANE NO PARKING" shall appear in four inch (4") white letters at 25
feet intervals on the red border markings along both sides of the fire lanes. Where a curb is
available, the stripping shall be on the vertical face of the curb.
(2) Signs - shall read "NO PARKING FIRE LANE" or 'FIRE LANE NO PARKING" and
shall be 12" wide and 18" high. Signs shall be painted on a white background with letters and
borders in red, using not less than 2" lettering. Signs shall be permanently affixed to a stationary
post and the bottom of the sign shall be six feet. six inches (6'6") above finished grade. Signs
shall be spaced not more than fifty feet (50') apart. Signs may be installed on permanent
buildings or walls or as approved by the Fire Chief.
(Reason: Establishes a standard method of marking.)
Section 503.4; change to read as follows:
Page 4 of 18
503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be
obstructed in any manner, including the parking of vehicles. The minimum widths and
clearances established in Section 503.2.1 and any area marked as a fire lane as described in
Section 503.3 shall be maintained at all times.
(Reason: As originally worded, it implied that vehicles could be parked in the marked fire lane
and not be in violation if the minimum width is still maintained. Current accepted enforcement
practice is to require all of the marked fire lane to be maintained clear and unobstructed.)
Section 503.6.1; Security Gates add:
All primary emergency access points shall be equipped to operate with the Opticom gate opening
system. The opener shall incorporate a fail-safe manual backup or an automatic release in the
event of a failure of the electrical or mechanical system. Primary emergency access points shall
be approved by the Fire Marshal. All secondary emergency access points shall be equipped with
a Knox padlock. Existing security gates shall be upgraded to meet current code within 2 years.
Section 704.1; change to read asfollows:
704.1 Enclosure. Interior vertical shafts, including but not limited to stairways, elevator
hoistways, service and utility shafts, that connect two or more stories of a building shall be
enclosed or protected in accordance with the codes in effect at the time of construction but,
regardless of when constructed, not less than as specified in Table 704.1. When openings are
required to be .,. (remainder of section unchanged).
(Reason: Provides standard minimum protection retroactively, but clarifies that this section is
not to be used to reduce higher protection levels that were required when originally constructed.)
Section 803.3.2 and Section 803.4.2; add an exception to read as follows:
Exception: Corridors protected by an approved automatic sprinkler system installed in
accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area.
(Reason: This change allows an increase in wall coverage due to the presence of sprinklers.)
Section 804.1.1; add a second exception to read asfollows:
Exceptions:
1. (existing exception unchanged)
2. Trees shall not be prohibited inside private dwelling units of Group R-2 Occupancies.
(Reason: Eliminates rule for private dwelling space.)
Page 5 of 18
Section 901. 7; change to read asfollows:
901. 7 Systems out of service. Where a required fire protection system is out of service or in the
event of an excessive number of accidental activations, the fire department and the code official
shall be notified immediately and, where required by the code official, the building shall either be
evacuated or an approved fire watch standby personnel shall be provided for all occupants left
unprotected by the shut down until the fire protection system has been returned to service.
Where utilized, fire watches standby personnel shall be provided with at least one approved
means for notification of the fire department and their only duty shall be to perform constant
patrols of the protected premises and keep watch for fires.
(Reason: Gives Fire Chief more discretion. Requires adoption of definition amendment in
Section 202.)
Section 902.1; add definition of "Fire Area" to read as follows:
FIRE AREA. The aggregate floor area enclosed and bounded by fire walls, fire barriers,
exterior walls or fire-resistance-rated horizontal assemblies of a buildinf2:.
(Reason: Gives definition to a term used within Chapter 9.)
Section 902.1; under "Standpipe, Types of" definition, amend "Manual dry" by adding a
sentence to read as follows:
The system must be supervised as specified in Section 905.2.
(Reason: Corresponds with Section 905.2 recommended amendment.)
