HomeMy WebLinkAboutOrdinance 3614 ORDINANCE NO. 3614
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF
NORTH RICHLAND HILLS, TEXAS, AMENDING CHAPTER 98,
ARTICLE VII, OF THE NORTH RICHLAND HILLS CODE OF
ORDINANCES, ADOPTING THE 2018 INTERNATIONAL FUEL
GAS CODE AS AMENDED AS THE FUEL GAS CODE OF THE
CITY OF NORTH RICHLAND HILLS; PROVIDING A PENALTY;
PROVIDING THAT THIS ORDINANCE SHALL BE CUMULATIVE
OF ALL ORDINANCES AND REPEAL OF CONFLICTING
PROVISIONS; PROVIDING SAVINGS CLAUSE; PROVIDING A
SEVERABILITY CLAUSE; AND PROVIDING AN EFFECTIVE
DATE.
WHEREAS, the City of North Richland Hills, Texas ("the City") is a home rule city acting
under its power adopted by the electorate pursuant to Article XI, Section 5
of the Texas Constitution and Chapter 9 of the Local Government Code;
and
WHEREAS, the International Fuel .Gas Code is developed by construction industry
professionals and adopted around the world as the model code based on
the best, most recent building science; and
WHEREAS, updates to the building codes are meant to track with changes in building
industry standards, practices, innovations, and technologies; and
WHEREAS, the North Richland Hills City Council desires to adopt the 2018 International
Fuel Gas Code with amendments recommended by the North Central
Texas Council of Governments and other local amendments in order to
better provide for the health, safety, and welfare of its residents, businesses
and their property, as well as all occupants and users of buildings and
structures within the community; and
WHEREAS, it is the policy of the City of North Richland Hills to update its building codes
every six years; and
WHEREAS, updated codes benefit North Richland Hills citizens by establishing
consistency of code adoptions with other local jurisdictions; ensuring the
best rating possible by the Insurance Services Organization (ISO);
Contributes to the city's good standing in FEMA's Community Rating
System (CRS) which enables discounted flood insurance rates for our
residents; and
Ordinance No.3614
Page 1 of 9
WHEREAS, the North Richland Hills Construction Code Appeals Board acting in its
capacity as the Construction Advisory Board on September 12th, 2019
reviewed and unanimously recommended the adoption of the 2018
International Fuel Gas Code with the amendments recommended by the
North Central Texas Council of Governments and other local amendments;
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF
NORTH RICHLAND HILLS, TEXAS:
SECTION 1: The City Council hereby finds the recitals above to be true and correct,
and such recitals are hereby incorporated into this Ordinance as if written
herein.
SECTION 2: THAT Chapter 98, Article VII, Section 98-284 of the North Richland Hills
Code of Ordinances be amended to read as follows:
Sec. 98-284. International Fuel Gas Code adopted.
The International Fuel Gas Code, 2018 Edition, as adopted by the International Code
Council, Inc., a copy of which is on file in the office of the city secretary, as amended by
the recommended amendments of the North Central Texas Council of Governments, as
modified by the city.technical code committee, a copy of which is also on file in the office
of the city secretary, is hereby adopted by reference and designated as the fuel gas code
of the city, the same as though such code were copied at length herein."
SECTION 3: THAT Chapter 98, Article VII, Section 98-285 of the North Richland Hills
Code of Ordinances be amended to read as follows:
Sec. 98-285. Amendments to the International Fuel Gas Code.
The following sections, paragraphs, and sentences of the 2018 International Fuel Gas
Code are hereby amended as follows:
**Section 101.1; change to read as follows:
101.1 Title. These regulations shall be known as the Fuel Gas Code of the City of North
Richland Hills, hereinafter referred to as "this code."
** Section 102.2; add an exception to read as follows:
Exception: Existing dwelling units shall comply with Section 621.2.
**Section 102.8; change to read as follows:
Ordinance No.3614
Page 2 of 9
102.8 Referenced codes and standards. The codes and standards referenced in this
code shall be those that are listed in Chapter 8 and such codes, when specifically
adopted, and standards shall be considered part of the requirements of this code to the
prescribed extent of each such reference. Where differences occur between provisions
of this code and the referenced standards, the provisions of this code shall apply.
Whenever amendments have been adopted to the referenced codes and standards, each
reference to said code and standard shall be considered to reference the amendments
as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical
Code as adopted.
