HomeMy WebLinkAboutOrdinance 3611 ORDINANCE NO. 3611
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF NORTH
RICHLAND HILLS, TEXAS, AMENDING CHAPTER 98, ARTICLE VI, OF
THE NORTH RICHLAND HILLS CODE OF ORDINANCES, ADOPTING
THE 2017 NATIONAL ELECTRICAL CODE AS AMENDED AS THE
OFFICIAL ELECTRICAL CODE OF THE CITY OF NORTH RICHLAND
HILLS; AMENDING OTHER PROVISIONS OF CHAPTER 98, ARTICLE
VI; PROVIDING A PENALTY; PROVIDING THAT THIS ORDINANCE
SHALL BE CUMULATIVE OF ALL ORDINANCES AND REPEAL OF
CONFLICTING PROVISIONS; PROVIDING SAVINGS CLAUSE;
PROVIDING A SEVERABILITY CLAUSE; AND PROVIDING AN
EFFECTIVE DATE.
WHEREAS, the City of North Richland Hills, Texas ("the City") is a home rule city acting
under its power adopted by the electorate pursuant to Article XI, Section 5
of the Texas Constitution and Chapter 9 of the Local Government Code;
and
WHEREAS, The 2017 edition of the National Electrical Code (NEC) as published by the
National Fire Protection Association, became the official electrical code of
Texas on September 1, 2017 through the Texas Electrical Safety and
Licensing Act; and
WHEREAS, the City of North Richland Hills deems it necessary to adopt this ordinance
providing minimum standards to safeguard the health, property, and
welfare of its citizens by regulating and controlling the use, occupancy,
maintenance, repair, design, construction and materials for buildings and
structures within the City; and
WHEREAS, the City of North Richland Hills has previously adopted versions of the
National Electrical Code, codified in Article VI "Electrical Standards" of
Chapter 98 " Buildings and Building Regulations" of the North Richland Hills
Code of Ordinances; and
WHEREAS, the City having reviewed the available codes and desires to adopt the 2017
National Electrical Code with amendments recommended by the North
Central Texas Council of Governments and other amendments proposed
by staff in order to better provide for the safety of its residents and their
property; and
WHEREAS, the North Richland Hills Construction Code Appeals Board acting in its
capacity as the Construction Advisory Board has reviewed and
recommends the adoption of the 2017 National Electrical Code with
amendments recommended by the North Central Texas Council of
Governments and other amendments proposed by staff; and
Ordinance No.3611
Page 1 of 14
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF
NORTH RICHLAND HILLS, TEXAS:
SECTION 1: The City Council hereby finds the recitals above to be true and correct,
and such recitals are hereby incorporated into this Ordinance as if written
herein.
SECTION 2: THAT Section 98-232 of Article VI "Electrical Standards" of Chapter 98
"Buildings and Building Regulations" of the North Richland Hills Code of
Ordinances is hereby amended to read as follows:
Sec. 98-232 2017 edition of the National Electric Code adopted.
All electrical equipment installed or used in the city and all installations of electrical
equipment shall be reasonably safe to persons and property and in conformity with the
standards provided by the National Fire Protection Association, and with the provisions
of this chapter, applicable state statutes, and any rules or regulations issued under
authority thereof. The National Electrical Code, 2017 edition, including Annex H (Article
80), as published by the National Fire Protection Association, a copy of which is on file in
the office of the city secretary, and the regional amendments and interpretations thereto
recommended by the North Central Texas Council of Governments, as further amended
by the City of North Richland Hills set out in section 98-233 hereof is hereby adopted by
reference to the same extent as though set out here in full as the Electrical Code of the
City of North Richland Hills.
SECTION 3: Section 98-233 of Article VI "Electrical Standards" of Chapter 98 "Buildings
and Building Regulations" of the North Richland Hills Code of Ordinances
is hereby amended to read as follows:
Sec. 98-233.-Amendments to the 2017 National Electric Code
The 2017 National Electrical Code is hereby modified by the following amendments:
*Article 80.11(C) and(D) - add new paragraphs.