Section 903.1.2; change to read as follows:
903.1.2 Residential systems. Unless specifically allowed by this code or the International
Building Code, residential sprinkler systems installed in accordance with NFP A 13 D or NFP A
13R shall not be recognized for the purposes of exceptions or reductions, commonly referred to
as "trade-offs", permitted by other requirements of this code.
In addition, residential sprinkler svstems installed in accordance with NFP A 13 R must include
attic sprinkler protection to be recognized for the purposes of such trade-offs permitted by other
requirements of this code.
(Reason: Because 13R system trade-offs allowed in the International Codes compromise 13R
intent of life safety, attic sprinklers regain some protection by minimizing likelihood of
residential fire spreading through the attic space.)
Page 6 of 18
Sections 903.2.1.1,903.2.1.3 and 903.2.1.4; change to read asfollows:
903.2.1.1 Group A-I. An automatic sprinkler system shall be provided throughout a fire area
containing a for Group A-I occupancy Occupancies where one of the following conditions
exists:
1.
2.
3.
4.
The fire area exceeds 12,000 square feet (11115 m2).
The fire area has an occupant load of 300 or more.
The fire area is located on a floor other than the level of exit discharge.
The fire area contains a multi theater complex.
903.2.1.3 Group Á-2. An automatic sprinkler system shall be provided throughout a fire area
containing a for Group A-2 occupancy Occupancies where one of the following conditions
exists:
1.
2.
3.
The fire area exceeds 5,000 square feet (464.5 m2).
The fire area has an occupant load of 300 or more.
The fire area is located on a floor other than the level of exit discharge.
903.2.1.4 Group A-3. An automatic sprinkler system shall be provide throughout a fire area
containing a for Group A-3 occupancy Occupancies where one of the following conditions
exists:
1.
2.
3.
The fire area exceeds 12,000 square feet (1115 m2).
The fire area has an occupant load of 300 or more.
The fire area is located on a floor other than the level of exit discharge.
Exception: Areas using exclusively as participant sports areas where the main floor is located at
the same level as the level of exit discharge of the main entrance and exit.
(Reason: Current wording implies that only the fire area needed to be sprinklered. This conflicts
with the charging section, 903.2.1, which specifies the entire floor and all floors down to level of
exit discharge are to be sprinklered.)
Section 903.2.7; change to read as follows:
903.2.7 Group R-l. An automatic sprinkler system shall be provided throughout buildings with
a Group R -1 fire area.
Exceptions:
1. Where guestrooms are not located more than three 5torie5 one story in height and the
building contains less than 20 guest rooms abovc thc lowest level of exit di5charge and each
guestroolll ha5 at lca5t one. door leading directly to all exteriör cxit acceS5 that leads directly to
approved exits.
2. A residential sprinkler system installed in accordance with Section 903.3.1.2. shall be
allowed in buildings, or portions thereof, Group - R -1.
Page 7 of 18
Section 903.2.8; change to read as follows:
903.2.8 Group R-2. An automatic sprinkler system shall be provided throughout all buildings
with a Group R-2 fire area where any of the following conditions applv:
1. The R-2 contains four or less units and is more than two stories in height: or,
2. The R-2 is located more than twú stories one story in height, including basements;
or
3. The building contains having more than 16 dwelling units; or
4. The building contains fraternities and sororities with an occupant load of more than
~
Exception: A residential sprinkler system installed in accordance with Section 903.3.1.2 shall
be permitted in building, or portions thereof, of Group R-2.
(Reason: Reflects local enforcement practice.)
Add Sections 903.2.10.2 and 903.2.10.3 to read as follows:
903.2.10.2 Bulk storage oftires. Buildings and structures where the area for the storage of tires
exceeds 20,000 cubic feet (566 m3) shall be equipped throughout with an automatic fire sprinkler
system in accordance with Section 903.3.1.1.
903.2.10.3 Self-service storage facility. An automatic sprinkler system shall be installed
throughout all self-service storage facilities.
Exception: One-story self-service storage facilities that have no interior corridors, with a one-
hour fire barrier separation wall installed between every storage compartment.
(Reason: Consistent with unamended IBC.)