**Section 304.10; change to read as follows:
304.10 Louvers and grilles. The required size of openings for combustion, ventilation
and dilution air shall be based on the net free area of each opening. Where the free area
through a design of louver, grille or screen is known, it shall be used in calculating the
size opening required to provide the free area specified. Where the design and free area
of louvers and grilles are not known, it shall be assumed that wood louvers will have 25-
percent free area and metal louvers and grilles will have 50-percent free area. Screens
shall have a mesh size not smaller than '/4 inch (6.4 mm). Nonmotorized louvers and
grilles shall be fixed in the open position. Motorized louvers shall be interlocked with the
appliance so that they are proven to be in the full open position prior to main burner
ignition and during main burner operation. Means shall be provided to prevent the main
burner from igniting if the louvers fail to open during burner start-up and to shut down the
main burner if the louvers close during operation.
**Section 304.11; change item #8 to read as follows:
304.11 Combustion air ducts. Combustion air ducts shall comply with all of the
following:
8. Combustion air intake openings located on the exterior of a building shall have the
lowest side of such openings located not less than 12 inches (305 mm) vertically from
the adjoining ground level or the manufacturer's recommendation, whichever is more
restrictive.
**Section 306.3; change to read as follows:
[M] 306.3 Appliances in attics. Attics containing appliances requiring access shall be
provided . . . (bulk of paragraph unchanged) . . . side of the appliance. The clear access
opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm),
and large enough to allow removal of the largest appliance. As a minimum, for access
to the attic space, provide one of the following:
1. A permanent stair.
Ordinance No.3614
Page 3 of 9
2. A pull down stair with a minimum 300 lb (136 kg) capacity.
3. An access door from an upper floor level.
4. Access Panel may be used in lieu of items 1, 2, and 3 with prior approval of the code
official due to building conditions.
Exceptions:
1. The passageway and level service space are not required where the appliance
is capable of being serviced and removed through the required opening.
2. Where the passageway is not less than ...(bulk of section to read the same).
**Section 306.5; change to read as follows:
[M] 306.5 Equipment and appliances on roofs or elevated structures. Where
equipment requiring access or appliances are located on an elevated structure or the roof
of a building such that personnel will have to climb higher than 16 feet (4877 mm) above
grade to access, an a permanent interior or exterior means of access shall be provided.
Permanent exterior ladders providing roof access need not extend closer than 12 feet
(2438 mm) to the finish grade or floor level below and shall extend to the equipment and
appliances' level service space. Such access shall . . . (bulk of section to read the same].
. . on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent
slope). ... (bulk of section to read the same].
**Section 306.5.1; change to read as follows:
[M] 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that
require service are installed on roofs having slopes greater than 4 units vertical in 12 units
horizontal and having an edge more than 30 inches (762 mm) above grade at such edge,
a catwalk at least 16 inches in width with substantial cleats spaced not more than 16
inches apart shall be provided from the roof access to a level platform at the appliance.
The level platform shall be provided on each side of the appliance to which access is
required for service, repair or maintenance. The platform shall be not less than 30 inches
(762 mm) in any dimension and shall be provided with guards. The guards shall extend
not less than 42 inches (1067 mm) above the platform, shall be constructed so as to
prevent the passage of a 21-inch-diameter (533 mm) sphere and shall comply with the
loading requirements for guards specified in the International Building Code.
**Section 306; add Section 306.7with exception and subsection 306.7.1 to read as
follows:
306.7 Water heaters above ground or floor. When the attic, roof, mezzanine or
platform in which a water heater is installed is more than eight (8) feet (2438 mm) above
Ordinance No.3614
Page 4 of 9
the ground or floor level, it shall be made accessible by a stairway or permanent ladder
fastened to the building.
Exception: A max 10 gallon water heater (or larger when approved by the code
official) is capable of being accessed through a lay-in ceiling and a water heater is
installed is not more than ten (10) feet (3048 mm) above the ground or floor level and
may be reached with a portable ladder.
306.7.1. Illumination and convenience outlet. Whenever the mezzanine or platform is
not adequately lighted or access to a receptacle outlet is not obtainable from the main
level, lighting and a receptacle outlet shall be provided in accordance with Section
306.3.1.