80.11(C) Change in occupancy. It shall be unlawful to make a change in the
occupancy type or use of any structure which will subject the structure to any
special provision of this code applicable to the new occupancy without approval of
the code official. The code official shall certify that such structure meets the intent
of the provisions of law governing building construction for the proposed new
occupancy and that such change of occupancy does not result in any hazard to
the public health, safety or welfare.
Ordinance No.3611
Page 2 of 14
No change shall be made in the use or occupancy of any building that would place
the building in a different division of the same group of occupancy or in a different
group of occupancies as defined by the building code, unless such building is
made to comply with the requirements of this code for such division or group of
occupancy. Subject to the approval of the code official, the use or occupancy of
existing buildings shall be permitted to be changed and the building is allowed to
be occupied for purposes in other groups without conforming to all the
requirements of this code for those groups, provided the new or proposed use is
less hazardous, based on life and fire risk, than the existing use.
80.11(D) Moved buildings. Electrical systems and equipment that are a part of
buildings or structures moved into or within the jurisdiction shall comply with the
provisions of this code for new installations.
EXCEPTIONS: The factory installed and inspected systems of:
1. HUD or Texas State approved mobile and manufactured homes
2. Texas State approved modular homes.
3. Texas State approved industrialized buildings
*Article 80.15 Electrical Board- Delete entire section.
*Article 80.19(D) - Delete paragraph D.
*Article 80.19(E) Amend as follows:
Fees for electrical permits shall be paid by the applicant before the permit is issued
in accordance with Appendix A — Fee Schedule in the North Richland Hills Code
of Ordinances.
* Article 80.19(F)2 & 4 - Delete paragraphs
*Article 80.23(A) — Replace to read as follows:
80.23(A) Unlawful acts. It shall be unlawful for any person, firm or corporation to
erect, construct, alter, repair, remove, demolish or utilize any electrical system or
equipment, or cause same to be done, in conflict with or in violation of any of the
provisions of this code.
*Article 80.23(C, D, E, & F) —Add sections to read as follows:
Ordinance No.3611
Page 3 of 14
80.23(C) Stop work orders. Upon notice from the code official, work on any
electrical system that is being done contrary to the provisions of this code or in a
dangerous or unsafe manner shall immediately cease. Such notice shall be in
writing and shall be given to the owner of the property, or to the owner's agent, or
to the person doing the work or causing such work to be done. Where an
emergency exists, the code official shall not be required to give a written notice
prior to stopping the work. Such work shall not resume until authorized by the code
official to proceed.
80.23(D) Abatement of violation. The imposition of the penalties herein
prescribed shall not preclude the legal officer of the jurisdiction from instituting
appropriate action to prevent unlawful construction or to restrain, correct or abate
a violation, or to prevent illegal occupancy of a building, structure or premises, or
to stop an illegal act, conduct, business or utilization of the electrical on or about
any premises.
80.23(E) Unsafe electrical systems or equipment. Any electrical system or
equipment regulated by this code that is unsafe or that constitutes a fire or health
hazard, unsanitary condition, or is otherwise dangerous to human life is hereby
declared unsafe. Any use of an electrical system or equipment regulated by this
code constituting a hazard to safety, health or public welfare by reason of improper
installation, inadequate maintenance, dilapidation, obsolescence, fire hazard,
disaster, damage or abandonment is hereby declared an unsafe use. Any such
unsafe equipment is hereby declared to be a public nuisance and shall be abated
by repair, rehabilitation, demolition or removal.
When any electrical system or equipment is maintained in violation of this code,
and in violation of any notice issued pursuant to the provisions of this section, the
code official may institute any appropriate action to prevent, restrain, correct or
abate the violation.
All buildings or structures subjected to damage by deterioration or by fire shall be
inspected by the code official, and all unsafe wiring or electrical equipment shall
be repaired or replaced.