Section 903.2.12; amend 903.2.12.3 and add 903.2.12.4 and 903.2.12.5 as follows:
903.2.12.3 Buildings over 55 35 feet in height. An automatic sprinkler system shall be installed
throughout buildings with a floor level, other than penthouses in compliance with Section 1509
of the International Building Code, having an occupant load of 30 or mol'{; that is located 55
35 feet (16764 10 668 mm) or more above the lowest level of fire department vehicle access.
Exception:
1. Airport control towers.
2. Open parking structures in compliance with Section 406.3 of the International Building
Code.
J. Occupancies in Croup [-2.
Page 8 of 18
Section 903.2.12; add 903.2.12.4,903.2.12.5 and 903.2.12.6 asfollows:
903.2.12.4 Hi~h-Piled Combustible Stora2e. For any building with a clear height exceeding 12
feet (4572 mm), see Chapter 23 to determine if those provisions apply.
903.2.12.5 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall
be protected by an approved automatic fire-extinguishing system.
Section 903.3.1.1.1; Exempt locations. When approved by the code official, automatic
Automatic sprinklers shall not be required in the following rooms or areas where such. . . { bulk of
section unchanged} . . . because it is damp, of fire-resistance-rated construction or contains
electrical equipment.
1. Any room where the application of water, or flame and water, constitutes a serious life or
fire hazard.
2. Any room or space where sprinklers are considered undesirable because of the nature of
the contents, when approved by the code official.
3. Generator and transformer rooms, under the direct control of a public utility, separated
from the remainder ofthe building by walls and floor/ceiling or room/ceiling assemblies
having a fire-resistance rating of not less than 2 hours.
4. Spaccs or areas in telccommunications buildings...2 hours.
5. In rooms or areas that are of noncombustible construction with wholly n(}llcombustiblc
contcnts.
(Reason: Gives more discretion to code official. Protects locations where fire risks are poorly
addressed. )
Section 903.23.1.2; change to read asfollows;
903.3.1.2 NFP A 13R sprinkler systems. Where allowed in buildings of Group R, up to and
including four stories in height, automatic sprinkler systems shall be installed throughout in
accordance with NFP A 13R. However, for the purposes of exceptions or reductions permitted by
other requirements of this code, see Section 903.1.2.
(Reason: Editorial to be included with recommended amendment to 903.1.2.)
Section 903.3.5; add a second paragraph to read as follows:
Water supply as required for such svstems shall be provided in conformance with the supply
requirements of the respective standards: however, every fire protection system shall be designed
with a 10 psi safety factor.
Page 9 of 18
(Reason: To define uniform safety factor.)
Section 903.4; add a second paragraph after the exceptions to read as follows:
Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the
sprinkler system and shall cause an alarm upon detection of water flow for more than 30 seconds.
All control valves in the sprinkler and standpipe systems except for fire department hose
connection valves shall be electrically supervised to initiate a supervisory signal at the central
station upon tampering.
(Reason: To avoid significant water losses. Consistent with amendment to IFC 905.9.)
Add Section 903.6.2 to read as follows:
903.6.2 Spray booths and rooms. New and existing spray booths and spray rooms shall be
protected by an approved automatic fire-extinguishing system in accordance with Section 1504.
(Reason: Consistent with amendment to IFC 1504.)
Section 905.2; change to read as follows:
905.2 Installation standards. Standpipe systems shall be installed in accordance with this
section and NFP A 14. Manual dry standpipe systems shall be supervised with a minimum of 10
psig and a maximum of 40 psig air pressure with a high/low alarm.
(Reason: To define manual dry standpipe supervision requirements.)
Section 905.3.2; delete exceptions #1 and 2.
(Reason: Reflects local practice.)
Section 905.4, item #5; change to read asfollows:
5. Where the roofhas a slope less than four units vertical in 12 units horizontal (33.3
percent slope), each standpipe shall be provided with a two-way hose connection located
either... {remainder of paragraph unchanged)...
(Reason: Clarity.)