**Section 310.2; add a second paragraph to read as follows:
When a gas distribution system of corrugated stainless steel tubing (CSST) is installed
that does not have enhanced lightning protection properties or an outer conductive jacket
and/or a wire mesh layer that is electrically continuous designed to provide lightening
resistance, a notarized affidavit shall be filed with Tarrant County Records indicating that
non-lightning resistant CSST has been installed in the home. A copy of the filed affidavit
shall be provided to the City of North Richland Hills at the time of permit application.
**Section 401.5; add a second paragraph to read as follows:
Both ends of each section of medium pressure corrugated stainless steel tubing (CSST)
shall identify its operating gas pressure with an approved tag. The tags are to be
composed of aluminum or stainless steel and the following wording shall be stamped into
the tag:
"WARNING
1/2 to 5 psi gas pressure
Do Not Remove"
**Section 402.3; add an exception to read as follows:
Exception: Corrugated stainless steel tubing (CSST) shall be a minimum of 1/2" (18
EHD).
**Section 404.11.4; change to read as follows:
Steel risers connected to plastic piping shall be connected with approved anodeless
risers.
**Section 404.12; change to read as follows:
Ordinance No.3614
Page 5 of 9
404.12 Minimum burial depth. Underground piping systems shall be installed a
minimum depth of 18 inches (458 mm) top of pipe below grade.
**Section 404.12.1; delete in its entirety:
**Section 406.1; change to read as follows:
406.1 General. Prior to acceptance and initial operation, all piping installations shall be
inspected and pressure tested to determine that the materials, design, fabrication, and
installation practices comply with the requirements of this code. The permit holder shall
make the applicable tests prescribed in Sections 406.1.1 through 406.1.6 to determine
compliance with the provisions of this code. The permit holder shall give reasonable
advance notice to the code official when the piping system is ready for testing. The
equipment, material, power and labor necessary for the inspections and test shall be
furnished by the permit holder and the permit holder shall be responsible for determining
that the work will withstand the test pressure prescribed in the following tests.
**Section 406.4; change to read as follows:
406.4 Test pressure measurement. Test pressure shall be measured with a monometer
or with a pressure-measuring device designed and calibrated to read, record, or indicate
a pressure loss caused by leakage during the pressure test period. The source of
pressure shall be isolated before the pressure tests are made.
**Section 406.4.1; change to read as follows:
406.4.1 Test pressure. The test pressure to be used shall be no less than 3 psig (20
kPa gauge), or at the discretion of the Code Official, the piping and valves may be tested
at a pressure of at least six (6) inches (152 mm) of mercury, measured with a manometer
or slope gauge. For tests requiring a pressure of 3 psig, diaphragm gauges shall utilize
a dial with a minimum diameter of three and one half inches (3 '/2"), a set hand, 1/10
pound incrementation and pressure range not to exceed 6 psi for tests requiring a
pressure of 3 psig. For tests requiring a pressure of 10 psig, diaphragm gauges shall
utilize a dial with a minimum diameter of three and one-half inches (3 '/"), a set hand, a
minimum of 2/10 pound incrementation and a pressure range not to exceed 20 psi. For
welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches
water column pressure (3.48 kPa) (1/2 psi) and less than 200 inches of water column
pressure (52.2 kPa) (7.5 psi), the test pressure shall not be less than ten (10) pounds per
square inch (69.6 kPa). For piping carrying gas at a pressure that exceeds 200 inches of
water column (52.2 kPa) (7.5 psi), the test pressure shall be not less than one and one-
half times the proposed maximum working pressure.
Diaphragm gauges used for testing must display a current calibration and be in good
working condition. The appropriate test must be applied to the diaphragm gauge used
for testing.
Ordinance No. 3614
Page 6 of 9
**Section 406.4.2; replace section as follows:
406.4.2 Test duration. Test duration shall be held for a length of time satisfactory to the
Code Official, but in no case for less than fifteen (15) minutes. For welded piping, and for
piping carrying gas at pressures in excess of fourteen (14) inches water column pressure
(3.48 kPa), the test duration shall be held for a length of time satisfactory to the Code
Official, but in no case for less than thirty (30) minutes.
**Section 409.1; add Section 409.1.4 to read as follows:
409.1.4 Valves in CSST installations. Shutoff valves installed with corrugated stainless
steel (CSST) piping systems shall be supported with an approved termination fitting, or
equivalent support, suitable for the size of the valves, of adequate strength and quality,
and located at intervals so as to prevent or damp out excessive vibration but in no case
greater than 12-inches from the center of the valve. Supports shall be installed so as not
to interfere with the free expansion and contraction of the system's piping, fittings, and
valves between anchors. All valves and supports shall be designed and installed so they
will not be disengaged by movement of the supporting piping.
