HomeMy WebLinkAboutOrdinance 3605 ORDINANCE NO. 3605
• AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF NORTH
RICHLAND HILLS, TEXAS, AMENDING CHAPTER 98 OF THE NORTH
RICHLAND HILLS CODE OF ORDINANCES, ADOPTING THE 2018
INTERNATIONAL RESIDENTIAL CODE AS AMENDED AS THE
RESIDENTIAL CODE OF THE CITY OF NORTH RICHLAND HILLS;
PROVIDING A PENALTY; PROVIDING THAT THIS ORDINANCE SHALL
BE CUMULATIVE OF ALL ORDINANCES AND REPEAL OF
CONFLICTING PROVISIONS; PROVIDING SAVINGS CLAUSE;
PROVIDING A SEVERABILITY CLAUSE; AND PROVIDING AN
EFFECTIVE DATE.
WHEREAS, the City of North Richland Hills, Texas ("the City") is a home rule city acting
under its power adopted by the electorate pursuant to Article XI, Section 5
of the Texas Constitution and Chapter 9 of the Local Government Code;
and
WHEREAS, the International Building Codes are developed by construction industry
professionals and adopted around the world as model codes based on the
best, most recent building science; and
WHEREAS, updates to the building codes are meant to track with changes in building
industry standards, practices, innovations, and technologies; and
WHEREAS, the North Richland Hills City Council desires to adopt the 2018 International
Residential Code with amendments recommended by the North Central
Texas Council of Governments and other local amendments in order to
better provide for the health, safety, and welfare of its residents and their
property, as well as all occupants and users of buildings and structures
within the community; and
WHEREAS, it is the policy of the City of North Richland Hills to update its building codes
every six years; and
WHEREAS, updated codes benefit North Richland Hills citizens by establishing
consistency of code adoptions with other local jurisdictions; ensuring the
best rating possible by the Insurance Services Organization (ISO);
Contributes to the city's good standing in FEMA's Community Rating
System (CRS) which enables discounted flood insurance rates for
residents; and
WHEREAS, the North Richland Hills Construction Code Appeals Board acting in its
capacity as the Construction Advisory Board on August 15, 2019 reviewed
and unanimously recommended the adoption of the 2018 International
Ordinance No.3605
Page 1 of 23
Residential Code with the amendments recommended by the North Central
Texas Council of Governments and other local amendments.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF
NORTH RICHLAND HILLS, TEXAS:
SECTION 1: The City Council hereby finds the recitals above to be true and correct,
and such recitals are hereby incorporated into this Ordinance as if written
herein.
SECTION 2: THAT Section 98-141 of the North Richland Hills Code of Ordinances be
amended to read as follows:
Sec. 98-141. 2018 International Residential Code adopted.
The International Residential Code for One and Two-Family Dwellings, 2018 Edition,
together with Appendix H and K of such Code, as adopted by the International Code
Council, Inc., a copy of which is on file in the office of the city secretary, as hereinafter
amended, is hereby adopted as the residential building code of the city, which governs
the construction of one-family and two-family dwelling units in the city.
SECTION 3: THAT Section 98-142 of the North Richland Hills Code of Ordinances be
amended to read as follows:
Sec. 98-142. Amendments to the 2018 International Residential Code.
The 2018 International Residential code is amended as set forth below:
**Section R102.4; change to read as follows:
R102.4 Referenced codes and standards. The codes, when specifically adopted, and
standards referenced in this code shall be considered part of the requirements of this code
to the prescribed extent of each such reference and as further regulated in Sections
R102.4.1 and R102.4.2. Whenever amendments have been adopted to the referenced
codes and standards, each reference to said code and standard shall be considered to
reference the amendments as well. Any reference made to NFPA 70 or the Electrical
Code shall mean the Electrical Code as adopted.
**Section R102.7; change to read as follows:
The legal occupancy of any structure existing on the date of adoption of this code shall
be permitted to continue without change, except as is specifically covered in this code,
the International Fire Code or Chapter 89, Article X of North Richland Hills Code of
Ordinances, or as is deemed necessary by the building official for the general safety and
welfare of the occupants and the public.
** Section R103 and R103.1 amend to insert the Department Name:
Ordinance No.3605
Page 2 of 23
BUILDING INSPECTION DEPARTMENT OF THE CITY OF NORTH RICHLAND HILLS,
TEXAS
R103.1 Creation of enforcement agency. The Building Inspection Department of the
City of North Richland Hills is hereby created and the official in charge thereof shall be
known as the building official.
**Section R104.10.1 Flood Hazard areas; delete this section.
**Section R105.2, item #1, 2, 3, 5, 10, 11, 12, 13; change to read as follows:
1. One-story detached accessory structures used as tool and storage sheds,
playhouses, carports and similar uses, provided it is located at least 3 feet from the
primary residence, the floor area does not exceed 144 square feet, and complies
with Chapter 118 of the North Richland Hills Code of Ordinances.
Replacement of upto four eight-foot longsections of fence.
2. g
3. Retaining walls not over 3 feet in height measured from the bottom of the footing
to the top of the wall, unless supporting a surcharge or impounding class I, II or III-
A liquids. (Retaining walls placed in succession shall be considered one wall if,
upon drawing a line from the bottom of the footing of the lower wall at a 45-degree
angle up and towards the higher wall, the line intersects the higher wall or any
material retained by the wall at any point.) Retaining walls 3 feet or taller must be
designed by an engineer licensed to practice in the State of Texas.
4. Private sidewalks and other flatwork less than 300 SF in area not considered a
driveway, a public sidewalk, the public right-of-way, or more than 30 inches above
grade, and not over a basement or story below, and are not part of an accessible
route or intended for public use.
10. Decks, patio covers, and pergolas not exceeding 200 square feet in area and
meeting section R302.1, that do not contain a walking surface more than 30 inches
above grade at any point, and are not attached to or located within 6 feet a dwelling.
11. Roof repairs on dwellings and their accessory structures. For the purpose of this
section, roof repairs shall include the repair and replacement of the roof coverings
only, but not including the decking material, lathing boards or sheathing panels.
The building official is authorized to revoke this exception during periods of federal
or state disaster relief efforts; in which case a building permit and contractor
registration is required prior to commencement of roofing repair/replacement
activities.