Section 905.9; add a second paragraph after the exceptions to read as follows:
Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the
sprinkler system and shall cause an alarm upon detection of water flow for more than 30 seconds.
All control valves in the sprinkler and standpipe systems except for fire department hose
Page 10 of 18
connection valves shall be electrically supervised to initiate a supervisory signal at the central
station upon tampering.
(Reason: To avoid significant water losses. Consistent with amendment to IFC 903.4.)
Add Section 907.1.3 to read as follows:
907.1.3 Desifn Standards. All alarm systems new or replacement serving 50 or more alarm
actuating devices shall be addressable fire detection systems. Alarm systems serving more than
75 smoke detectors or more than 200 total alarm activating devices shall be analog intelligent
addressable fire detection systems.
Exception: Existing systems need not comply unless the total building remodel or expansion
initiated after the effective date of this code, as adopted, exceeds 30% of the building. When
cumulative building remodel or expansion exceeds 50% of the building must comply within 18
months of permit application.
(Reason: Consistent with local practice.)
Section 907.2.3; change to read as follows:
907.2.3 Group E. A manual fire alarm system shall be installed in Group E educational
occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems
or detectors shall be connected to the building fire alarm system. An approved smoke detection
system shall be installed in Group E day care occupancies. Unless separated by a minimum of
100' open space, all buildings, whether portable buildings or the main building, will be
considered one building for alarm occupant load consideration and interconnection of alarm
systems.
(Reason: To distinguish educational from day care occupancy minimum protection
requirements. Further, to define threshold at which portable buildings are considered a separate
building for the purposes of alarm systems.)
Section 907.2.3; change exception #1 and add exception #1.1 to read asfollows:
1. Group E educational and day care occupancies with an occupant load of less than 50
when provided with an approved automatic sprinkler system.
1.1. Residential In-Home day care with not more than 12 children may use interconnected single
station detectors in all habitable rooms. (For care of more than five children 2 1/2 or less years of
age, see Section 907.2.6.)
(Reason: Consistent with Texas State laws concerning day care facility requirements.)
Page 11 of 18
Section 907.2.12; change to read asfollows:
907.2.12 High-rise buildings. Building having floors used for human occupancy located more
than 95-55 feet (22860 16764 mm) above the lowest level of fire department vehicle access shall
be provided with an automatic fire alarm system and an emergency voice/alarm communications
system in accordance with Section 907.2.12.2.
(Reason: To correct definition of high-rise.)
Section 907.2.12, exception #3, change to read asfollows:
3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the
International Building Code, when used for open air seating: however, this exception does not
apply to accessory uses including but not limited to sky boxes, restaurants and similarly enclosed
areas.
(Reason: To indicate that enclosed areas within open air seating type occupancies are not
excepted from automatic fire alarm system requirements.)
Section 907.2.12.2; change the beginning paragraph to read asfollows:
907.2.12.2. Emergency voice/alarm communication system. The operation of any automatic
fire detector, sprinkler water-flow device or manual fire alarm box shall automatically sound an
alert tone followed by voice instructions giving approved information and directions on a general
or selective basis to the following terminal areas on a minimum ofthe alarming floor. the floor
above, and the floor below in accordance with the building's fire safety and evacuation plans
required by Section 404:
(Reason: To provide minimum evacuation buffer around alarming floor.)
Section 907.4; add a second paragraph to read as follows:
Manual alarm actuating devices shall be an approved double action tvpe.
(Reason: Consistent with local requirements.)
Add Section 907.6.1 to read asfollows:
907.6.1 Installation. All fire alarm systems shall be installed in such a manner that the failure
of anv single alarm-actuating or alarm-indicating device will not interfere with the normal
operation of anv other such devices. All svstems shall be Class "A" wired with a minimum of six
feet separation between supply and return loops. IDC-Class "A" style - D - SLC Class "A" Style
6 - notification Class "B" Style Y.
Page 12 of 18
(Reason: To provide uniformity in system specifications and guidance to design engineers.)