80.23(F) Authority to condemn. Whenever the code official determines that any
electrical system or equipment, or portion thereof, regulated by this code has
become hazardous to life, health or property or has become unsanitary, or is
otherwise dangerous to human life, the code official shall order in writing that such
electrical system or equipment either be removed or restored to a safe or sanitary
Ordinance No.3611
Page 4 of 14
condition. A time limit for compliance with such order shall be specified in the
written notice. No person shall use or maintain defective electrical after receiving
such notice.
*Article 80.25- Delete and replace as follows:
80.25(A) Authority to order disconnection of utilities. The code official shall
have the authority to order disconnection of any energy source or utility service
supplied to a building, structure or equipment regulated by this code when it is
determined that the equipment or any portion thereof has become hazardous,
unsanitary, or being used in violation of this code. The code official shall also have
the authority to order disconnection of any energy source or utility service supplied
to a building, structure or equipment regulated by this code when it is determined
that a building or property is being used without a valid certificate of occupancy or
in violation of a valid certificate of occupancy. Written notice of such order to
disconnect service and the causes thereof may be given within 24 hours to the
owner and occupant of such building, structure or premises, provided, however,
that in cases of immediate danger to life or property, such disconnection shall be
made immediately without such notice. If not notified prior to disconnecting, the
owner or occupant of the building, structure or service systems may be notified in
writing, as soon as practical thereafter.
80.25(B) Connection after order to disconnect. No person shall make
connections from any energy, fuel, power supply or water distribution system or
supply energy, fuel or water to any equipment regulated by this code that has been
disconnected or ordered to be disconnected by the code official or the use of which
has been ordered to be discontinued by the code official until the code official
authorizes the reconnection and use of such equipment.
*Article 80.27- Delete and replace as follows:
80.27(A) Code official. Whenever the term "code official" or "electrical inspector"
is used in this code, it shall be construed to mean the building official or his
authorized representative(s).
80.27(B) Deputies. In accordance with the prescribed procedures of this
jurisdiction, the code official shall have the authority to appoint an assistant code
official, other related technical officers, inspectors, and other employees.
Ordinance No. 3611
Page 5 of 14
80.27(C) Restriction of employees. An official or employee connected with the
department of inspection shall not be engaged in directly or indirectly with the
furnishing of labor, materials or appliances for the construction, alteration or
maintenance of a building within the City of North Richland Hills; and such officer
or employee shall not engage in any work that conflicts with official duties or with
the interests of the department.
Further no official or employee shall be permitted to work for, or be connected with,
any electrical contractor, electrical manufacturer or wholesale supply company, or
do any electrical work within the City of North Richland Hills while employed as an
inspector by the city.
80.27(D) Liability. The code official charged with the enforcement of this code,
acting in good faith and without malice in the discharge of the duties required by
this code or other pertinent law or ordinance shall not thereby be rendered
personally liable for damages that may accrue to persons or property as a result
of an act or by reason of an act or omission in the discharge of such duties. A suit
brought against the code official or employee because of such act or omission
performed by the code official or employee in the enforcement of any provision of
such codes or other pertinent laws or ordinances implemented through the
enforcement of this code or enforced by the code enforcement agency shall be
defended by this jurisdiction until final termination of such proceedings and any
judgment resulting there from shall be assumed by this jurisdiction.
Add new Article 80.28:
80.28 Who May do the Work.
80.28(A) General. It shall be unlawful for any person to do or cause to be done
any electrical work within the City of North Richland Hills except as provided in this
section. Doing work other than what is authorized by this section is considered a
violation by the worker as well as the master and/or contractor.
Master electrician. A master electrician may contract for and engage in the
business of installing, repairing, or replacing electrical wiring or equipment of any
nature on or in buildings or structures. The master electrician may employ, direct
and supervise journeyman electricians, residential wireman electricians,
maintenance electricians, residential maintenance electricians, helpers, and
apprentice electricians as allowed by state statute.