12. Freestanding satellite dishes not exceeding one meter in diameter that do not
exceed 12 feet in height.
Ordinance No.3605
Page 3 of 23
13. Replacement of up to three exterior windows provided the windows do not reduce
the size of existing emergency egress windows per requirements of section R310
of this code and meet the adopted version of International Energy Code
Conservation Code.
Exemption from the permit requirements of this code shall not be deemed to grant
authorization for any work to be done in any manner in violation of the provisions of this
code or any other laws or ordinances of this jurisdiction.
**Section R105.3.1.1 & R106.1.4; delete these sections.
**Section R105.3.2; change to read as follows:
R105.3.2 Time limitation of application. An application for a permit for any proposed
work shall be deemed to have been abandoned 90 days after the date of filing unless
such application has been pursued in good faith or a permit has been issued; except that
the building official is authorized to grant one or more extensions for an additional period
not exceeding 90 days. The extension shall be requested in writing and justifiable cause
demonstrated.
**Section R105.5; change to read as follows:
R105.5 Expiration. Every permit issued shall become invalid unless the work authorized
by such permit is commenced within 90 days after its issuance, or if the work authorized
by such permit is suspended or abandoned for a period of 90 days after the time the work
is commenced. The building official is authorized to grant, in writing, one or more
extensions of time, for periods not more than 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated.
**Section R109.1.5.2; add section to read as follows:
109.1.5.2 Lath, EIFS flashing and drainage. Lath and EIFS product inspections shall
be made after exterior lathing and EIFS flashing & drainage systems are in place, but
before plastering and/or insulation panels are applied.
**Section R110. 1; change to read as follows:
R110.1 Use and Occupancy. No building or structure shall be used or occupied until the
code official has issued an approved final inspection report. The approval of a final
inspection shall not be construed as an approval of a violation of the provisions of this
code or of other ordinances of the jurisdiction. Approved final inspections presuming to
give authority to violate or cancel the provisions of this code or other ordinances of the
jurisdiction shall not be valid.
Exceptions:
Ordinance No.3605
Page 4 of 23
1. Final inspections are not required for work exempt from permits under Section
R105.2
2. Accessory buildings or structures exempt from permits under Section R105.2
**Amend Section R110.2; change to read as follows:
R110.2 Change in use. Changes in the character or use of an existing residential
structure shall not be made except as specified in the International Building Code and/or
Sections 407 and 408 of the International Existing Building Code.
R110.2.2 Change in tenancy (single-family rental). The owner of a residential rental
unit must obtain a Certificate of Occupancy from the Building Official prior to the unit being
occupied by a new tenant. The Building Official or his designated representative will
inspect the unit and premises for compliance with Sections 98-462(b) through 98- 462(n)
of the North Richland Hills Code of Ordinances and other applicable ordinances of the
City. If deficiencies are found, the Building Official may prohibit occupancy of the unit and
premises until such time as the owner takes action needed to bring the unit and premises
into compliance. The inspection required by this section shall also be required for a
dwelling unit and premises prior to its original occupancy as a rental unit.
Exceptions:
1. Units provided to members of the building owner's immediate family.
2. Units that have entered the rental market in an effort to prevent foreclosure or
similar economic hardship. This exception shall apply to the initial tenant of the
rental unit only.
3. Units which have passed inspection shall not be subject to inspection as a condition
of a Certificate of Occupancy requested within one year of such inspection unless
a complaint is received.
R110.2.2.1 Administrative Fee. If the dwelling unit is found to be occupied prior to
inspection, the Building Official shall assess an administrative fee, as indicated in the Fee
Schedule found in Appendix A of the North Richland Hills Code of Ordinances. This fee
shall be paid by the owner prior to any subsequent inspection or reinspection of the unit
and shall be cumulative of all other fees or penalties provided in this code.
**Amend Section 110.3; change to read as follows:
R110.3 Rental Certificate of Occupancy. When the Building Official or his
representative determines that a rental dwelling unit and premises are in compliance with
the provisions of this code and other applicable codes of the City of North Richland Hills,
a Rental Certificate of Occupancy containing the following shall be issued:
1. The address of the structure;
2. A statement that the described portions of the structure have been approved for
occupancy;
Ordinance No.3605
Page 5 of 23
inspection);
3. The name of the tenant (if known at the time of
4. The name of the building inspector;
5. The date the Rental Certificate of Occupancy was issued.
No certificate-of-occupancy shall be issued for a rental dwelling unit until the owner has
paid all outstanding fees, including past due fees from other rental units; and has
perfected all liens attached to the property by the City of North Richland Hills. Rental
Certificates of Occupancies issued to a building owner or owner's representative shall
expire in 60 days if the unit is not occupied by a tenant.
R110.3.1 Establishing water utility service. Once a rental unit is approved for
occupancy, the tenant of the rental unit shall present the Rental Certificate of Occupancy
to the North Richland Hills Utility Billing Department before a new water service account
can be established in the tenant's name. No water service account to any single-family
rental unit shall be established until the Building Official or his designated representative
has issued a Rental Certificate of Occupancy for the unit. No water service account to any
single-family rental unit shall be established until the Building Official or his designated
representative has inspected the unit(s) and issued a Rental Certificate of Occupancy for
the unit.
R110.3.2 Temporary Rental Certificate of Occupancy. In cases where violations are
minor and will not affect the safety of the occupant(s), the Building Official is authorized
to issue the owner a 60-Day Temporary Rental Certificate of Occupancy. It is the
responsibility of the building owner to correct all noted deficiencies and to obtain a
reinspection prior to the expiration of the temporary rental certificate of occupancy. Failure
to correct all deficiencies prior to the expiration of a temporary rental certificate of
occupancy is considered a violation of this code and shall be subject to penalties as
prescribed by ordinance.
** Section R110.5; change section to read as follows:
R110.5 Revocation. The building official shall, in writing, suspend or revoke temporary
or permanent occupancy issued under the provisions of this code wherever the
occupancy is granted in error, or on the basis of incorrect information supplied, or where
it is determined that the building or structure or portion thereof is in violation of any
ordinance or regulation of any of the provisions of this code.