Section 907.9.2; change to read asfollows,'
907.9.2 High-rise buildings. In buildings that have floors located more than 75 55 feet (22 860
16764 mm) above the... (remainder of section unchanged).
(Reason: Correct definition of high-rise.)
Section 913.4; add a second paragraph to read asfollows;
The fire-pump system shall also be supervised for "loss of power", "phase reversal" and "pump
running" conditions by supervisory signal on distinct circuits.
(Reason: To define other conditions requiring supervision.)
Section 1003.2.12.2, exception #3; change to read asfollows:
3. In occupancies in Group I-3, F, H or in non-public portions of S, balusters, horizontal
intermediate rails or other... (remainder of exception unchanged).
(Reason: Consistent with regional amendment to IBC 1003.2.12.2.)
Section 1005.2.1; change to read asfollows:
1005.2.1 Minimum number of exits. Every floor area shall be provided with the minimum
number of approved independent exits as required by Table 1005.2.1 based on the occupant load,
except as modified in Section 1004.2.1 or 1005.2.2. For the purposes of this chapter, occupied roofs
shall... {remainder of section unchanged}.
(Reason: Section 1004.2.1 is referenced in Section 1005.2.2, item #3. Its reference in this section
creates confusing code requirements. Consistent with regional amendment to IBC 1005.2.1.)
Section 1005.3.2.5; change to read asfollows:
1005.3.2.5 Smoke proof enclosures. In buildings required to comply with the high-rise provisions
of the International Building Code or the provisions for underground buildings in the International
Building Code, each of the exits of a building that serves stories where the floor surface is located
more than 75 55 feet (22 860 16764 mm) above the lowest level of fire... (remainder of section
unchanged).
Reason: Correct definition of high-rise.)
Page 13 of 18
Section 1504.6; change to read asfollows:
1504.6 Fire Protection. New and existing spray 5prny- booths and spray rooms shall be protected
by an approved automatic fire-extinguishing system... {remainder of section unchanged}...
(Reason: Consistent protection in all spray booths.)
Section 2302; add a second paragraph to the definition of "High-Piled Combustible Storage" to
read as follows:
Any building exceeding 6,000 sq. ft. that has a clear height in excess of 12 feet, making it possible
to be used for storage in excess of 12 feet, shall be considered to be high-piled storage and shall
comply with the provisions of this section. When a specific product cannot be identified, a fire
protection system shall be installed as for Class IV commodities, to the maximum pile height.
(Reason: To provide protection for worst-case scenario in flexible or unknown situations.)
Section 2416.1; change to read asfollows:
2416.1 Standby personnel/Crowd managers. When, in the opinion of the code official, it is
essential for public safety in a place of assembly or any other place where people congregate, because
ofthe number of persons, or the nature of the performance, exhibition, display, contest or activity,
the owner, agent or lessee shall employ standby personnel one of mere qualified persons, as required
and approved, to remain on duty during the times such places are open to the public, or when such
activity is being conducted.
Before each performance or the start of such activity, standby personnel shall keep diligent watch
for fires during the time such place is open to the public or such activity is being conducted and take
prompt measures as directed by the Fire Chief. Such duties may include, but not be limited to-;-for
extinguishment of fires that occur and assist in the evacuation of the public from the structure.
There shall be trained crowd managers or crowd manager supervisors at a ratio of one crowd
manager/supervisor for every 250 occupants, as approved.
(Reason: Gives Fire Chief more discretion. Requires adoption of definition recommendations in
Section 202.)
Section 3301.1.3,' change to read asfollows:
3301.1.3 Fireworks. The possession, manufacture, storage, sale, handling and use of fireworks are
prohibited.
Page 14 of 18
Exceptions:
1. Only when approved for fireworks displays, storage and handling of fireworks as provided
penl1itted in Section 3304 and 3308.
2. Manufacture, asembly and testing of fireworks as pelülÍtted in Section 3304.
3. The use of fireworks for approved display as permitted in Section 3308.
4. The possession... .conSlliner fireworks.
(Reason: Restricts to approved displays, which is consistent with local practice.)