Ordinance No.3611
Page 6 of 14
80.28(B) Home owner permits/projects. Permits may be issued to a property
owner who wishes to do electrical work in their owner-occupied homestead. This
provision authorizes the homeowner to work on that part of the electrical system
that occurs after, but does not include, the first main breaker behind the electrical
meter or the meter base. Work under this provision is authorized to be done solely
by the homeowner and shall not be subcontracted or delegated to other persons.
*Add additional paragraph to Article 90.4
Supervision of Work. In the actual work of installing, maintaining, altering or
repairing any electric conductors or equipment which requires a permit, apprentice
electricians shall be directly supervised by an on-site journeyman electrician when
electrical work is being performed. At no time shall an unlicensed or licensed
apprentice electrician be allowed to install, maintain, alter or repair any electrical
conductors or equipment which requires a permit without direct on-site supervision
by a journeyman electrician licensed by the State of Texas.
*Article 100;amend the following definition:
Intersystem Bonding Termination. A device that provides a means for connecting
intersystem bonding conductors for communication systems to the grounding
electrode system.
*Article 110.2; change the following to read as follows:
110.2 Approval. The conductors and equipment required or permitted by this
Code shall be acceptable only if approved. Approval of equipment may be evident
by listing and labeling of equipment by a Nationally Recognized Testing Lab
(NRTL) with a certification mark of that laboratory or a qualified third party
inspection agency approved by the AHJ.
Exception: Unlisted equipment that is relocated to another location within a
jurisdiction or is field modified is subject to the approval by the AHJ. This
approval may be by a field evaluation by a NRTL or qualified third party
inspection agency approved by the AHJ.
Informational Note No. 1: See 90.7, Examination of Equipment for Safety,
and 110.3, Examination, Identification, Installation, and Use of Equipment.
See definitions of Approved, Identified, Labeled, and Listed.
Ordinance No.3611
Page 7 of 14
Informational Note No. 2:Manufacturer's self-certification of equipment may
not necessarily comply with US product safety standards as certified by a
Nationally Recognized Testing Lab.
Informational Note No. 3: NFPA 790 and 791 provide an example of an
approved method for qualifying a third party inspection agency.
*Article 210.52(G) (1) Garages: replace as follows:
(1) Garages. In each attached garage and in each detached garage with electric
power. At least one receptacle outlet shall be installed for each car space.
*Article 230.2(A) add a seventh special condition.
(7) In supplying electrical service to multifamily dwellings, two or more laterals
or overhead service drops shall be permitted to a building when the following
conditions are met:
a. The building has six or more individual gang meters and all meters are
grouped at the same location.
b. Each lateral or overhead service drop originates from the same point of
service.
c. The building contains an automatic fire sprinkler system throughout.
d. The area served by each electrical service is separated from other
area(s) served by a separate electrical service by approved fire walls
constructed in accordance with the International Building Code.
*Article 250.52(1) add a paragraph.
Where the code official has determined that a metal underground water pipe is not
present or is unsuitable, a method of grounding as specified in (2) through (4)
below shall be used.
*Section 310.104(B); change to read as follows:
310.104(B) Conductor material. Conductors in this article shall be of copper
unless otherwise specified. Aluminum conductor materials shall not be installed;
however, aluminum conductors or copper-clad aluminum conductors may be
utilized for service entrance and feeder conductors of 1/0 in size or larger.
Aluminum conductors or copper-clad aluminum conductors shall not be utilized for
branch circuits or other wiring methods.
*Article 500.8(A)(3); change to read as follows:
Ordinance No. 3611
Page 8 of 14
500.8 Equipment. Articles 500 through 504 require equipment construction and
installation standards that ensure safe performance under conditions of proper use
and maintenance.
Informational Note No. 1: It is important that inspection authorities and users
exercise more than ordinary care with regard to installation and maintenance.
Informational Note No. 2: Since there is no consistent relationship between
explosion properties and ignition temperature, the two are independent
requirements.
Informational Note No. 3: Low ambient conditions require special
consideration. Explosion proof or dust-ignition proof equipment may not be
suitable for use at temperatures lower than -25°C (-13°F) unless they are
identified for low-temperature service. However, at low ambient temperatures,
flammable concentrations of vapors may not exist in a location classified as
Class I, Division 1 at normal ambient temperature.