** IRC Section 111.1; replace entire section as follows:
R111.1 Connection of service utilities. No person shall make connection from a utility,
source of energy, fuel, power or water to any new dwelling unit, townhouse, or system
that is regulated by this code for which a permit is required, until such connection is
approved by the Building Official. No person shall make connections for water utilities to
any rental dwelling unit that is required by this code to be inspected prior to occupancy
until the unit is approved by the Building Official and issued a Rental Certificate of
Occupancy.
Ordinance No.3605
Page 6 of 23
**Amend Section 111.2; change to read as follows:
R111.2 Temporary connection of utilities. The building official shall have the authority
to authorize, approve, or order the disconnection of the temporary connection of the
building system to the utility source of energy, power or water.
** IRC Section R111.3; replace entire section as follows:
R111.3 Authority to disconnect service utilities. In case of an emergency necessitating
disconnection of utilities to eliminate an immediate hazard to life or property, the Building
Official shall have the authority to authorize disconnection of utility service to a building,
structure or system regulated by this code and the referenced codes and standards set
forth in Section R102.4. The Building Official shall notify the service utility and whenever
possible the owner and occupant of the building, structure or service system of the
decision to disconnect prior to taking such action. If prior notification is not possible, the
owner or occupants of the building, structure or service system shall be notified in writing,
as soon as practical thereafter. In addition, the Building Official shall have the authority to
authorize disconnection of utility service to a building, structure or system, if a building,
structure or system is found to be in violation of this code, including a connection made
without the approval required by Sections R111.1 and R111.2, or any other ordinance of
the City and after notification of the violation has been made to the owner and/or occupant
of the building or structure and the violation is not corrected.
**Section R115; add new sections as follows:
SECTION 115 - UNSAFE BUILDINGS, STRUCTURES OR EQUIPMENT
115.1 Unsafe buildings.All buildings, structures or equipment regulated by this code that
are structurally unsafe or not provided with adequate egress, or that constitute a fire
hazard, or are otherwise dangerous to human life are, for the purpose of this section,
unsafe. Any use of buildings or structures constituting a hazard to safety, health or public
welfare by reason of inadequate maintenance, dilapidation, obsolescence, fire hazard,
disaster, damage or abandonment is, for the purpose of this section, an unsafe use.
Parapet walls, cornices, spires, towers, tanks, statuary and other appendages or
structural members that are supported by, attached to, or a part of a building and that are
in deteriorated condition or otherwise unable to sustain the design loads that are specified
in this code are hereby designated as unsafe building appendages.
All such unsafe buildings, structures or appendages are hereby declared to be public
nuisances and shall be abated by repair, rehabilitation, demolition or removal in
accordance with the procedures set forth in this code or such alternate procedures as
may have been or as may be adopted by this jurisdiction. As an alternative, the building
Ordinance No.3605
Page 7 of 23
official, or other employee or official of this jurisdiction as designated by the governing
body, may institute any other appropriate action to prevent, restrain, correct or abate the
violation. This may include ordering the disconnection of water and/or electrical utilities.
A vacant structure that is not secured against entry shall be deemed unsafe. Materials
used to secure a structure, which deteriorate or increase in susceptibility to fire hazard
over time, shall be replaced or treated to eliminate the increase of the hazard.
Any work covered or concealed without inspection shall be considered to constitute an
unsafe structure. Such consideration as an unsafe structure shall exist every day until the
work is inspected and approved as being in compliance with this code. Inspections will
not be performed until a valid active permit is obtained in accordance with this code.
115.1.2 Dangerous Demolition. The Building Official may order the cessation of the
wrecking or demolition of any building or structure within the City when the same is being
accomplished in a reckless or careless manner or in such a manner so as to endanger
life and property. When such work has been ordered stopped by the Building Official,
same shall not be resumed until said official is satisfied that adequate precautions have
been or will be taken for protection for life and property. To continue such work without
the expressed approval of the Building Official shall constitute a violation of this ordinance,
and each day that such work continues shall constitute a separate offense.
*Section R202; modify section to add/change the following definitions to read as
follows:
COURT. {Existing definition unchanged}. When approved by the building official, a court
serving an emergency escape and rescue window may have no more than 5 feet of roof
extending from the exterior wall of the building.
any living unit within an
RENTAL UNIT. A residential rental unit is
RESIDENTIAL
attached or detached one-family dwelling, two-family dwelling, three-family dwelling, four-
family dwelling, or townhouse that is rented or leased for use as a residence by a single
family, individual or group of individuals.
single-family dwellingunit constructed in a groupof three or more
TOWNHOUSE. A single y
attached units separated by property lines in which each unit extends from foundation to
roof and with a yard or public way on at least two sides.
**Table R301.2(1); fill in as follows:
WIND DESIGN
GROUND SEISMIC
SNOW SPEEDd Topographic Special Windborne DESIGN
LOAD m h Effectsk Wind Debris CATEGORYf
(mph) Region' Zonem
Ordinance No.3605
Page 8 of 23
115 (3-sec-
5 lb/ft2 gust)/76 No No No A
fastest mile
SUBJECT TO DAMAGE FROM
Weatheringa Frost line depthb Termite°
moderate 6" very heavy
WINTER ICE BARRIER FLOOD AIR MEAN
DESIGN UNDER-LAYMENT FREEZING ANNUAL
TEMPO REQUIRED" HAZARDS9 INDEX TEMP)
22°F No local code 150 64.9°F
MANUAL J DESIGN CRITERIAn
Summer Altitude
Elevation Latitude Winter Heating Cooling CorreFactoction
610 32 22 99 0.985
Cooling Wind velocity Wind velocity Coincident
temperature heating cooling wet bulb Daily range
difference
24 np np np Medium
Indoor Design Design Heating
Temperature Temperature Temperature
Cooling Difference
70 75 48
Winter humidity Summer
humidity
np np
np— Not Provided
**Section R302.2.2; delete item #2
**Section R302.2.6; modify Exception #5 to read as follows:
Exceptions:
Ordinance No.3605
Page 9 of 23
5. Townhouses separated by a common wall as provided in Section R302.2.2, Item
1, and provided with a fire sprinkler system in accordance with Section P2904.
**Section R302.3; add Exception #3 to read as follows:
Exceptions:
1. {existing text unchanged}
2. {existing text unchanged}
3. Two-family dwelling units that are also divided by a property line
through the structure shall be separated as required for townhouses.