Section 3402; add new definitions to read as follows:
FUEL LIMIT SWITCH. A mechanism, located on a tank vehicle, which limits the quantity of
product dispensed at one time.
MOBILE FUELING. The operation of dispensing liquid fuels from tank vehicles into the fuel
tanks of motor vehicles. Mobile Fueling may also be known by the terms Mobile Fleet Fueling; Wet
Fueling; and Wet Hosing.
REMOTE EMERGENCY SHUT -OFF DEVICE. The combination of an operator carried
signaling device and a mechanism on the tank vehicle. Activation of the remote emergency shut-off
device sends a signal to the tanker mounted mechanism and causes fuel flow to cease.
(Reason: Definitions required for amendments in 3406.5.4.5 to handle mobile fleet fueling "wet-
hosing" industry.)
Section 3403.6; add a sentence to read asfollows:
An approved method of secondary containment shall be provided for underground tank and piping
systems.
Section 3404.2.11.5; add a sentence to read asfollows:
An approved method of secondary containment shall be provided for underground tank and piping
systems.
(Reason: Increased protection in response to underground leak problems and rehabilitation difficulty
in underground applications.)
Section 3404.2.11.5.2; change to read as follows:
3404.2.11.5.2 Leak detection. Underground storage tank systems... {bulk of provision
unchanged}.. . and installed in accordance with NFPA 30 and as specified in Section 3404.2.11.5.3.
Page 15 of 18
(Reason: Reference to Section 3404.2.11.5.3 amendment.)
Add Section 3404.2.11.5.3 to read asfollows:
3404.2.11.5.3 Dry sumps. Approved sampling tubes of a minimum 6 inches in diameter shall be
installed in the backfill material of each underground flammable or combustible liquid storage tank.
The tubes shall extend from a point 12 inches below the average grade of the excavation to ground
level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling
sump at the corners of the excavation with a minimum of 4 sumps. Sampling tubes shall be placed
in the product line excavation within 10 feet of the tank excavation and one every 50 feet routed
along product lines towards the dispensers, a minimum of two are required.
(Reason: Provides an economical means of checking potential leaks at each tank site.)
Add Sections 3406.5.4.5 and 3406.5.4.5.1 through 3406.5.4.5.3 to read asfollows:
3406.5.4.5 Commercial. industrial. fovernmeotal ormanufacturinr. Dispensing of Class Ii and
III motor vehicle fuel from tank vehicles into the fuel tanks of motor vehicles located at commercial,
industrial, governmental or manufacturing establishments is allowed where permitted, provided such
dispensing operations are conducted in accordance with Sections 3406.5.4.5.1 through 3406.5.4.5.3.
3406.5.4.5.1 Site requirements.
1. Dispensing may occur at sites that have been permitted to conduct mobile fueling.
2. A detailed site plan shall be submitted with each application for a permit. The site plan must
indicate:
a. all buildings, structures, and appurtenances on site and their use or function;
b. all uses adjacent to the property lines of the site;
c. the locations of all storm drain openings, adjacent waterways or wetlands;
d. information regarding slope, natural drainage, curbing, impounding and how a spill will be
retained upon the site property; and,
e. the scale of the site plan.
1. The Code Official is authorized to impose limits upon: the times and/or days during which
mobile fueling operations are allowed to take place, and specific locations on a site where fueling
is permitted.
2. Mobile fueling operations shall be conducted in areas not generally accessible to the public.
3. Mobile fueling shall not take place within 15 feet (4.572 m) of buildings, property lines, or
combustible storage.
163406.5.4.5.2
Refueling Operator Requirements.
Page 16 of 18
1. The owner of a mobile fuelling operations shall provide to the jurisdiction a written response
plan which demonstrates readiness to respond to a fuel spill, carry out appropriate mitigation
measures, and to indicate its process to properly dispose of contaminated materials when
circumstances require.