(A) Suitability. Suitability of identified equipment shall be determined by one
of the following:
(1) Equipment listing or labeling
(2) Evidence of equipment evaluation from a qualified testing laboratory or
inspection agency concerned with product evaluation
(3) Evidence acceptable to the authority having jurisdiction such as a
manufacturer's self-evaluation or an engineering judgment signed and
sealed by a qualified Licensed Professional Engineer in the State of Texas.
Informational Note: Additional documentation for equipment may include
certificates demonstrating compliance with applicable equipment
standards, indicating special conditions of use, and other pertinent
information.
*Article 505.7(A) changed to read as follows:
505.7 Special Precaution. Article 505 requires equipment construction and
installation that ensures safe performance under conditions of proper use and
maintenance.
Informational Note No. 1: It is important that inspection authorities and users
exercise more than ordinary care with regard to the installation and maintenance
of electrical equipment in hazardous (classified) locations.
Ordinance No.3611
Page 9 of 14
Informational Note No. 2: Low ambient conditions require special consideration.
Electrical equipment depending on the protection techniques described by
505.8(A) may not be suitable for use at temperatures lower than -20°C (-4°F)
unless they are identified for use at lower temperatures. However, at low ambient
temperatures, flammable concentrations of vapors may not exist in a location
classified Class I, Zones 0, 1, or 2 at normal ambient temperature.
(A)Implementation of Zone Classification System. Classification of areas,
engineering and design, selection of equipment and wiring methods,
installation, and inspection shall be performed by a qualified Licensed
Professional Engineer in the State of Texas.
*Article 517.2 Definitions. (Health Care Facility); modify as follows:
Medical Office (Dental Office).
A building or part thereof in which the following occur:
(1) (unchanged)
(2) No sedation is involved (including the use of nitrous oxide) and only local
anesthesia is involved where treatment or procedures do not render the patient
incapable of self-preservation under emergency conditions
(3) (unchanged)
*Article 517.30 Essential Electrical Systems for Hospitals; create a new (H)
and add the following language:
(G) Coordination. Overcurrent protective devices serving the equipment branch
of the essential electrical system shall be coordinated for the period of time that a
fault's duration extends beyond 0.1 second.
Exception No. 1: Between transformer primary and secondary overcurrent
protective devices, where only one overcurrent protective device or set of
overcurrent protective devices exists on the transformer secondary.
Exception No. 2: Between overcurrent protective devices of the same size
(ampere rating) in series.
Informational Note: The terms coordination and coordinated as used in this
section do not cover the full range of overcurrent conditions.
*Article 600.6(A) (1) At Point of Entry to a Sign; Exception 1 changed to read
as follows:
Ordinance No.3611
Page 10 of 14
Exception No.1: A disconnect shall not be required for branch circuits(s) or feeder
conductor(s) passing through the sign where enclosed in a Chapter 3 listed
raceway or metal-jacketed cable identified for the location. The conductor(s) shall
not serve the sign body or sign enclosure where passing through.
*Article 600.6(A) (1) At Point of Entry to a Sign; create a new Exception No. 2
to add the following language:
Exception No. 2. A disconnect shall not be required at the point of entry to a sign
body, sign enclosure, or pole for branch circuit conductor(s). The conductors shall
be enclosed in a Chapter 3 listed raceway or metal-jacketed cable identified for the
location. The conductor(s) shall be routed to a device box which contains the
disconnect. A field-applied permanent warning label that is visible during servicing
shall be applied to the raceway at or near the point of entry into the sign enclosure
or sign body. The warning label shall comply with 110.21(B) and state the
following: "Danger. This raceway contains energized conductors." The marking
shall include the location of the disconnecting means for the energized
conductor(s). The disconnecting means shall be capable of being locked in the
open position in accordance with 110.25.