** Table R302.6; replace as follows:
TABLE R302.6
DWELLING/GARAGE SEPARATION
SEPARATION MATERIAL
From the residence and attics Not less than I/2-inch gypsum board or equivalent applied to the
garage side
From all habitable rooms above and adjacent the garage Not less than Vs-inch Type X gypsum board or equivalent
Structure(s)supporting floor/ceiling assemblies used for separation Not less than'lr inch gypsum board or equivalent
required by this section
Garages located less than 3 feet from a dwelling unit on the same lot Not less than�/Z inch gypsum board or equivalent applied to the inte-
Garages side of exterior walls that are within this area
For SI: 1 inch=25.4 mm.1 foot=304.8 mm.
**Section R310; add new sentence to paragraph as follows:
{Existing text unchanged). When considering placement of emergency escape and
rescue openings, a covered patio may be considered a yard when at least 50% of the
cover's perimeter is open to the air without windows or screens and travel distance
beneath the ceiling/roof above does not exceed 15 feet.
**Section R311. 7. 13; add text to read as follows:
R311.7.13 Under stair protection. Enclosed accessible space under stairs shall have
walls, under stair surface and any soffits protected on the enclosed side with 5/8-inch
(15.8 mm) fire-rated gypsum board or one-hour fire-resistive construction.
**Section R313.2; add exception as follows:
Exceptions:
1. {unchanged}
2. An automatic residential fire sprinkler system shall not be required in new one-
and two-family dwellings when they are omitted in accordance with state law.
A notarized affidavit shall be filed with Tarrant County Records indicating that
Ordinance No.3605
Page 10 of 23
the builder has chosen to defer to Section 1301.551 of the Texas Occupations
Code and opted to omit the residential fire sprinkler system otherwise
prescribed by Section R313 of the 2018 International Residential Code. A copy
of the filed affidavit shall be provided to the City of North Richland Hills at the
time of permit application.
**Section R315.2.2 Alterations, repairs and additions. Amend to read as follows:
Exceptions:
1. {existing text remains}
2. Installation, alteration or repairs of all electrically powered mechanical systems or
plumbing appliances.
**Section R316.5; Change to read as follows:
R316.5 Specific requirements. The following requirements shall apply to these uses of
foam plastic.
** Section R316.5.3; change to read as follows:
R316.5.3 Attics. The thermal barrier specified in Section R316.4 is not required where all
of the following apply:
1. {unchanged}
2. The space is entered only for purposes of repairs or maintenance and cannot be
utilized for storage.
3. {unchanged}
3.1. 11/2-inch-thick (38 mm) mineral fiber insulation.
3.2. 1/4-inch-thick (6.4 mm) wood structural panels.
3.3. 3/8-inch (9.5 mm) particleboard.
3.4. 1/4-inch (6.4 mm) hardboard;
3.5. 3/8-inch (9.5 mm) gypsum board.
3.6. Corrosion-resistant steel having a base metal thickness of 0.016 inch
(0.406 mm).
3.7. 11/2-inch-thick (38 mm) cellulose insulation.
3.8. 1/4-inch fiber-cement panel, soffit or backer board.
3.9. Approved proprietary ignition barrier coatings
The ignition barrier is not required where the foam plastic insulation has been tested in
accordance with Section R316.6, can only be accessed by a 24 inch by 32 inch scuttle
hole, and cannot be used for storage. For the purpose of this section, all attics with a
vertical height of 42 inches or more are considered to be storage areas when they are
accessed by a pull-down stair, permanent stair, and/or door.
Ordinance No.3605
Page 11 of 23
**Section R317.1 item #3; change to read as follows:
3. Sills and sleepers on a concrete or masonry slab that is in direct contact with the ground.
**Section R322 Flood Resistant Construction. Deleted Section.
**Section R401.2, amend by adding a new paragraph following the existing
paragraph to read as follows:
Section R401.2. Requirements. (existing text unchanged) ...
Every foundation and/or footing, or any size addition to an existing post-tension
foundation, regulated by this code shall be designed and sealed by a Texas-registered
engineer.
**Section 602.6.1; amend the following:
R602.6.1 Drilling and notching of top plate. When piping or ductwork is placed in or
partly in an exterior wall or interior load-bearing wall, necessitating cutting, drilling or
notching of the top plate by more than 50 percent of its width, a galvanized metal tie not
less than 0.054 inch thick (1.37 mm) (16 Ga) and 5 inches (127 mm) wide shall be
fastened across and to the plate at each side of the opening with not less than eight 10d
(0.148 inch diameter) having a minimum length of 1 1/2 inches (38 mm) at each side or
equivalent. Fasteners will be offset to prevent splitting of the top plate material. The metal
tie must extend a minimum of 6 inches past the opening. See figure R602.6.1. {remainder
unchanged}
**Section 602.6.1; amend the following:
Ordinance No.3605
Page 12 of 23
EXTERIOR OR BEARING WALL
•
NOTCH GREATER THAN 50
PERCENT OF THE PLATE WIDTH -.41I► 4'
16 GAGE(.054 IN.)AND 51N.WIDE
METAL TIE FASTENED ACROSS AND
TO THE PLATE AT EACH SIDE OF THE
NOTCH WITH 8.10d NAILS EACH SIDE
TOP PLATES
PIPE
l
**Add section R703.8.4.1.2; Veneer Ties for Wall Studs. To read as follows:
R703.8.4.1.2 Veneer Ties for Wall Studs. In stud framed exterior walls, all ties shall be
anchored to studs as follows:
1. When studs are 16 in (407 mm) o.c., stud ties shall be spaced no further apart than
24 in (737 mm) vertically starting approximately 12 in (381 mm) from the
foundation; or
2. When studs are 24 in (610 mm) o.c., stud ties shall be spaced no further apart than
16 in (483 mm) vertically starting approximately 8 in (254 mm) from the foundation.