**Section 410.1; add a second paragraph and exception to read as follows:
Access to regulators shall comply with the requirements for access to appliances as
specified in Section 306.
Exception: A passageway or level service space is not required when the regulator
is capable of being serviced and removed through the required attic opening.
**Section 621.2; add exception as follows:
621.2 Prohibited use. Unvented room heaters shall not be used as the sole source of
comfort heating in a dwelling unit.
Exception: Existing approved unvented heaters may continue to be used in dwelling
units, in accordance with the code provisions in effect when installed, when approved
by the Code Official unless an unsafe condition is determined to exist as described in
Section 108.7.
**Section 624.1.1; change to read as follows:
624.1.1 Installation requirements. The requirements for water heaters relative to
access, sizing, relief valves, drain pans and scald protection shall be in accordance with
the International Plumbing Code."
Ordinance No.3614
Page 7 of 9
SECTION 4: Any person intentionally, knowingly, recklessly, or with criminal
negligence violating any of the provisions of this ordinance shall be
deemed guilty of a misdemeanor and upon conviction thereof shall be
fined an amount not to exceed two thousand dollars ($2,000). Each day
any such violation shall be allowed to continue shall constitute a separate
violation and be punishable hereunder.
SECTION 5: This Ordinance shall be cumulative of all provisions of the Code of
Ordinances of the City of North Richland Hills, except where the provisions
of this Ordinance are in direct conflict with the provisions of such ordinances
and such Code, in which event conflicting provisions of such ordinances and
such Code are hereby repealed.
SECTION 6: All rights and remedies of the City of North Richland Hills are expressly
saved as to any and all violations of the provisions of any ordinances in
the Code of Ordinances of the City of North Richland Hills that have
accrued at the time of the effective date of this Ordinance; and, as to such
accrued violations and all pending litigation, both civil and criminal,
whether pending in court or not, under such ordinances, same shall not
be affected by this Ordinance but may be prosecuted until final disposition
by the courts.
SECTION 7: It is hereby declared to be the intention of the City Council that the
phrases, clauses, sentences, paragraphs and sections of this ordinance
are severable, and if any phrase, clause, sentence, paragraph or section
of this ordinance shall be declared unconstitutional by the valid judgment
or decree of any court of competent jurisdiction, such unconstitutionality
shall not affect any of the remaining phrases, clauses, sentences,
paragraphs and sections of this ordinance, since the same would have
been enacted by the City Council without the incorporation in this
ordinance of any such unconstitutional phrase, clause, sentence,
paragraph or section.
SECTION 8: This Ordinance shall be in full force and effect from and after its passage
and publication as required by law.
AND IT IS SO ORDAINED.
PASSED AND APPROVED on this 14th day of October, 2019.
Ordinance No.3614
Page 8 of 9
CITY OF NORTH RICHLAND HILLS, TEXAS:
By:
Rita Wri h ujesky, yor o em
ATTEST: �`�� ?, . "° s�47,7,J
ti\ 't-
Alicia Richardson City Sef etary1 j
.
',////!/,1////milllII1'
APPROVED AS TO FORM AND LEGALITY:
aleshia B. McGinnis, City Attorney
APPROVED AS TO CONTENT:
Clayton omstock, Tanning Director
Ordinance No.3614
Page 9 of 9
Star-Telegram
MEDIA
Arlington Citizen-Journal I The Keller zen I La Estrella
Mansfield News-Mirror I Star-Ts •am Northeast I Weatherford Star-Telegram
star-telegram.com 1 808 Throckmorton St.1 Ft Worth,Tx.78102.8315
AFFIDAVIT OF PUBLICATION
Account it Ad Number Identification PO Amount ( Ccls Depth
600579 0004423004 CITY OF NORTH RICHLAND HILLS ORDINANC ORDINANCE NO.3614 $87.32 49.00 L i
Attention: Traci Henderson THE STATE OF TEXAS
CITY OF NORTH RICHLAND HILLS County of Tarrant
PO BOX 820609
NORTH RICHLAND HILLS. TX 761820609 Before me. a Notary Public in and for
said County and State,this day
personally appeared VICTORIA
CITY OF NORTH RICHLAND HILLS 9
ORDINANCE NO.3614 RODELA, Bid and Legal Coordinator
AN ORDINANCE OF THE CITY published by
ram
for the Star-Tele
COUNCIL OF THE CITY OF g p y
NORTH RICHLAND HILLS, the Star-Telegram, Inc. at Fort Worth,
TEXAS, AMENDING CHAPTER
98, ARTICLE VII, OF THE in Tarrant County,Texas;and who.