*Article 600.6(A) (1) At Point of Entry to a Sign; move the original Exception
2 to create a new Exception No. 3 and add the following language:
Exception No. 3: A disconnect shall not be required at the point of entry to a sign
enclosure or sign body for branch circuit(s) or feeder conductor(s) that supply an
internal panelboard(s) in a sign enclosure or sign body. The conductors shall be
enclosed in a Chapter 3 listed raceway or metal-jacketed cable identified for the
location. A field-applied permanent warning label that is visible during servicing
shall be applied to the raceway at or near the point of entry into the sign enclosure
or sign body. The warning label shall comply with 110.21(B) and state the
following: "Danger. This raceway contains energized conductors." The marking
shall include the location of the disconnecting means for the energized
conductor(s). The disconnecting means shall be capable of being locked in the
open position in accordance with 110.25.
(2017 Code) Informational Note: The location of the disconnect is intended to allow
service or maintenance personnel complete and local control of the disconnecting
means.
**Article 680.22(E)1-3; add new section.
680.22(E)1. Door Alarms Serving Swimming Pools, Hot Tubs and Spa Areas.
Door alarms must be installed on all building doors providing direct access to a
swimming pool, hot tub and/or spa. Alarms shall be provided on all new residential
and commercial installations, existing single-family rental installations; as well as
existing residential and commercial installations that are substantially modified.
Ordinance No.3611
Page 11 of 14
Door alarms required by this section must be capable of meeting the following
specifications:
1. The alarm must sound continuously for a minimum of 30 seconds within 7
seconds after the door is opened.
2. The alarm must have a sound pressure rating of at least 85 dBA at 10 ft. and
be able to be heard throughout a residence. Alarms installed in commercial
buildings must have a sound pressure rating of at least 85 dBA at 10 ft. and
be able to be heard throughout the immediate area as determined by the code
official
3. The alarm must have an automatic reset.
4. When equipped with a deactivation switch, the switch or touch pad must be
placed at a height of 54 inches above the threshold of the door.
5. In new and existing construction the alarm may be battery operated or
connected to the electrical wiring of the building.
6. Door alarms shall be installed in such a way that it is unable to be removed
without the use of tools, keys, or other approved measures.
7. The alarm must have a manual means, such as a touch pad or switch, to
temporarily deactivate the alarm for a single opening for a maximum 15
seconds.
8. Door alarms shall be installed, used, and maintained in accordance with the
manufacturer's instructions.
680.22(E)2. Swimming Pool, Hot Tub and Spa Inspection. It shall be the
responsibility of the installer to insure that security and safety is provided at all
times a swimming pool, hot tub or spa is under construction. Prior to filling or
partially filling the swimming pool, hot tub or spa, the installer shall obtain a Pre-
Plaster/Pre-Fill Safety Inspection from the code official. All safety devices required
by the Authority Having Jurisdiction (AHJ) must be installed and in operable
condition prior to this inspection. Safety devices shall include, but may not be
limited to, a six foot tall perimeter fence, self-closing/self-latching gate(s), door
alarms required by 680.22(E)1; as well as rescue equipment required in
commercial applications by other ordinances.
680.22(E)3. Safety Video. The Code Official is hereby authorized to develop a
written policy requiring all new swimming pool, hot tub and/or spa owners to view
an approved water safety video prior to issuing the construction permit. This policy
shall also apply to the tenants of single-family rental properties prior to granting a
Certificate of Occupancy.
Ordinance No.3611
Page 12 of 14
**Article 680.25(A) replace section to read as follows:
680.25 Feeders. These provisions shall apply to any feeder on the supply side of
panelboards supplying branch circuits for pool equipment covered in Part II of this
article and on the load side of the service equipment or the source of a separately
derived system.
(A) Wiring Methods.