**Amend section R703.8.2.2 requiring treated wood for masonry supported by roof
construction to read as follows:
R703.8.2.2 Support by roof construction. A steel angle shall be placed directly on top
of the roof construction. The roof supporting construction for the steel angle shall consist
of not fewer than three 2-inch by 6-inch (51 mm by 152 mm) treated wood member
{remainder of section unchanged)
**Section R902.1; Amend and add exception #5 to read as follows:
Ordinance No.3605
Page 13 of 23
R9O2.1 Roofing covering materials. Roofs shall be covered with materials as set forth
in Sections R9O4 and R9O5. Class A, B, or C roofing shall be installed. Class A, B and C
roofing required by this section to be listed shall be tested in accordance with UL 790 or
ASTM E1O8.
Exceptions:
1. {text unchanged}
2. {text unchanged}
3. {text unchanged}
4. {text unchanged}
5. Non-classified roof coverings shall be permitted on one-story detached accessory
structures used as tool and storage sheds, playhouses and similar uses, provided
the floor area does not exceed 144 square feet
**Section R9O5.1O.3; Add sentence to prohibit corrugated steel roofing:
R9O5.1O.3 Material standards. {section unchanged}. Corrugated galvanized panels
shall be prohibited as a roofing material unless specifically listed for that purpose.
** Chapter 11 [RE] — Energy Efficiency is deleted in its entirety; Reference the 2015
IECC for energy code provisions and recommended amendments.
**Section M13O5.1.2; change to read as follows:
M13O5.1.2 Appliances in attics. Attics containing appliances shall be provided . . . {bulk
of paragraph unchanged} . . . side of the appliance. The clear access opening dimensions
shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), and large enough to
allow removal of the largest appliance. As a minimum, for access to the attic space,
provide one of the following:
1. A permanent stair.
2. A pull down stair with a minimum 300 lb (136 kg) capacity.
3. An access door from an upper floor level.
Exceptions: (unchanged)
**Section M1411.3; change to read as follows:
M1411.3 Condensate disposal. Condensate from all cooling coils or evaporators shall
be conveyed from the drain pan outlet to a sanitary sewer through a trap, by means of a
direct or indirect drain. {remaining text unchanged}.
Ordinance No.3605
Page 14 of 23
Exception: Condensate may be conveyed to other locations when approved by the
building official.
**Section M1411.3.1, Items 3 and 4; add text to read as follows:
M1411.3.1 Auxiliary and secondary drain systems. {bulk of paragraph unchanged}
1. {text unchanged}
2. {text unchanged}
3. An auxiliary drain pan... {bulk of text unchanged}... with Item 1 of this section. A
water level detection device may be installed only with prior approval of the building
official.
4. A water level detection device... {bulk of text unchanged}... overflow rim of such
pan. A water level detection device may be installed only with prior approval of the
building official.
**Section M1411.3.1.1; add text to read as follows:
M1411.3.1.1 Water-level monitoring devices. On down-flow units ...{bulk of text
unchanged}... installed in the drain line. A water level detection device may be installed
only with prior approval of the building official.
**Section M1502.4.5; amend to read as follows:
M1502.4.5 Duct length. The maximum allowable exhaust duct length shall be
determined by using the methods specified in Section M1502.4.5.1.
**Section M1502.4.5.2; delete.
**Section M1503.6 Makeup Air Required. Amend as follows:
M1503.6 Makeup air required. Where one or more gas, liquid or solid fuel-burning
appliance that is neither direct-vent nor uses a mechanical draft venting system is located
within a dwelling unit's air barrier, each exhaust system capable of exhausting in excess
of 400 cubic feet per minute (0.19 m3/s) shall be mechanically or passively provided with
makeup air at a rate approximate to the difference between exhaust air rate and 400 cubic
feet per minute. Such makeup air systems shall be equipped with not fewer than one
damper complying with Section M1503.6.2.
Ordinance No.3605
Page 15 of 23
Exception: Makeup air is not required for exhaust systems installed for the
exclusive purpose of space cooling and intended to be operated only when
windows or other air inlets are open. Where all appliances in the house are of
sealed combustion, power-vent, unvented, or electric, the exhaust hood system
shall be permitted to exhaust up to 600 cubic feet per minute (0.28 m3/s) without
providing makeup air. Exhaust hood systems capable of exhausting in excess of
600 cubic feet per minute (0.28 m3/s) shall be provided with a makeup air at a rate
approximately to the difference between the exhaust air rate and 600 cubic feet
per minute.
**Section M1504.1; add second sentence as follows:
M1504.1 Exhaust ducts. Where duct construction ... {remainder of sentence
unchanged}. Ducts located in inaccessible areas that are concealed within the building's
construction shall have a smooth interior finish and be constructed of metal having a
minimum thickness of 0.0157 inches (0.3950 mm) (No. 28 gage).
**Section M2005.2; change to read as follows:
M2005.2 Prohibited locations. Fuel-fired water heaters shall not be installed in a room
used as a storage closet. Water heaters located in a bedroom or bathroom shall be
installed in a sealed enclosure so that combustion air will not be taken from the living
space. Access to such enclosure may be from the bedroom or bathroom when through a
solid door,weather-stripped in accordance with the exterior door air leakage requirements
of the International Energy Conservation Code and equipped with an approved self-
closing device. Installation of direct-vent water heaters within an enclosure is not required.
**Section G2404.12;Add new section to read as follows:
Gas risers. Unless approved by the code official, all risers connecting underground
plastic gas piping and tubing shall be anodeless per section G2414.6.1 of this code.
**Section G2415.2.1 (404.2.1) CSST; add a second paragraph to read as follows:
Both ends of each section of medium pressure gas piping shall identify its operating gas
pressure with an approved tag. The tags are to be composed of aluminum or stainless
steel and the following wording shall be stamped into the tag:
"WARNING: 1/2 to 5 psi gas pressure - Do Not Remove"
** Section G2415.2.2;add a third paragraph to read as follows:
When a gas distribution system of corrugated stainless steel tubing (CSST) is installed
that does not have enhanced lightning protection properties or an outer conductive jacket
and/or a wire mesh layer that is electrically continuous designed to provide lightening
resistance, a notarized affidavit shall be filed with Tarrant County Records indicating that
Ordinance No.3605
Page 16 of 23
non-lightning resistant CSST has been installed in the home. A copy of the filed affidavit
shall be provided to the City of North Richland Hills at the time of permit application.