2. The tank vehicle shall comply with the requirements ofNFP A 385 and Local, State and Federal
requirements. The tank vehicle's specific functions shall include that of supplying fuel to motor
vehicle fuel tanks. The vehicle and all its equipment shall be maintained in good repair.
3. Signs prohibiting smoking or open flames within 25 feet (7.62 m) of the tank vehicle or the point
of fueling shall be prominently posted on 3 sides of the vehicle including the back and both sides.
4. A fire extinguisher with a minimum rating of 40:BC shall be provided on the vehicle with
signage clearly indicating its location.
5. The dispensing nozzles and hoses shall be of an approved and listed type.
6. The dispensing hose shall not be extended from the reel more than 100 feet (30.48 m) in length.
7. Absorbent materials, non-water absorbent pads, a 10 foot (3.048 m) long containment boom, an
approved container with lid, and a non-metallic shovel shall be provided to mitigate a minimum 5-
gallon fuel spill.
8. Tanker vehicles shall be equipped with a fuel limit switch such as a count-back switch, limiting
the amount of a single fueling operation to a maximum of 500 gallons (1893 L) between resetting
of the limit switch.
Exception: Tankers utilizing remote emergency shut-off device capability where the operator
constantly carries the shut-off device which, when activated, immediately causes flow of fuel from
the tanker to cease.
9. Persons responsible for dispensing operations shall be trained in the appropriate mitigating
actions in the event of a fire, leak, or spill. Training records shall be maintained by the dispensing
company and shall be made available to the Code Official upon request.
10. Operators of tank vehicles used for mobile fueling operations shall have in their possession at
all times an emergency communications device to notify the proper authorities in the event of an
emergency.
3406.5.4.5.3 Operational Requirements
1. The tank vehicle dispensing equipment shall be constantly attended and operated only bv
designated personnel who are trained to handle and dispense motor fuels.
2. Prior to beginning dispensing operations. precautions shall be taken to assure ignition sources
are not present.
3. The engines of vehicles being fueled shall be shut off during dispensing operations.
4. Nighttime fueling operations shall only take place in adequately lighted areas.
5. The tank vehicle shall be positioned with respect to vehicles being fueled so as to preclude traffic
from driving over the delivery hose and between the tank vehicle and the motor vehicle being fueled.
Page 17 of 18
6. During fueling operations, tank vehicle brakes shall be set, chock blocks shall be in place and
warning lights shall be in operation.
7. Motor vehicle fuel tanks shall not be topped off.
8. The dispensing hose shall be properly placed on an approved reel or in an approved compartment
prior to moving the tank vehicle.
9. The Code Official and other appropriate authorities shall be notified when a reportable spill or
unauthorized discharge occurs.
(Reason: Provide guidelines for a recognized operation. Correlates with changes expected in the
2001 supplement to the IFC, with modifications customized to this region. See definitions in
regional amendments to IFC 3402.)
Add Section 3803.2.1.8 to read as follows:
3803.2.1.8 Jewelry Repair. Dental Labs and Similar Occupancies. Portable LP-Gas containers
are allowed to be used to supply approved torch assemblies or similar appliances. Such containers
shall not exceed 20-pound (9.0 kg) water capacity. Aggregate capacity shall not exceed 60-pound
(27.2 kg) water capacity. Each device shall be separated from other containers by a distance of not
less than 20 feet.
(Reason: To provide a consistent and reasonable means of regulating the use of portable LP-Gas
containers in these situations.)
Section 3804.2 (limits in which the storage of liquefied petroleum gas is restricted for the protection
of heavily populated or congested areas): Multifamily residentially zoned districts.
Section 3204.3.1.1 (limits in which the storage of flammable cryogenic fluids in stationary
containers is prohibited): None.
Section 3404.2.9.5.2 (limits in which the storage of Class I and Class II liquids in above-ground
tanks outside of buildings is prohibited): All except areas zoned industrial.
Add Section 3804.3.2 to read as follows:
3804.3.2 Spas and Pool Heaters. Where natural gas service is not available, LP-Gas containers are
allowed to be used to supply spa and pool heaters. Such containers shall not exceed 250-gallon
water capacity. See Table 3804.3 for location of containers.