(1) Feeders. Feeders shall be installed in rigid metal conduit or intermediate
metal conduit. The following wiring methods shall be permitted if not subject to
physical damage:
(1) Liquidtight flexible nonmetallic conduit
(2) Rigid polyvinyl chloride conduit
(3) Reinforced thermosetting resin conduit
(4) Electrical metallic tubing where installed on or within a building
(5) Electrical nonmetallic tubing where installed within a building
(6) Type MC cable where installed within a building and if not subject to
corrosive environment
SECTION 4: Any person intentionally, knowingly, recklessly, or with criminal
negligence violating any of the provisions of this ordinance shall be
deemed guilty of a misdemeanor and upon conviction thereof shall be
fined an amount not to exceed two thousand dollars ($2,000). Each day
any such violation shall be allowed to continue shall constitute a separate
violation and be punishable hereunder.
SECTION 5: This Ordinance shall be cumulative of all provisions of the Code of
Ordinances of the City of North Richland Hills, except where the provisions
of this Ordinance are in direct conflict with the provisions of such ordinances
and such Code, in which event conflicting provisions of such ordinances and
such Code are hereby repealed.
SECTION 6: All rights and remedies of the City of North Richland Hills are expressly
saved as to any and all violations of the provisions of any ordinances in
the Code of Ordinances of the City of North Richland Hills that have
accrued at the time of the effective date of this Ordinance; and, as to such
accrued violations and all pending litigation, both civil and criminal,
whether pending in court or not, under such ordinances, same shall not
be affected by this Ordinance but may be prosecuted until final disposition
by the courts.
SECTION 7: It is hereby declared to be the intention of the City Council that the
phrases, clauses, sentences, paragraphs and sections of this ordinance
are severable, and if any phrase, clause, sentence, paragraph or section
Ordinance No.3611
Page 13 of 14
of this ordinance shall be declared unconstitutional by the valid judgment
or decree of any court of competent jurisdiction, such unconstitutionality
shall not affect any of the remaining phrases, clauses, sentences,
paragraphs and sections of this ordinance, since the same would have
been enacted by the City Council without the incorporation in this
ordinance of any such unconstitutional phrase, clause, sentence,
paragraph or section.
SECTION 8: This Ordinance shall be in full force and effect from and after its passage
and publication as required by law.
AND IT IS SO ORDAINED.
PASSED AND APPROVED on this 14th day of October, 2019.
CITY OF NORTH RICHLAND HILLS, TEXAS:
B
Y•
Rita Wright Oujesky M or ro Tern
ATTEST: kS``� :. . . . . v
h1-1k-A:t
Alicia RichardsokCCity SecrPtar• '
/i,;,,,i8i!l1ll 100
APPROVED AS TO FORM AND LEGALITY:
aleshia B. McGinnis, City Attorney
APPROVED AS TO CONTENT: •
Clayton Comstock, Planning Director
Ordinance No.3611
Page 14 of 14
Star-Telegram
MEDIA
Arlington Citizen-Journal I The Keller Citizen I La Estrella
Mansfield News-Mirror I Star-Telegram Northeast I Weatherford Star-Telegram
star-telegram.com 1 808 Throckmorton St.I Ft Worth,Tx.76102.8315
AFFIDAVIT OF PUBLICATION
Account# Ad Number Identification PO Amount Cols Deoth
600579 0004422945 CITY OF NORTH RICHLAND HILLS ORDINANCI ORDINANCE NO.3611 $90.68 I 1 51.00 Li
Attention: Traci Henderson THE STATE OF TEXAS