** Section G2415.12 (404.12); change to read as follows:
G2415.12 (404.12) Minimum burial depth. Underground piping systems shall be
installed a minimum depth of 18 inches (457 mm) below grade.
**G2415.12.1 (404.12.1) Individual Outdoor Appliances; Delete in its entirety
**Section G2417.1 (406.1); change to read as follows:
G2417.1 (406.1) General. Prior to acceptance and initial operation, all piping installations
shall be inspected and pressure tested to determine that the materials, design, fabrication,
and installation practices comply with the requirements of this code. The permit holder
shall make the applicable tests prescribed in Sections 2417.1.1 through 2417.1.5 to
determine compliance with the provisions of this code. The permit holder shall give
reasonable advance notice to the building official when the piping system is ready for
testing. The equipment, material, power and labor necessary for the inspections and test
shall be furnished by the permit holder and the permit holder shall be responsible for
determining that the work will withstand the test pressure prescribed in the following tests.
**Section G2417.4; change to read as follows:
G2417.4.1 (406.4.1) Test pressure. The test pressure to be used shall be no less than
3 psig (20 kPa gauge), or at the discretion of the Code Official, the piping and valves may
be tested at a pressure of at least six (6) inches (152 mm) of mercury, measured with a
manometer or slope gauge. For tests requiring a pressure of 3 psig, diaphragm gauges
shall utilize a dial with a minimum diameter of three and one half inches (31/2"), a set hand,
1/10 pound incrementation and pressure range not to exceed 6 psi for tests requiring a
pressure of 3 psig. For tests requiring a pressure of 10 psig, diaphragm gauges shall
utilize a dial with a minimum diameter of three and one-half inches (3 1/2"), a set hand, a
minimum of 2/10 pound incrementation and a pressure range not to exceed 20 psi. For
welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches
water column pressure (3.48 kPa) (1/2 psi) and less than 200 inches of water column
pressure (52.2 kPa) (7.5 psi), the test pressure shall not be less than ten (10) pounds per
square inch (69.6 kPa). For piping carrying gas at a pressure that exceeds 200 inches of
water column (52.2 kPa) (7.5 psi), the test pressure shall be not less than one and one-
half times the proposed maximum working pressure.
Diaphragm gauges used for testing must display a current calibration and be in good
working condition. The appropriate test must be applied to the diaphragm gauge used for
testing.
Ordinance No.3605
Page 17 of 23
**Section G2417.4.2; change to read as follows:
G2417.4.2 (406.4.2) Test duration. The test duration shall be held for a length of time
satisfactory to the Building Official, but in no case for less than fifteen (15) minutes. For
welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches
water column pressure (3.48 kPa), the test duration shall be held for a length of time
satisfactory to the Building Official, but in no case for less than thirty (30) minutes.
**Section G2420.1 (406.1); add Section G2420.1.4 to read as follows:
G2420.1.4 Valves in CSST installations. Shutoff valves installed with corrugated
stainless steel (CSST) piping systems shall be supported with an approved termination
fitting, or equivalent support, suitable for the size of the valves, of adequate strength and
quality, and located at intervals so as to prevent or damp out excessive vibration but in no
case greater than 12-inches from the center of the valve. Supports shall be installed so
as not to interfere with the free expansion and contraction of the system's piping, fittings,
and valves between anchors. All valves and supports shall be designed and installed so
they will not be disengaged by movement of the supporting piping.
**Section G2420.5.1 (409.5.1); add text to read as follows:
G2420.5.1 (409.5.1) Located within the same room. The shutoff valve ...{bulk of
paragraph unchanged}... in accordance with the appliance manufacturer's instructions. A
secondary shutoff valve must be installed within 3 feet (914 mm) of the firebox if appliance
shutoff is located in the firebox.
**Section G2421.1 (410.1); add text and Exception to read as follows:
G2421.1 (410.1) Pressure regulators. A line pressure regulator shall be ... {bulk of
paragraph unchanged}... approved for outdoor installation. Access to regulators shall
comply with the requirements for access to appliances as specified in Section M1305.
Exception:A passageway or level service space is not required when the regulator is
capable of being serviced and removed through the required attic opening.
**Section G2422.1.2.3 (411.1.3.3); delete Exception 1 and Exception 4.
**Section G2445.2 (621.2); add Exception to read as follows:
G2445.2 (621.2) Prohibited use. One or more unvented room heaters shall not be used
as the sole source of comfort heating in a dwelling unit.
Exception: Existing approved unvented room heaters may continue to be used in
dwelling units, in accordance with the code provisions in effect when installed,
when approved by the Building Official unless an unsafe condition is determined
to exist as described in International Fuel Gas Code Section 108.7 of the Fuel Gas
Code.
Ordinance No.3605
Page 18 of 23
**Section G2448.1.1 (624.1.1); change to read as follows:
G2448.1.1 (624.1.1) Installation requirements. The requirements for water heaters
relative to access, sizing, relief valves, drain pans and scald protection shall be in
accordance with this code.
**Section P2603; add to read as follows:
P2603.3 Protection against corrosion. Metallic piping, except for cast iron, ductile iron
and galvanized steel, shall not be placed in direct contact with steel framing members,
concrete or cinder walls and floors or other masonry. Metallic piping shall not be placed
in direct contact with corrosive soil. Where sheathing is used to prevent direct contact, the
sheathing shall have a thickness of not less than 0.008 inch (8 mil) (0.203 mm) and the
sheathing shall be made of approved material. Where sheathing protects piping that
penetrates concrete or masonry walls or floors, the sheathing shall be installed in a
manner that allows movement of the piping within the sheathing.
**Section P2603.5.1 Sewer Depth; change to read as follows:
P2603.5.1 Sewer depth. Building sewers that connect to private sewage disposal
systems shall be a minimum of 12 inches (304mm) below finished grade at the point of
septic tank connection. Building sewers shall be a minimum of 12 inches (304 mm) below
grade.
**Section P2604; add to read as follows:
P2604.2.1 Plastic sewer and DWV piping installation. Plastic sewer and DWV piping
installed underground shall be installed in accordance with the manufacturer's installation
instructions.