(Reason: Allows for an alternate fuel source.)
Section 3406.2.4.4 (limits in which the storage of Class I and Class II liquids in above-ground tanks
is prohibited): All residentially zoned districts."
Page 18 of 18
INVOICE
Star- Telegram
400 W. 7th Street
FORT WORTH, TX 76102
(817)390-7761
Federal Tax ID 22-3148254
Customer ID:
Invoice Number:
Invoice Date:
Terms:
Due Date:
PO Number:
Order Number:
Sales Rep:
Description:
Publication Dates:
Bill To:
CITY OF N RICHLAND HILLS/SECRET
PO BOX 820609
NORTH RICHLAND HILLS, TX 76182-
Pi \~ uJ I 6 \( L "" ..V'\~ N 6. 3.tþ~¡;
Attn ACCOUNTS. PAYABLE
""c
CIT13
215531551
6/19/02
Net due in 21 days
6/30/02
21553155
073
CITY OF NORTH RI
6/18/02 - 6/19/02
4t:\\~·
CITY OF NORTJ- ~~ 13180 93 93 LINE $6.08 $ I, I 30.88
Sales Discount ~fi ($1,063,92)
c~J:;· O,'....&'dlnances
~affl~~°'bVn~~e I~~~~
national Fire Code.
a~d",~~f t~~~~ ~ó'8õ Net Amount: $66.96
Pnternatlona1 Fire
Code; providing
amendments to the
International Fire
code; regulating and
governing the safe-
guarding of life and
property from fire and
explosion hazards
arising from the stor-
~pe, ~:z'1.~~'6~;md s~t':
~~aJ1å:~lces. ~~àef~g~
conditions hazardous
to .lIfe. or property In
the occupancy of
~~~~~q~ . N~~~¡:f¡~~:
~~~d th~lIIr¿sJ'J~~~dinoq
permits for hazar~ous
uses or ,;'operatlons;
2~~n~ ~fTia~~n~ ~.' ~~._~;~:~.~O~.'~.. :g~
59::0- ,!ät;t:o--
62, 1 , ,~~t
Before me, a Notar ~~ Md == County and State, this day personally appeared KAREN WILLIAMS, Bid and Legal Coordinator
for the Star-Telegra of U r-Telegram, Inc. at Fort Worth, in Tarrant County, Texas; and who, after being duly sworn, did depose and say
that the a~hed cl ~f\8' · _ ent was published n~he ab e named paper on the listed dates: BIDS ~ LEGALS DEPT. STAR TELEGRAM
(817) 390 7182. an effective date. lJ úlili
Any person, firm, or (1liJVl ) ÚYtJ- D
corporation; violating
~1).~ prß~~~n ~~r~~ Signed _
I ~~~~~~ g~~t~" of b~
SUBSCRIBED AN misdem ear:'0[ fan~' ME, THIS Thursday, Jun.e 2.0Q2r;;¿£2... ... (/. ..
f:r~~dc~~6c~~n n6~~o ~ , " ... J
f;rg~!~I~~~~{?~~~ Notary Public . .. .'_'.',,, """ Lie ~ðV'---
tlon· Each day a .,...... -_...~-------~
vlolatlotl sh~1I contin- VICKI L, WASON I
ue to eXIst shall 1 ,
g~~~~~te ~u~'f~~~1: \~,:OM:\i:S:::IOI, EXP'FŒS I,
hereunder. Violations "I ','..., .-r ""r ¡;
Thank You F ( may also be punished it _ ".... .... ... "u·,us I ¿5, .2004 I.
by civil ~enalties im- .,.,.,,",~¡$~'(-~.~-::--::-'~~.~~:::-f~¡..,..~J.
- - - - - - - ~~~~nta o,r s~~fi I~f¡ - - - - - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
~:;,no~~~s t~all t~e ~g~
,..,~vi""II"" ~lIn\AlQ,rl hv