CITY OF NORTH RICHLAND HILLS County of Tarrant
PO BOX 820609
NORTH RICHLAND HILLS, TX 761820609 Before me, a Notary Public in and for
said County and State,this day
personally appeared VICTORIA
CITY OF NORTH RICHLAND HILLS RODELA, Bid and Legal Coordinator
ORDINANCE NO.3611 9
AN ORDINANCE OF THE CITY for the Star-Telegram, published b
COUNCIL OF THE CITY OF g p by
NORTH RICHLAND HILLS, the Star-Telegram, Inc. at Fort Worth,
TEXAS, AMENDING CHAPTER
98,ARTICLE VI,OF THE NORTH in Tarrant County,Texas;and who,
RICHLAND HILLS CODE OF OR-
DINANCES, ADOPTING THE after being duly sworn, did depose
2017 NATIONAL ELECTRICAL CITY OF NORTH RICHLAND HILLS and say that the attached clipping of
CODE AS AMENDED AS THE ORDINANCE NO.3611 Y Pp 9
OFFICIAL ELECTRICAL CODE OF AN ORDINANCE OF THE CITY an advertisement was ublished in
THE CITY OF NORTH RICHLAND COUNCIL OF THE CITY OF p
HILLS;AMENDING OTHER PRO- NORTH RICHLAND HILLS, the above named paper on the listed
VISIONS OF CHAPTER 98, AR- TEXAS, AMENDING CHAPTER
TICLE VI;PROVIDING A PENAL- 98,ARTICLE VI,OF THE NORTH dates:
TY;PROVIDING THAT THIS OR- RICHLAND HILLS CODE OF OR-
DINANCE SHALL BE CUMULA- DINANCES, ADOPTING THE
TIVE OF ALL ORDINANCES AND 2017 NATIONAL ELECTRICAL
REPEAL OF CONFLICTING PRO- CODE AS AMENDED AS THE
VISIONS; PROVIDING SAVINGS OFFICIAL ELECTRICAL CODE OF
CLAUSE; PROVIDING A THE CITY OF NORTH RICHLAND
SEVERABILITY CLAUSE; AND HILLS;AMENDING OTHER PRO- 2 Insertion(s)
PROVIDING AN EFFECTIVE VISIONS OF CHAPTER 98, AR-
DATE.
Any person intentionally,knowing- TICLE VI;PROVIDING A PENAL- Published On:
ly, recklessly, or with criminal TY PROVIDING THAT THIS OR- October 17,2019,October 18,2019
negligence violating any of the DINANCE SHALL BE CUMULA-
provisions of this ordinance TIVE OF ALL ORDINANCES AND
shall be deemed guilty of a mis- REPEAL OF CONFLICTING PRO-
demeanor and upon conviction VISIONS; PROVIDING SAVINGS
thereof shall be fined an amount VISIONS; PROVIDING A
not to exceed two thousand dol- CLAUSE; CLAUSE; AND
violation tion shall Each day we such PROVIDING AN EFFECTIVE
violation shall be allowed to
continue shall constitute a sep- DATE.
arate violation and be punisha- Any person intentionally,knowing-
ble hereunder. IY, recklessly, or with criminal
PASSED AND APPROVED on this negligence violating any of the
14th day of October,2019. provisions of this ordinance
CITY OF NORTH RICHLAND HILLS shall be deemed guilty of a mis-
By:/s/Rita Wright Oujesky_ demeanor and upon conviction
Rita Wright Oujesky, Mayor Pro thereof shall be fined an amount
Tern not to exceed two thousand dol-
ATTEST:/s/Alicia Richardson lars($2,000).Each day any such
Alicia Richardson,City Secretary violation shall be allowed to APPRO VED AS TO FORM AND LE- continue shall constitute a sep
Yoc/dL '�
GALITY: /5/ Maleshia B. arate violation and be unisha-
McGinnis ble hereunder. P VED
Maleshia B. McGinnis, City Attor- PASSED AND APPROVED on this
ney 14th day of October,2019. (Principal Clerk)
CITY OF NORTH RICHLAND HILLS
By:/s/Rita Wright Oujesky_ SUBSCRIBED AND SWORN TO
Rita Wright Oujesky, Mayor Pro
Tern BEFORE ME,THIS 18th day of
ATTEST:/s/ onia City O, ob- in the year of 2019
Alicia Richardson,City Secretary
APPROVED AS TO FORM AND LE- ,
GALITY: /s/ Maleshia B.
McGinnis
Maleshia B. McGinnis, City Attor-
ney Atli"
tar�Puhlir-
:: • "'•- AMBAR UZARRAGA
_w. My Notary ID#132031291
..��'•` Expires May 30,2023
Extra charge for lost or duplicate affidavits.
Legal document please do not destroy!