**Section P2610; add new section to read as follows:
SECTION P2610
LANDSCAPE IRRIGATION
P2610. Landscape Irrigation. The landscape irrigation rules promulgated by the Texas
Commission on Environmental Quality and contained in Chapter 344, Subchapters A, E
and F, of the TEXAS ADMINISTRATIVE CODE, as the same may be from time to time
amended, are hereby adopted by reference as the landscape irrigation rules of the City.
** Section P2801; change to read as follows:
P2801.6 Required pan. Where a storage tank-type water heater or a hot water storage
tank is installed in a location where water leakage from the tank will cause damage, the
tank shall be installed in a pan constructed of one of the following:
Ordinance No.3605
Page 19 of 23
1. Galvanized steel or aluminum of not less than 0.0236 inch (0.6010 mm) in
thickness.
2. Plastic not less than 0.036 inch (0.9 mm) in thickness.
3. Other approved materials.
**Section P2801.6.1; change to read as follows:
P2801.6.1 Pan size and drain. The pan shall be not less than 1-1/2 inches (38 mm) in
depth and shall be of sufficient size and shape to receive all dripping or condensate from
the tank or water heater. The pan shall be drained by an indirect waste pipe having a
diameter of not less than 3/4 inch (19 mm). Piping for safety pan drains shall be of those
materials listed in Table P2906.5.
Multiple pan drains may terminate to a single discharge piping system when approved by
the administrative authority and permitted by the manufactures installation instructions
and installed with those instructions. {existing text unchanged)
**Section P2804.6.1; change to read as follows:
P2804.6.1 Requirements for discharge piping.The discharge piping serving a pressure
relief valve, temperature relief valve or combination thereof shall:
1. Not be directly connected to the drainage system.
2. Discharge through an air gap.
3. Not be smaller than the diameter of the outlet of the valve served and shall
discharge full size to the air gap.
4. Serve a single relief device and shall not connect to piping serving any other relief
device or equipment.
Exception: Multiple relief devices may be installed to a single T & P discharge
piping system when approved by the administrative authority and permitted by
the manufactures installation instructions and installed with those instructions.
5. Discharge to an approved location or to the outdoors.
{remainder unchanged}
**Section P2902.5.3; change to read as follows:
P2902.5.3 Lawn irrigation systems. The potable water supply to lawn irrigation systems
shall be protected against backflow by an atmospheric-type vacuum breaker, a pressure-
type vacuum breaker, a double-check assembly or a reduced pressure principle backflow
preventer. A valve shall not be installed downstream from an atmospheric vacuum
breaker. Where chemicals are introduced into the system, the potable water supply shall
be protected against backflow by a reduced pressure principle backflow preventer.
**Section P3003.9; delete exceptions to read as follows:
Ordinance No.3605
Page 20 of 23
P3003.9.2 Solvent cementing. Joint surfaces shall be clean and free from moisture. A
purple primer that conforms to ASTM F 656 shall be applied. Solvent cement not purple
in color and conforming to ASTM D 2564, CSA B137.3, CSA B181.2 or CSA B182.1 shall
be applied to all joint surfaces. The joint shall be made while the cement is wet and shall
be in accordance with ASTM D 2855. Solvent cement joints shall be permitted above or
below ground.
**Section P3111.1; modify section as follows:
P3111.1 Type of fixtures. In circumstances in which conventional plumbing methods
cannot be utilized, and where approved by the code official, a combination waste and vent
system may serve floor drains, sinks, {remainder of section unchanged}
**Section P3112.2 Vent Connection; delete and replace with the following:
P3112.2 Installation. Traps for island sinks and similar equipment shall be roughed in
above the floor and may be vented by extending the vent as high as possible, but not less
than the drainboard height and then returning it downward and connecting it to the
horizontal sink drain immediately downstream from the vertical fixture drain. The return
vent shall be connected to the horizontal drain through a wye-branch fitting and shall, in
addition, be provided with a foot vent taken off the vertical fixture vent by means of a wye-
branch immediately below the floor and extending to the nearest partition and then
through the roof to the open air or may be connected to other vents at a point not less
than six (6) inches (152 mm) above the flood level rim of the fixtures served. Drainage
fittings shall be used on all parts of the vent below the floor level and a minimum slope of
one-quarter (1/4) inch per foot (20.9 mm/m) back to the drain shall be maintained. The
return bend used under the drain-board shall be a one (1) piece fitting or an assembly of
a forty-five (45) degree (0.79 radius), a ninety (90) degree (1.6 radius) and a forty-five (45)
degree (0.79 radius)elbow in the order named. Pipe sizing shall be as elsewhere required
in this Code. The island sink drain, upstream of the return vent, shall serve no other
fixtures. An accessible cleanout shall be installed in the vertical portion of the foot vent.
** Section P3114.1;section as follows:
P3114.1 General. Vent systems using mechanical vents and/or air admittance valves
shall only be installed when conditions exist that would prevent the venting methods
prescribed in sections P3101 through P3113 and when approved by the building official.
Mechanical vents and/or air admittance valves shall not be used in new construction or
as an alternate to section P3112. Vent systems using air admittance valves shall
comply... {remainder of section unchanged}.
SECTION 4: Any person intentionally, knowingly, recklessly, or with criminal
negligence violating any of the provisions of this ordinance shall be
deemed guilty of a misdemeanor and upon conviction thereof shall be
fined an amount not to exceed two thousand dollars ($2,000). Each day
Ordinance No.3605
Page 21 of 23
any such violation shall be allowed to continue shall constitute a separate
violation and be punishable hereunder.
SECTION 5: This Ordinance shall be cumulative of all provisions of the Code of
Ordinances of the City of North Richland Hills, except where the provisions
of this Ordinance are in direct conflict with the provisions of such ordinances
and such Code, in which event conflicting provisions of such ordinances and
such Code are hereby repealed.
SECTION 6: All rights and remedies of the City of North Richland Hills are expressly
saved as to any and all violations of the provisions of any ordinances in
the Code of Ordinances of the City of North Richland Hills that have
accrued at the time of the effective date of this Ordinance; and, as to such
accrued violations and all pending litigation, both civil and criminal,
whether pending in court or not, under such ordinances, same shall not
be affected by this Ordinance but may be prosecuted until final disposition
by the courts.