NORTH RICHLAND HILLS CODE
OF ORDINANCES, ADOPTING after being duly sworn, did depose
THE 2018 INTERNATIONAL
FUEL GAS CODE AS AMENDED and say that the attached clipping of
AS THE FUEL GAS CODE OF
THE CITY OF NORTH RICHLAND CITY OF NORTH RICHLAND HILLS an advertisement was published in
HILLS;PROVIDING A PENALTY; ORDINANCE NO.3614 the above named paper on the listed
PROVIDING THAT THIS ORDI- AN ORDINANCE OF THE CITY P P
NANCE SHALL BE CUMULATIVE COUNCIL OF THE CITY OF dates:
OF ALL ORDINANCES AND RE- NORTH RICHLAND HILLS,
PEAL OF CONFLICTING PROVI- TEXAS, AMENDING CHAPTER
SIONS; PROVIDING SAVINGS 98, ARTICLE VII, OF THE
CLAUSE; PROVIDING A NORTH RICHLAND HILLS CODE
SEVERABILITY CLAUSE; AND OF ORDINANCES, ADOPTING
PROVIDING AN EFFECTIVE THE 2018 INTERNATIONAL
DATE. FUEL GAS CODE AS AMENDED 2 Insertion(s)
Any person intentionally,knowing- AS THE FUEL GAS CODE OF
ly, recklessly, or with criminal THE CITY OF NORTH RICHLAND
negligence violating any of the HILLS;PROVIDING A PENALTY; Published On:
provisions of this ordinance PROVIDING THAT THIS ORDI-
shall be deemed guilty of a mis- October 17,2019,October 18,2019
demeanor and upon conviction NANCE SHALL BE CUMULATIVE
thereof shall be fined an amount OF ALL ORDINANCES AND RE-
not to exceed two thousand dol- PEAL OF CONFLICTING PROVI-
lars($2,000).Each day any such SIONS; PROVIDING SAVINGS
violation shall be allowed to CLAUSE; PROVIDING A
continue shall constitute a sep- SEVERABILITY CLAUSE; AND
arate violation and be punisha- PROVIDING AN EFFECTIVE
ble hereunder. DATE.
PASSED AND APPROVED on this Any person intentionally,knowing-
14th day of October,2019. ly, recklessly, or with criminal
CITY OF NORTH RICHLAND HILLS negligence violating any of the
By:/s/Rita Wright Ouiesky_ provisions of this ordinance
Rita Wright Oujesky, Mayor Pro shall be deemed guilty of a mis-
Tern demeanor and upon conviction
ATTEST:/s/Alicia Richardson thereof shall be fined an amount
Alicia Richardson,City Secretary not to exceed two thousand dol-
APPROVED AS TO FORM AND LE- lars($2,000).Each day any such
McGinn: /s/ Maleshia B. violation shall n allowed p- t /7
McGinnis continue shall constitute a sep-
Maleshia / ///
Maleshia B. McGinnis, City Attor- arate violation and be punisha- ,�
ney ble hereunder. �4-' ( �L
PASSED AND APPROVED on this (Principal Clerk)
14th day of October,2019.
CITY OF NORTH RICHLAND HILLS
By:/s/Rita Wright Oujesky_ SUBSCRIBED AND SWORN TO
Rita Wright Oujesky, Mayor Pro
Tern BEFORE ME, THIS 18th day of
ATTEST:/s/Alicia Richardson._.
Alicia Richardson,City Secretary 1rin the year of 20
APPROVED AS FORM AND LE-
GALITY: /s// B.Maleshia B.
McGinnis
Maleshia B. McGinnis, City Attor-
ney
ntary Public-
:t w AMBAR LIZARRAGA
My Notary ID#132031291
",t a.,,, Expires May 30,2023
. _r.
Extra charge for lost or duplicate affidavits.
Legal document please do not destroy!