SECTION 7: It is hereby declared to be the intention of the City Council that the
phrases, clauses, sentences, paragraphs and sections of this ordinance
are severable, and if any phrase, clause, sentence, paragraph or section
of this ordinance shall be declared unconstitutional by the valid judgment
or decree of any court of competent jurisdiction, such unconstitutionality
shall not affect any of the remaining phrases, clauses, sentences,
paragraphs and sections of this ordinance, since the same would have
been enacted by the City Council without the incorporation in this
ordinance of any such unconstitutional phrase, clause, sentence,
paragraph or section.
SECTION 8: This Ordinance shall be in full force and effect from and after its passage
and publication as required by law.
AND IT IS SO ORDAINED.
PASSED AND APPROVED on this 23rd day of September, 2019.
CITY OF N TH RIC ND LS:
By:
Oscar Tre o, yor
Ordinance No.3605
Page 22 of 23
ATTEST:
i\iilffitli#I,JF,/!/Jlfj�`�
b`kiLte,_)
•
Alicia Richardsongeity Secr tary `,
APPROVED AS TO k)RMll' #► D LEGALITY:
aleshia B. McGinnis, City Attorney
APPROVED AS TO CONTENT:
Clayton C stock, Dire or of Planning
Ordinance No.3605
Page 23 of 23
Star-Telegram SCANN,�
MEDIA D
Arlington Citizen-Journal 1 The Keller Citizen 1 La Estrella n 20
Mansfield News-Mirror I Star-Telegram Northeast 1 Weatherford Star-Telegram OC 2 2019
star-telegram.com 1 808 Throckmorton St.1 Ft Worth,Tx.76102-6315 T
AFFIDAVIT OF PUBLICATION
A- 0..._- L-,
Account# Ad Number Identification PO Amount Cols Depth
600579 0004395016 CITY OF NORTH RICHLAND HILLSORDINANC ORDINANCE NO.3605 $83.96 1 47.00 Li
Attention: Traci Henderson THE STATE OF TEXAS
CITY OF NORTH RICHLAND HILLS County of Tarrant
PO BOX 820609
NORTH RICHLAND HILLS, TX 761820609 Before me,a Notary Public in and for
said County and State,this day
personally appeared VICTORAI
CITY OF NORTH RICHLAND HILLS
ORDINANCE NO.3605 RODELA, Bid and Legal Coordinator
AN ORDINANCE OF THE CITY for the Star-Telegram,published by
COUNCIL OF THE CITY OF
NORTH RICHLAND HILLS, the Star-Telegram, Inc. at Fort Worth,
TEXAS, AMENDING CHAPTER
98 OF THE NORTH RICHLAND in Tarrant County,Texas;and who,
HILLS CODE OF ORDINANCES,
ADOPTING THE 2018 INTERNA- after being duly sworn,did depose
TIONAL RESIDENTIAL CODE AS .
AMENDED AS THE RESIDEN- CITY OF NORTH RICHLAND HILLS and say that the attached clipping of
TIAL CODE OF THE CITY OF ORDINANCE NO.3605
NORTH RICHLAND HILLS;PRO- AN ORDINANCE OF THE CITY an advertisement was published in
VIDING A PENALTY; PROVID- COUNCIL OF THE CITY OF the above named paper on the listed
ING THAT THIS ORDINANCE NORTH RICHLAND HILLS,
SHALL BE CUMULATIVE OF ALL TEXAS, AMENDING CHAPTER dates:
ORDINANCES AND REPEAL OF 98 OF THE NORTH RICHLAND
CONFLICTING PROVISIONS; HILLS CODE OF ORDINANCES,
PROVIDING SAVINGS CLAUSE; ADOPTING THE 2018 INTERNA-
PROVIDING A SEVERABILITY TIONAL RESIDENTIAL CODE AS
CLAUSE; AND PROVIDING AN AMENDED AS THE RESIDEN- '
EFFECTIVE DATE. TIAL CODE OF THE CITY OF
Any person intentionally,knowing- NORTH RICHLAND HILLS;PRO- I 2 Insertion(s)
ly, recklessly, or with criminal VIDING A PENALTY; PROVID-
negligence violating any of the ING THAT THIS ORDINANCE
provisions of this ordinance SHALL BE CUMULATIVE OF ALL Published On:
shall be deemed guilty of a mis- ORDINANCES AND REPEAL OF
demeanor and upon conviction CONFLICTING PROVISIONS; September 26,2019,September
not to shall be fined an samount PROVIDING SAVINGS CLAUSE;
not to exceed two thousand dol- PROVIDING A SEVERABILITY 27,2019
lars Lion shall Each day any such CLAUSE; AND PROVIDING AN
violation shall be allowed to
continue shall constitute a sep- EFFECTIVE DATE.
arate violation and be punisha- Any person intentionally,knowing-
ble hereunder. ly, recklessly, or with criminal
PASSED AND APPROVED on this negligence violating any of the
23rd day of September,2019. provisions of this ordinance
CITY OF NORTH RICHLAND HILLS shall be deemed guilty of a mis-
By:/s/Oscar Trevino_ demeanor and upon conviction
Mayor thereof shall be fined an amount
ATTEST: not to exceed two thousand dol-
/s/Alicia Richardson lars($2,000).Each day any such
City Secretary violation shall be allowed to
APPROVED AS TO FORM AND LE- continue shall constitute a sep-
GAL ITY: arate violation and be punisha- 7:471L
/s/Maleshia McGinnis S hereunder.
Attorney Attornn ey PASSSED AND APPROVED on this
23rd day of September,2019.
CITY OF NORTH RICHLAND HILLS
By:/s/Oscar Trevino_ (Principal Clerk)
Mayor
ATTEST:
/s/Alicia Richardson SUBSCRIBED AND SWORN TO
City Secretary
APPROVED AS TO FORM AND LE- BEFORE ME,THIS 27th day of
GALITY:
/s/Maleshia B.McGinnis September in the year of 2119
City Attorney
ilk ° 11
Noo'ublic-
*. ,/,..i.., •" My NCtc^;.^v IL:#1S2031291
V?'.Y V,7;°,..:
--,71-6,..F SVr., Expires s I,f Dp J0,2023
-' :: :r-_.3r.+mstiKr::-..ex:-ii:wvu_, Extra charge for lost or duplicate affidavits.
Legal document please do not destroy!